Stratford Manor-LR 990727FUGRO SOUTH, INC.
2880 Virgo Lane; Dallas, Texas 75229
Ph (972) 484-8301; Fax (972) 620-7328
COMPRESSIVE STRENGTH OF CONCRETE REPORT
CLIENT: Huie Construction Co. Report Date: July 27, 1999
PROJECT: Stratford Manor, Coppell, Texas Project No.: 0791-2064
SAMPLE DATE: June 28, 1999
CONTRACTOR:
TICKET NO.:
AMBIENT TEMP. (°F):
CONCRETE TEMP. (°F) (ASTM C-1064):
TIME BATCHED:
TIME SAMPLED:
WEATHER CONDITION:
LOCATION OF PLACEMENT:
CONCRETE SUPPLIER:
PLANT/TRUCK:
MIX ID NUMBER:
AIR (%) (ASTM C-231):
WATER ADDED (gal):
SLUMP (in.) (ASTM C-'143):
Stratford Lane, inlet at station 9+00
CONCRETE CYLINDER COMPRESSIVE STRENGTH TESTS
Standard 6" x 12", 28.27 square inches
TOTAL COMPRESSIVE SPECIFIED COMPRESSIVE
CYLINDER AGE DATE LOAD STRENGTH STRENGTH
NUMBER (days) TESTED (pounds) (psi) (psi)
SMC 17 7 7-05-99 122000 4320 3500/28 days
SMC 18 28 7-26-99 152000 5380
SMC 19 28 7-26-99 149000 5270
SMC 20 Hold Fracture mode is (A) unless otherwise noted
Specifications: Making & ASTM C-31 Testing ASTM C-143, Typesof [~ [~ [~ [-~
Curing: Methods: ASTM C-39 Fracture: A B C D
REMARKS: Cylinders cast by Contractor. All information except test data furnished by Contractor and assumed
to be correct.
Technician:
William Granger
FUGRO SOUTH INC.
Reviewed ~
SMH/bg
Distribution: Huie Construction Co. - David A. Whitsett
Alton Loyd, Inc. - Preston Skaggs