Loading...
Amberpoint BP 2-LR030203FIELD DENSITY TESTING Report Number: 94021380.0204 Service Date: January 21, 2003 'lrerracan 8901 Carpenter Frwy, Ste #100 Dallas, Texas 75247 (214) 630-1010 Client: Transwestern Commercial Services Attn: James Gaspard 5001 Spring Valley Rd Ste 600 W Dallas TX 75244 Report Date: Project: Staples 201 Northpoint Coppell, TX Project Number: 94021380 February 03, 2003 Ma terial Information Material Laboratory No. Test Method Description and Classification Lab Test Data Project Requirements Optimum Max. Lab Water Water Dry Unit Content Minimum Dry Content Weight Range Unit Weight (%) (pCD (%) (°,6 compaction) 1. 213800009 ASTM D 698 Lt brown silty clay 19.2 103.8 -1/+3 95 Field Test Data Probe Water Dry Unit Dry Unit Test Lift/ Mat. Depth Content Weight Weight No. Test Location Elevation No. (inches) (%) (pcf) (0,6 compaction) W Parking Area between Bldg & Fire Lane Subgrade 978 20' W of grid line A.4/11 at Grade I 6 21.9 98.8 95 979 35' W of grid line B.6/11 at Grade 1 6 20.6 99.7 96 980 40' W of grid line C.5/11 at Grade 1 6 21.2 99.1 95 981 25' W of grid line D.5/11 at Grade 1 6 20.4 99.4 96 982 30' W of grid line E.5/11 at Grade 1 6 20.7 100.6 97 983 35' W of grid line F.5/11 at Grade 1 6 20.8 101.4 98 984 40' W of grid line G.5/11 at Grade 1 6 19.6 104.2 100 985 30' W of grid line H.2/11 at Grade 1 6 18.4 105.6 100+ Comments: Test results on this report meet project specification. NOTE: The area tested is adjacent to Grid lines A/11-H.5/11. Services - Perform in-place density and moisture content tests to determine degree of compaction and material moisture condition. Fie. ld Test Method~,STM D2922, ASTM D3017 Gauge ID: Field Results Reported To: Brian w/Hill & Wilkinson Technician: Bradford T. Rengstorff Report Distribution: (1) Transwestern Commercial Services (1) TechniStructures (1) O'Brien & Assoc (1) City of Coppell - Constr Insp (1) Hill & Wilkinson LTD (1) Cib/of Coppell - Bldg Insp (2) Carter & Burgess Inc (1) Staples Inc Reviewed by: HBCFFerracon Eugene arbo~ur Principal The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon, Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 1 of 1 ~-so~07-.~f.~.~ FIELD DENSITY TESTING Report Number: 94021380.0201 Service Date: January 20, 2003 Client: Transwestem Commercial Services Attn: James Gaspard 5001 Spring Valley Rd Ste 600 W Dallas TX 75244 Report Date: Project: Staples 201 Northpoint Coppell, TX Project Number: 94021380 'lFerracan 8901 Carpenter Fr',w, Ste #100 Dallas, Texas 75247 (214) 630-1010 February 03, 2003 Material Information Material Laboratory No. Test Method Description and Classification Lab Test Data Proiect Requirements Optimum Max. Lab Water Water Dry Unit Content Minimum Dry Content Weight Range Unit Weight (%) (pc0 (%) (% compaction) 1. 213800009 ASTM D 698 Lt brown silty clay 19.2 103.8 -1/+3 95 Field Test Data Test No. Test Location Lift/ Elevation E Parking Area between BIdg & Fire Lane Subgrade 973 30' E of Grid line D/1 974 40' E of Grid line E/1 975 30' E of Grid line F/1 976 30' E of Grid line G/1 977 40' E of Grid line H/1 Probe Water Dry Unit Dry Unit Mat. Depth Content Weight Weight No. (inches) (%) (pCf') (% compaction) at Grade 1 6 20.4 102.4 99 at Grade 1 6 19.0 102.9 99 at Grade I 6 18.7 103.6 100 at Grade 1 6 18.4 104.2 100 at Grade 1 6 19.7 104.8 100+ Comments: Test results on this report meet project specification. NOTE: The area tested is adjacent to Grid lines B.6/1 to J/1. Services - Perform in-place density and moisture content tests to determine degree of compaction and material moisture condition. Field Test Method~,STM D2922, ASTM D3017 Gauge ID: Field Results Reported To: Brian w/Hill & Wilkinson Technician: Bradford T. Rengstorff Report Distribution: (1) Transwestern Commercial Services (1) TechniStructures (1) O'Brien & Assoc (1) City of Coppell - Constr Insp (1) Hill & Wilkinson LTD (1) City of Coppell - Bldg Insp (2) Carter & Burgess Inc (1) Staples Inc Reviewed by: Eugene Harbour Principal The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 1 of 1 Q7~,~o7~,o~ REPORT OF CONCRETE PLACEMENT OBSERVATION Report Number: 94021380.0190 Service Date: January 14, 2003 lrerracan 8901 Carpenter Frwy, Ste #100 Dallas, Texas 75247 (214) 630-1010 Client: Transwestern Commercial Services Attn: James Gaspard 5001 Spring Valley Rd Ste 600 W Dallas TX 75244 Report Date: Project: Staples 201 Northpoint Coppell, TX February 03, 2003 Project Number: 94021380 Services: Concrete placement observation. On this date, a HBC/Terracon technician arrived at the above referenced jobsite as scheduled for concrete placement observation. After arriving at the jobsite, HBC's technician was notified that the scheduled concrete placement was cancelled and rescheduled due to the wrong mix was delivered. Technician: Jose A. Martinez Report Distribution: (1) Transwestern Commercial Services (1) O'Brien & Assoo (1) Hill & Wilkinson LTD (2) Carter & Burgess Inc (1) TechniStructures (1) City of Coppell - Constr Insp (1) City of Coppell - Bldg Insp (I) Staples Inc Reviewed by: HBC/Terr~ Eugene Harbour Principal The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and ara not necessarily indicative of the properties of other apparently similar or identical materials. Page 1 of 1 FIELD DENSITY TESTING Report Number: 94021380.0212 Service Date: January 23, 2003 l[erracan 8901 Carpenter Fn~y, Ste #100 Dallas, Texas 75247 (214) 630-1010 Client: Transwestern Commemial Services Attn: James Gaspard 5001 Spring Valley Rd Ste 600 W Dallas TX 75244 Report Date: Project: Staples 201 Northpoint Coppell, TX Project Number: 94021380 February 03, 2003 Material Information Material Laboratory No. Test Method Description and Classification Lab Test Data Proiect Requirements Optimum Max. Lab Water Water Dry Unit Content Minimum Dry Content Weight Range Unit Weight (%) (pcf) (%) (% compaction) 1. 213800009 ASTM D 698 Lt brown silty clay 19.2 103.8 =/> +3 92 Field Test Data Probe Water Dry Unit Dry Unit Test Lift/ Mat. Depth Content Weight Weight No. Test Location Elevation No. (inches) (%) (pct~ (% compaction) Leaveout Backfill 986 Grid line A.4/1 1st 1 6 24.6 98.7 95 987 Gdd line A/1.5 1st 1 6 23.7 99.6 96 988 Grid line N3.5 1 st 1 6 23.8 99.4 96 Comments: Test results on this report meet project specification. Services- Perform in-place density and moisture content tests to determine degree of compaction and material moisture condition. Field Test Method:ASTM D2922, ASTM D3017 Gauge ID: Field Results Reported To: Contractor/Brian Technician: Bradford T. Rengstorff Report Distribution: (1) Transwestem Commercial Services (1) TechniStructures (1) O'Bden & Assoc (1) City of Coppell - Constr Insp (1) Hill & Wilkinson LTD (1) City of Coppell - BIdg Insp (2) Carter & Burgess Inc (1) Staples Inc Reviewed by: H BC/'I',~_~ Eugene Harbour Principal The tests were pen~ormed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be repmducad except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 1 of 1