Amberpoint BP 2-LR021110?REPORT OF SOIL-LIME MIXTURE PULVERIZATION ll'etracan 8901 Ca.enter Frwy., Suite #100 Dallas. Texas 75247 Date of Service: Client No.: Client: 11/10/02 3181 Transwestern Commercial Services 5001 Spring Valley Rd Ste 600W Dallas, TX 75244 Report No.: Project No.: Project: 94021380.0076 94021380 Staples 201 Northpoint Coppell, TX Contractor: Test Location: Wier Bros. Lines A to J and 3 to 4 Test Method: NTCOG Specification Requirements: Minimum Passing I 3/4" Sieve: 100% Minimum Passing #4 Sieve: , 60% Sample Condition: Field Moist TEST LOCATION 1-3/4" SIEVE #4 SIEVE NO. % PASSING % PASSING 1 Grid line A.2/4.5 100 63 2 Grid line B/4.8 100 62 3 Grid line B.8/4.2 100 53* 4 Grid line C.7/4.8 100 66 5 Grid line D.6/4.5 100 64 6 Grid line E.5/4.2 100 48* 7 Grid line F.4/4.8 100 60 8 Grid line G.2/4.5 100 64 9 Grid line H/4.2 100 51' 10 Grid line H.8/4.5 100 63 11 Grid line A.2/3.2 100 62 12 Grid line B/3.5 100' 63 13 Grid line B.8/3.8 100 52* 14 Grid line C.7/3.2 100 64 15 Grid line D.6/3.5 100 63 16 Grid line E.5/3.8 100 51' 17 Grid line F.4/3.2 100 62 18 Grid line G.2/3.5 100 61 19 Grid line 1-[/3.8 100 48* 20 Grid line H.8/3.5 100 66 *Does not meet specification requirements. Technician: B. Rengstorff Report Distribution: (1) Transwestern Commercial Services (1) Hill & Wilkinson, Ltd. (1) O'Brien & Associates (1) Technistructures (1) City of Coppell - Bldg. Insp. (1) City of Coppell - Constr. Insp. (1) State Farm insurance (1) HBC Engineering - Project File (1) Carter & Burgess 309 lrerracon Eugene Harbour Principal This report is exclusively for the use of the client indicated above and shall not be reproduced in full without written approval of HBC/Terracon. z x