Amberpoint BP 2-LR021109REPORT OF SOIL-LIME MIXTURE PULVERIZATION
ll'erracan
Consulting Engineers 8, Scientists
8901 Carpenter Frwy., Suite #100
Dallas. Texas 75247
Date of Service:
Client No.:
Client:
11/09/02
3181
Transwestern Commercial Services
5001 Spring Valley Rd Ste 600W
Dallas, TX 75244
Report No.:
Project No.:
Project:
Page No.:
94021380.0075
94021380
Staples
201 Northpoint
Coppell, TX
1 of 2
Contractor:
Test Location:
Wier Bros.
Lines A to J and 5 to 8
Test Method: NTCOG'
Specification Requirements:
Minimum Passing I 3/4" Sieve: ]00%
Minimum Passing #4 Sieve: 60%
sample Condition: Field Moist
1-3/4" SIEVE #4 SIEVE
TEST LOCATION
NO. % PASSING % PASSING
1 Grid line A.2/8.5 100 66
2 Grid line B/8.3 100 67
3 Grid line B.8/8.8 100 68
4 Grid line C.7/8.5 100 65
5 Grid line D.6/8.2 100 68
6 Grid line E.5/8.7 100 66
7 Grid line F.4/8.5 100 64
8 Grid line G.2/8.5 100 64
9 Grid line H/8.7 100 65
10 Grid line H.8/8.3 100 66
11 Grid line A.2/7.5 100 67
12 Grid line B/7.3 100 65
13 Grid line B.8/7.8 100 64
14 Grid line C.7/7.5 100 63
15 Grid line D.6/7.3 100 62
16 Grid line E.5/7.8 100 66
17 Grid line F.4/7.5 100 66
18 Grid line G.2/7.5 100 64
19 Grid line 1-1/7.2 100 65
20 Grid line H.8/7.7 100 64
21 Grid line A.2/6.5 100 66
22 Grid line B/6.3 100 67
23 Grid line B.8/6.8 100 63
24 Grid line C.7/6.5 100 65
25 Grid line D.6/6.2 100 64
(continued on next page)
309 This report is exclusively for the use of the client indicated above and shall not be reproduced, in full without written approval of HBC/Terracon.
'REPORT OF SOIL-LIME MIXTURE PULVERIZATION
'lretracan
Dallas. Texas 75247
Date of Service:
Client No.:
Client:
'11/09/02
3181
Transwestern Commercial Services
5001 Spring Valley Rd Ste 600W
Dallas, TX 75244
Report No.: 94021380.0075
Project No.: 94021380
Project: Staples
201 Northpoint
Coppell, TX
Page No.: 2of2
Contractor:
Test Location:
Wier Bros.
Lines A to J and 5 to 8
Test Method: NTCOG
Specification Requirements:
Minimum Passing 1 3/4" Sieve: 100%
Minimum Passing #4 Sieve: 60%
Sample Condition: Field Moist
1-3/4" SIEVE #4 SIEVE
TEST LOCATION
NO. % PASSING % PASSING
26 Grid line E.5/6.3 100 65
27 Grid line F.4/6.4 100 66
28 Grid line G.2/6.5 100 64
29 Grid line 1-I/6.7 100 64
30 Grid line H.8/6.5 100 66
31 Grid line A.2 100 68
32 Grid line B 100 64
33 Grid line B.8 100 63
34 Grid line C.7 100 67
35 Grid line D.6 100 64
36 Grid line E.5 100 66
37 Grid line F.4 100 63
38 Grid line G.2 100 64
39 Grid line H 100 64
40 Grid line H.8 100 65
Technician: B. Rengstorff
Report Distribution:
(1) Transwestern Commercial Services
(1) Hill & Wilkinson, Ltd.
(1) O'Brien & Associates
(1) TechniStructures
(1) City of Coppell - Bldg. Insp,
309
(1) City of Coppell - Constr. Insp.
(1) State Farm Insurance
(1) HBC Engineering - Project File
(1) Carter & Burgess
ll'erracon
Eugene Harbour
Principal