ST0001-LR0210248908 Ambassador Row Ro n e E n g i n ee rs Dallas Texas 79247-4510 (214) 630A745 - (214) 630 -9819 (fez) CONCRETE COMPRESSIVE STRENGTH TEST Client: City of Coppell Attn: Ms. Susan Taylor - Engineering Dept PO Box 478 Coppell TX 75019 Project: Creekview Drive and Freeport Parkway Coppell, TX ( J Report No.: 161428 Project No.: 015729 Date of Service: 09 /25/2002 Report Date: 10/24/2002 Services: Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. PROJECT DATA CONTRACTOR: Infrastructure Services, Inc. CONCRETE SUPPLIER: Lattimore PLANT: 3 SPECIFICATION REQUIREMENTS STRENGTH: 4000 psi @ 28 Days SLUMP (in): 3 11 - 5" AIR (%): 3%-5% TEST METHOD: ASTM C -172 ASTM C -31 ASTM C -143 ASTM C -231 ASTM C -1064 ASTM C -138 MIX DESIGN I.D.: 4000PS1 PLACEMENT DATE: 09/25/2002 WEATHER CONDITIONS: Partly cloudy TIME SAMPLED: 4:20pm BATCH TIME: 3:30pm TEMPERATURE (F) -AIR 94 F CONCRETE: 86 F TRUCK NO: 972 TICKET NO: 3151241 Am CONTENT ( %): 3.5 UNIT WEIGHT (pcf): NA OVERALL PLACEMENT LOCATION: Paving SAMPLE LOCATION: Station 20+40, Station 17 +50, Station 9+00 east of Creekview Dr 9 Hold on standby until concrete arrived at 4:00pm per Billy with Infrastructure LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in fidl without the written approval of Rone Engineers, Inc. 01DK Page 1 of 2 ASTM e -39 REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" (area 28.27 sq. in.) CYLINDER MEASURED MAXIMUM COMPRESSIVE MARKED SLUMP DATE AGE LOAD STRENGTH FRACTURE SET NO. (Inches) TESTED (days) (Iba force) (psi) TYPE 1 1 4.0 10/02/2002 7 108600 3840 Unbonded Cap 1 2 4.0 10/23/2002 28 131115 4640 Unbonded Cap 1 3 4.0 10/23/2002 28 131110 4640 Unbonded Cap Average 4640 9 Hold on standby until concrete arrived at 4:00pm per Billy with Infrastructure LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in fidl without the written approval of Rone Engineers, Inc. 01DK Page 1 of 2 Report No.: 161428 Project No.: 015729 Client: City of Coppell RoneEngineers MSi Services. Technician: Damon McDonald Started: 1:00pm Finished: 5:4_` Report Distribution: (1) City of Coppell (1) City of Coppell (1) Infrastructure Services, Inc. (1) Schrickel, Rollins & Assoc., Inc. LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in fidl without the written approval of Rone Engineers, Inc. 01DK Page 2 of 2