Amberpoint BP 2-LR030128STATISTICAL ANALYSIS OF CONCRETE MIXTURES
· Report Number: 94021380,0217
Service Date: January 28, 2003
'lrerracon
8901 Carpenter Frwy, Ste #100
Dallas, Texas 75247
(214) 630-1010
Client: Transwestern Commercial Services
Attn: James Gaspard
5001 Spring Valley Rd Ste 600 W
Dallas TX 75244
Report Date:
Project: Staples
201 Northpoint
Coppell, TX
Januaw 28,2003
Project Number: 94021380
Specification Requirements:
Concrete Class: 7753
PROJECT DATA
4500 psi @ 28 Days
REPORT OF TESTS
Number Air Concrete Compressive Running
Report Of Slump Content Temp Strength 3 Test Avg
Date Number Set Samples (in.) (%) (F) PSI PSI
11/25/2002 94021380.0124 1 2 5.00 5.0 43 6255
11/25/2002 94021380.0124 2 2 4.75 5.2 52 6185
11/25/2002 94021380.0124 3 2 5.00 4.8 52 5900 6113
11/25/2002 94021380.0124 4 2 5.00 5.0 56 5610 5898
11/25/2002 94021380.0124 5 2 5.00 4.9 57 6415 5975
12/02/2002 94021380.0135 1 2 5.00 5.0 60 4915 5647
12/02/2002 94021380.0135 2 2 5.00 5.2 62 4520 5283
12/02/2002 94021380.0135 3 2 5,00 5.3 63 4650 4i~95
12/02/2002 94021380.0135 4 2 4.50 5.2 64 5400 4857
12/16/2002 94021380.0155 1 2 5.00 5.7 69 5515 5188
12/16/2002 94021380.0155 2 2 5.50 7.0 68 4605 5173
12/16/2002 94021380.0155 3 2 5.75 7.2 68 4330 4817
12/16/2002 94021380.0155 4 2 5.50 5.5 67 4590 4508
12/16/2002 94021380.0155 5 2 5.75 7.4 68 4505 4475
12/16/2002 94021380.0155 6 2 5.00 6.9 69 4615 4570
12/17/2002 94021380.0159 I 2 5,50 7.0 66 43,70 4497
12/17/2002 94021380.0159 2 2 6.8 69 4705 4563
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.
Page 1 of 2 t$./R11.Futu,eKe¥
STATISTICAL ANALYSIS OF CONCRETE MIXTURES
Client: Transwestern Commercial Services
'lrerracon
Project Number: 94021380
Report Number: 94021380.0217
Number
Report Of Slump
Date Number Set Samples (in.)
12/17/2002 94021380.0159 3 2 5.50
12/17/2002 94021380.0159 4 2 5.00
Air Concrete Compressive Running
Content Temp Strength 3 Test Avg
(%) (F) PSI PSI
5.5 72 5655 4910
8.0 66 4585 4982
Technician: Eugene Harbour
Report Distribution:
(1) Transwestem Commercial Services
(1) O'Brien & Assoc
(1) Hill & Wilkinson LTD
(1) TechniStructures
(2) Carter & Burgess Inc
(1) City of Coppell - Constr Insp
(1) City of Coppeti - Bldg Insp
(1) HBC Engineering Inc
Reviewed by;
HBC/Te~
Eugene Harbour
Principal
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in fulI without the written approval of Terracon. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials,
Page 2 of 2 ,,.,.,,.,,,.,. K.~
PROJECT: -~ 1'/~' 'pl~.S , Page of
JOB NO.C~q~3'~3<~°'OI~/ Date t~/l~/o~ Comp. By CHECKED BY:
po rc
q
o o
~.D e'~
0
E