Amberpoint BP 2-LR030127FIELD DENSITY TESTING
Report Number: 94021380.0189
Service Date: January 9, 2003
/'lretr con
8901 Carpenter Fnmj, Ste #100
Dallas, Texas 75247
(214) 630-1010
Client: Transwestern Commercial Services
Attn: James Gaspard
5001 Spring Valley Rd Ste 600 W
Dallas TX 75244
~e: January 27, 2003
Proje~
-'~"~ppell, TX
Project Number: 94021360
Material Information
Material Laboratory
No. Test Method
Description and Classification
Lab Test Data Project Requirements
Optimum Max. Lab Water
Water Dry Unit Content Minimum Dry
Content Weight Range Unit Weight
(%) (pc0 (%) (% compaction)
1. 213800010 ASTM D 698 Brown clay
22.7 98.7 -1/+3 95
Field Test Data Probe
Test LiffJ Mat. Depth
No. Test Location Elevation No. (inches)
Paving, Parking Lot, Fire Lane, Approach
Subgrade
958 100' E of grid line D/1 at Grade 1 6
959 100' E of grid line BI1 at Grade 1 6
960 15' S and 175' E of grid line N1 at Grade 1 6
961 15' S and 75' E of grid line A/1 at Grade 1 6
962 10' E of drainage inlet adjacent to grid line at Grade 1 6
C.5/1
963 Retest of #962, dated 01/09/03 I 6
Water Dry Unit Dry Unit
Content Weight Weight
(%) (pct') (% compaction)
21.9 99.2 100+
23.6 97.3 99
24.8 96.4 98
25.2 95.2 96
28.6 * 89.7 91 *
25.4 93.9 95
Comments:
An asterisk (*) appears next to test results which do NOT meet the project specifications.
Services - Perform in-place density and moisture content tests to determine degree of compaction and material moisture
condition.
Field Test Method:ASTM D2922, ASTM D3017
Gauge ID:
Field Results Reported To: Bryan w/Hill & Wilkinson
Technician: Bradford T. Rengstorff
Report Distribution:
(1) Transwestern Commercial Services (2) Carter & Burgess Inc
(1) O'Bden &Assoc (1) City of Coppell - Bldg Insp
~~~ HBC/Ter~~
ed by:
(1) HEll & Wilkinson LTD (1) City of Coppell - Constr Insp Eugene Harbour
(1) TechniStructures (1) Staples Inc Principal
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.
Page 1 of I