Amberpoint BP 2-LR021108REPORT OF DAILY FIELD ACTIVITIES Report Number: 94021380.0055 Service Date: November 2, 2002 Client: Transwestern Commercial Services Attn: James Gaspard 5001 Spring Valley Rd Ste 600W Dallas TX 75244 Report Date: Project: Staples 201 Northpoint Coppell, TX Project Number: 94021380 'll'erracan 8901 Carpenter F~,vy, Ste #100 Dallas, Texas 75247 (214) 630-1010 November 08, 2002 Services: Daily field activities. On this date, a HBC-Terracon technician arrived at the above referenced jobsite as scheduled for observation of daily field activities. The following was observed and/or tested. HBC's technician observed the reconditioned and recompacted material placed in the building subgrade. In-place density tests will be performed at a later date. Technician: Bradford T. Rengstorff Report Distribution: (1) Transwestern Commercial Services (1) Hill & Wilkinson, Ltd. (1) O'Brien & Associates (1) TechniStructures (1) City of Coppell - Bldg Insp (1) City of Coppell - Constr Insp (1) Slate Farm Insurance (1) HBC Engineering Reviewed by: HBC~__.~ E~'~ Harbour Principal The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 1 of 1 ,~-SKS~-~,,K,~ REPORT OF DAILY FIELD ACTIVITIES Report Number: 94021380.0053 Service Date: November 1,2002 Client: Transwestern Commercial Services Attn: James Gaspard 5001 Spring Valley Rd Ste 600W Dallas TX 75244 Report Date: Project: Staples 201 Northpoint Coppell, TX Project Number: 94021380 lrerracan 8901 Carpenter Frwy, Ste #100 Dallas, Texas 75247 (214) 630-1010 November 08, 2002 Services: Daily field activities. On this date, a HBC-Terracon technician arrived at the above referenced jobsite as scheduled for observation of daily field activities. The following was observed and/or tested. HBC's technician observed the reconditioned and recompacted material placed in the building subgrade. In-place density tests will be performed at a later date. Technician: Bradford T. Rengstorff Report Distribution: (1) Transwestern Commercia~ Services (1) Hill & Wilkinson, Ltd (1) O'erien & Associates (1) TechniStruc{ures (1) City of Coppell - BIdg insp (1) City of Coppell - Constr Insp (1) State Farm insurance (1) HBC Engineering Reviewed by: H BC/Ter,,~,~/ Eugene our Principal The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 1 of 1 FIELD DENSITY TESTING Report Number: 94021380.0048 Service Date: October 30, 2002 Client: Transwestern Commercial Services Attn: James Gaspard 5001 Spring Valley Rd Ste 600W Dallas TX 75244 Report Date: Project: Staples 201 Northpoint Coppell, TX 'lrerracan 8901 Carpenter Frwy, Ste #100 Dallas, Texas 75247 (214) 630-1010 November 08, 2002 Project Number: 94021380 Material Information Material Laboratory No. Test Method Description and Classification Lab Test Data Proiect Requirements Optimum Max. Lab Water Water Dry Unit Content Minimum Dry Content Weight Range Unit Weight (%) (pc~ (%) (% compaction) 1. 213800010 ASTM D 698 Brown clay 22.7 98.7 =/> +3 93 Field Test Data Probe Water Dry Unit Dry Unit Test Lift/ Mat. Depth Content Weight Weight No. Test Location Elevation No. (inches) (%) (pcf) (% compaction) Moisture Conditioned Pad 613 Grid line A.2/10.8 6th 1 6 27.7 92.9 94 614 Grid line B/10.3 6th 1 6 28.1 93.6 95 615 Grid line B.8/10.7 6th 1 6 29.3 9117 93 616 Grid line C.6/10.2 6th 1 6 29.6 92.4 94 617 Grid line D.5/10.7 6th 1 6 28.2 93.5 95 618 Grid line E.4/10.3 6th 1 6 28.3 92.7 94 619 Grid line F.3/10.8 6th 1 6 29.2 91~5 93 620 Grid line G.2/10.2 6th 1 6 28.1 92.3 94 621 Grid line H/10.7 6th 1 6 27.4 94.1 95 622 Grid line H.8/10.3 6th 1 6 27.7 93.7 95 623 Grid line H.8/8.8 7th 1 6 26.9 95.1 96 624 Grid line H/8.3 7th 1 6 28.3 93.6 95 625 Grid line G.2/8.7 7th 1 6 28.6 94.6 96 626 Grid line F.3/8.2 7th 1 6 28.9 93.3 95 627 Grid line E.4/8.8 7th 1 6 27.7 93.1 94 628 Grid line D.5/8.3 7th 1 6 27.5 92.6 94 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This repod is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 1 of 2 ,FIELD DENSITY TESTING Client: Transwestern Commercial Services 'lrerracan Project Number:94021380 Report Number: 94021380.0048 Field Test Data Probe Water Dry Unit Dry Unit Test Lift/ Mat. Depth Content Weight Weight No. Test Location Elevation No. (inches) (%) (pct') (% compaction) 629 Grid line C.6/8.7 7th 1 6 27.6 92,7 94 630 Grid line B.8/8.2 7th 1 6 28.6 91.8 93 631 Grid line B/8.8 7th 1 6 28.9 93.0 94 632 Grid line A.2/8.3 7th 1 6 29.3 91.7 93 633 Grid line A.2/7.8 7th 1 6 28.7 92.4 94 634 Grid line B/7.2 7th I 6 28.4 92.8 94 635 Grid line B.8/7.7 7th 1 6 28.8 92.4 94 636 Grid line C.6/7.3 7th 1 6 29.2 91.7 93 637 Grid line D.5/7,8 7th 1 6 29.6 91.4 93 638 Grid line E.4/7.3 7th 1 6 29.1 91.9 93 639 Grid line F.3/7,7 7th 1 6 27.6 93.6 95 640 Grid line G,2/7.2 7th 1 6 28.1 92,1 93 641 Grid line H/7.8 7th 1 6 29.3 - 91,4 93 642 Grid line H.8/7.3 7th 1 6 29.4 91.6 93 Comments: Test results on this report meet project specification. Services - Perform in-place density and moisture content tests to determine degree of compaction and material moisture condition. Field Test Method~,STM D2922, ASTM D3017 Gauge ID: Field Results Reported To: Hill & Wilkinson Technician: Bradford T. Rengstorff Report Distribution: (1) Transwestem Commercial Services (1) City of CoppeJl - Bldg lnsp (1) Hill & Wilkinson, Ltd. (1) City of Coppell - Constr Insp (1) O'Brien & Associates (1) State Farm Insurance (1) TechniStructures (1) HBC Engineering Reviewed by: ,..E~ne Harbour Principal The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 2 of 2 x ,FIELD DENSITY TESTING Report Number: 94021380,0050 Service Date: October 31,2002 Client: Transwestern Commercial Services .Attn: James Gaspard 5001 Spring Valley Rd Ste 600W Dallas TX 75244 Report Date: Project: Staples 201 Northpoint Coppell, TX 'lrerracan 8901 Carpenter Frwy, Ste #100 Dallas, Texas 75247 (214) 630-1010 November 08, 2002 Project Number: 94021380 Material Information Material Laboratory No, Test Method Description and Classification Lab Test Data Proiect Requirements. Optimum Max. Lab Water Water Dry Unit Content Minimum Dry Content Weight Range Unit Weight (%) (PC0 (%) (% compaction) 1. 213800010 ASTM D698 Brown clay 22.7 98.7 =/> +3 93 Field Test Data Test Lift/ No. Test Location Elevation Probe Water Dry Unit Dry Unit Mat. Depth Content Weight Weight No. (inches) (%) · (pct") (% compaction) Moisture Conditioned Pad 643 Grid line A.2/10.2 7th 1 6 27~3 93.4 95 644 Grid line B/10.8 7th 1 6 28.2 92,6 94 645 Grid line B.8/10.2 7th 1 6 28.4 92.3 94 646 Grid line C.6/10.8 7th 1 6 29.2 91.7 93 647 Grid line D.5/10.3 7th 1 6 29.1 91.9 93 648 Grid line E.4/10.8 7th 1 6 28.6 92.7 94 649 Grid line F.3/10.2 7th 1 6 27.3 93.6 95 650 Grid line G.2/10,8 7th I 6 27.8 92.3 94 651 Grid line H/10.3 7th 1 6 28.1 92.8 94 652 Grid line H.8/10.8 7th 1 6 29.4 91.6 93 653 Grid line H.8/9.2 7th I 6 26.9 94.8 96 654 Grid line H/9.8 7th 1 6 28.3 92.3 94 655 Grid line G.2/9.2 7th 1 6 28.4 92.0 93 656 Grid line F.3/9.7 7th 1 6 27.3 93.2 94 657 Grid line E.4/9.3 7th 1 6 28.2 93.4 95 658 Grid line D.5/9.8 7th 1 6 29.3 91.5 93 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This repod is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 1 of 2 .~-~s~o7-.~., ~,y ~:IELD DENSITY TESTING Client:Transwestern Commercial Services lrerracan Project Number:94021380 Report Number: 94021380.0050 Field Test Data Test Lift/ No. Test Location Elevation Probe Water Dry Unit Dry Unit Mat. Depth Content Weight . Weight No. (inches) (%) (pcf') (% compaction) 659 Grid line C.7/9,2 7th 1 6 29.1 91.7 93 660 Grid line B.8/9.7 7th 1 6 27.2 92.6 94 661 Grid line B/9,3 7th 1 6 27,6 93.9 95 662 Grid Iine A.2/9,8 7th 1 6 28.2 92.5 94 Comments: Test results on this report meet project specification. Services - Perform in-place density and moisture content tests to determine degree of compaction and material moisture condition. Field Test Method~,STM D2922, ASTM D3017 Gauge ID: Field Results Reported To: Hill & Wilkinson Technician: Bradford T. Rengstorff Report Distribution: (1) Transwestern Commercial Services (1) City of Coppell - Bldg Insp (1) Hill & Wilkinson, Ltd. (1) City of Coppell - Constr Insp (1) O'Brien & Associates (1) State Farm Insurance (1) TechniStructures (1) HBC Engineering Reviewed by: Eu ' our Principal The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 2 of 2 FIELD DENSITY TESTING Report Number: 94021380.0054 Service Date: November 1, 2002 Client: Transwestem Commercial Services Attn: James Gaspard 5001 Spring Valley Rd Ste 600W Dallas TX 75244 Report Date: Project: Staples 201 Northpoint Coppell, TX 'lrerracon 8901 Carpenter Frwy, Ste #100 Dallas, Texas 75247 (214) 630-1010 November 08, 2002 Project Number: 94021380 Material Information Lab Test Data Project Requirements Optimum Max. Lab Water Water Dry Unit Content Minimum Dry Material Laboratory Content Weight Range Unit Weight No. Test Method Description and Classification (%) (pcf) (%) (% compaction) 1. 213800035 ASTM D 698 Dk brown clay (lime treated) 19.4 99.4 -1/+3 95 2. 213800036 ASTM D 698 Lt brown silty clay (lime treated) 20.2 100.6 -1/+3 95 Field Test Data Probe Water Dry Unit Dry Unit Test Lift/ Mat. Depth Content Weight Weight No, Test Location Elevation No. (inches) (%) (pct~ (% compaction) Lime Treated Subgrade 663 Grid line A.2/1.8 8th/Final 1 6 22.1 96.6 97 664 Grid line B/1.3 8th/Final 1 6 21.9 95.8 96 665 Grid line B.8/1.7 8th/Final 1 6 21.7 95.2 96 666 Grid line C.7/1.2 8th/Final 1 6 21.4 94.9 95 667 Grid line D.6/1.8 8th/Final 2 6 22.8 95.9 95 668 Grid line E,5/1.2 8th/Final 2 6 22.4 96.3 96 669 Grid line F.4/1.7 8th/Final 2 6 21.8 97.4 97 670 Grid line G.2/1.3 8th/Final 2 6 21.6 96.7 96 671 Grid line H/1.8 8th/Final 2 6 21.7 96.2 96 672 Grid line H.8/1.2 8th/Final 2 6 20.8 97.3 97 673 Grid line H.8/2.8 8th/Final 2 6 21.9 97.1 97 674 Grid line H/2.2 8th/Final 2 6 22.3 97.8 97 675 Grid line G.2/2.7 8th/Final 2 § 21.7 97.1 97 676 Grid line F.4/2.3 8th/Final 2 6 20.7 98.1 98 677 Grid line E.5/2.8 8th/Final 2 6 20.6 96.3 96 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 1 of 2 o~-.~.~o~-,.~,o,~,~ · FIELD DENSITY TESTING Client: Transwestern Commercial Services Field Test Data Test No. Test Location Z-DC 'll'erracan Project Number:94021380 Report Number: 94021380.0054 Probe Water Dry Unit Dry Unit Lift/ Mat. Depth Content Weight Weight Elevation No. (inches) (%) (pcf) (% compaction) 678 Grid line D.6/2.2 8th/Final 1 6 19.8 94.9 95 679 Grid line C.7/2.7 8th/Final 1 6 20.9 95.7 · 96 680 Grid line B.8/2.3 8th/Final 1 6 21.6 95.9 96 681 Grid line B/2.7 8th/Final 1 6 21.4 96.1 97 682 ' Grid line A.2/2.2 8th/Final 1 6 22.0 94.8 95 Comments: Test results on this report meet project specification. Services - Perform in-place density and moisture content tests to determine degree of compaction and material moisture condition. Field Test Method~,STM D2922, ASTM D3017 Gauge ID: Field Results Reported To: Wier Bros. Technician: Bradford T. Rengstorff Report Distribution: (1) Transwestern Commercial Services (1) City of Coppell * BIdg [nsp (1) Hill & Wilkinson, Ltd. (1) City of Coppell - Constr Insp (1) O'Brien & Associates (1) State Farm Insurance (1) TechniStructures (1) HBC Engineering Reviewed by: HBC~er~.~'~' E~gene Harbour Principal The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 2 of 2 ~;.~.~.,.~. ~ Z X