Wynnpage Plaza-LR021024FIELD DENSITY TESTING
Report Number: 94021373.0004
Service Date: October 14, 2002.
ENGINEERt~3
8901 Carpenter Frwy., Suite #100
Dallas, Texas 75247
(214) 630-1010
Client; Pacific Builders Inc
^ttn: Charles Coleman
3360 Wiley Post Rd Ste 100
Carrollton TX 75006
Report Date: October 24, 2002
Project: Wynnpage
255 Denton Tap
Coppell, TX
Project Number: 94021373
Material Information
Material Laboratory
No. Test Method
Description and Classification
Lab Test Data Project Requirements
Optimum Max. Lab Water
Water Dry Unit Content Minimum Dry
Content Weight Range Unit Weight
(%) (pcf) (%) (% compaction)
1. 213730001 ASTM D 698
2. 213730002 ASTM D 698
Field Test Data
Test
No.
Brown & dk brown silty clay
Reddish brown & tan clayey sand
Test Location
20.7 102.0 Opt/+5 95
12.0 116.8 -3/+3 95
Building Pad Subgrade
1 30' S & 50' E of NW corner of building
2 40' N & 30' E of SW corner of building
Parking Lot Subgrade
3 15' S & 30' W of SE corner of building
4 40' N & 25' W of SW corner of building
5 40' N & 75' W of SW corner of building
Building Pad Subgrade
6 Retest of #1
7 Retest of #2
Probe Water Dry Unit Dry Unit
Lift/ Mat. Depth Content Weight Weight
Elevation No. (inches) (%) (pcO (% compaction)
At Grade 2 6 18.7 * 104.8 90 *
At Grade 2 6 16.8 * 107.4 92 *
At Grade 1 6 20.9 104.2 100+
At Grade 1 6 21,2 99.9 98
At Grade 1 6 21.7 100.7 99
2 6 12.8 112.4 96
2 6 11.9 114.7 98
Comments:
An asterisk (*) appears next to test results which do NOT meet the project specifications.
Services - Perform in-place density and moisture content tests to determine degree of compaction and material moisture
condition.
Field Test Method;ASTM D2922, ASTM D3017
Gauge ID:
Field Results Reported To: Contractor
Technician: Bradford T. Rengstorff
Report Distribution:
(1) Pacific Builders 10c
(1) City of Coppe{I Engineering
Reviewed by:
H~neering
Hussei~'H'~ Abusaad, P.E.
Senior Project Manager
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
matedals.
Page 1 of 1 ,~-~Lw~-~,.~.~