Amberpoint BP 2-LR021209 (2)REPORT OF CONCRETE BATCH PLANT OBSERVATION 'Report Number: 94021380.0129 Service Date: November 25, 2002 'll'erracan 8901 Carpenter Frwy, Ste #100 Dallas, Texas 75247 (214) 630-1010 Client: Transwestern Commercial Services Attn: James Gaspard 5001 Spring Valley Rd Ste 600W Dallas TX 75244 Report Date: December 09, 2002 Project: Staples 201 Northpoint Coppell, TX Project Number: 94021380 Services: Concrete batch plant observation. On this date, a HBC/Terracon technician arrived at the above referenced jobsite as scheduled for concrete batch plant observaiton. See the attached sheet(s) for recorded data. Technician: Barry M. Cuble Repod Distribution: (1) Transwestern Commercial Services (1) Hill & Wilkinson, Ltd. (1) O'Brien & Associates (1) TechniStructures (1) City of Coppell- Bidg Insp (1) City of Coppell - Constr Insp (1) State Farm Insurance (1) HBC Engineering Reviewed by: HBCFFe.~~ Eugene Harbour Principal The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. ' · Page 1 of 1 ,~-sKs~-r~, ~D C) 0 REPORT OF DRILLED PIER OBSERVATION Report Number: 94021380.0127 Service Date: November 25, 2002 lrerracan 8901 Carpenter Frwy, Ste #100 Dallas, Texas 75247 (214) 630-1010 Client: Transwestern Commercial Services Attn: James Gaspard 5001 Spring Valley Rd Ste 600W Dallas TX 75244 Report Date: December 09, 2002 Project: Staples 201 Northpoint Coppell, TX Project Number: 94021380 Services: Drilled pier observation On this date, a HBCfTerracon technician arrived at the above referenced jobsite as scheduled for drilled pier observation. See the attached sheet(s) for recorded data. NOTE: Pier J/1.30 was concreted level with the soil. Technician: Bradford T. Rengstorrf Repod Distribution: (1) Transwestern Commercial Services (1) Hill & Wilkinson, Ltd. (1) O'Brien & Associates (1) TechniStructures (1) City of Coppell - BIdg Insp (1) City of Coppell - Constr Insp (1) State Farm Insurance (1) HBC Engineering Reviewed by: H B C/Te,~/~' Euger~e Harbour Principal The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This repod is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 1 of 1 iii LU