SS9901A-LR020919FIELD DENSITY TESTING
Report Number: 94021187.0~08
Service Date: September 13, 2002
Client: St. Joseph Village, Inc.
Attn: Joseph Dingman
13223 Glad Acres Drive
Dallas TX 75234
Report Date:
8901 Carpenter Frwy., Suite #100
Dallas, Texas 75247
(214) 630-!010
September 19, 2002
Project: St. Joseph Village
1201 East Sandy Lake Rd
Coppell, TX 75019
Project Number: 94021187
Material Information
Material Laboratory
No. Test Method
Description and Classification
1. 211870001 ASTM D 698 Med brown silty clay w/gravel
Lab Test Data Project Requirements
Optimum Max. Lab Water
Water Dry Unit Content Minimum Dry
Content Weight Range Unit Weight
(%) (pcf) (%) (% compaction)
17.6 107.9 -1/+3 95
Field Test Data Probe
Test LiftJ Mat. Depth
No. Test Location Elevation No. (inches)
Water Line Backfill, W Side Tie-In
793 3' N & 10' E of Manhole @ Std. 1+10 4'BEG 1 6
794 3' N & 15' E of Manhole @ Std. 1+10 3'BEG 1 6
795 3' N & 17' E of Manhole @ Sta..l+lO 2' BEG 1 6
796 3' N & 19' E of Manhole @ Std. 1+10 1' BEG 1 6
797 3' N & 20' E of Manhole @ Std. 1+10 Final 1 6
30" Force Main Line Backfill
798 Std. 0+95 4' BEG 1 6
799 Std. 0+98 3' BEG 1 6
800 Std. 1+00 2' BEG I 6
801 Std. 1+05 1' BEG I 6
802 Std. 1+10 Final 1 6
Datum: BEG -- Below existing Grade
Water Dry Unit Dry Unit
Content Weight Weight
(%) (pcf) (% compaction)
16.9 108.2 100
17.4 107.7 100
19.3 105.2 97
18.7 105.7 98
18.4 104.1 96
18.9 106.1 98
19.2 105.8 98
19.7 105.0 97
18.4 106.4 99
17.9 108.1 100
Comments:
Test results on this report meet project specification.
Services - Perform in-place density and moisture content tests to determine degree of compaction and material moisture
condition.
Field Test Method:ASTM D2922, ASTM D3017
Gauge ID: 2077
Field Results Reported To: Contractor
Technician: Bryan C. Hughes
Report Distribution: /'~ HBc Engineeri~
(1) St. Joseph Village, Inc. (1) City of Coppell Engineering ~J~. ~
(1) Agui~'e ColTJoratJon (1)SI Andrews Management Reviewed by: ~ L._~do~, Jj, _C~}~, P.E.r
(1) Centex - Jobsite (1) SI Andrews Management
(1) City of Coppell - Bldg Insp . i.,nnc~paLl=Tinasr
The tests were performed in general accon:lanca with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively fl~4he use of the client
indicated above and shall not be reproduced except In full without the written approval of Terracon. Test results transmitted herein are only applicable
to the actual samples tested at the Inca~n(s) referenced and are not nec~__~_~ri_ ly IodicaUve of the ~ of other apparently similar er identical
materials.