Amberpoint BP 2-LR030207 (2)FIELD DENSITY TESTING
Report Number: 94021380.0218
Service Date: January 29, 2003
Client: Transwestern Commercial Services
Attn: James Gaspard
5001 Spring Valley Rd Ste 600 W
Dallas TX 75244
° lrerracon
8901 Carpenter Frwy, Ste #100
Dallas, Texas 75247
(214) 630-1010
: February 07, 2003
Coppell, TX
Project Number: 94021380
Material Information
Material Laboratory
No. Test Method
¢i!~%Classification
Lab Test Data Proiect Requirements
Optimum Max. Lab Water
Water Dry Unit Content Minimum Dry
Content Weight Range Unit Weight
(%) (pct') (%) (% compaction)
1.213800010 ASTM D 698
2.213800009 ASTM D 698
Brown clay
Lt brown silty clay
22.7 98.7 =/> +3 92
19.2 103.8 -1/+3 95
Field Test Data
Test
No. Test Location
Lift/ Mat.
Elevation No.
Leaveout Backfill
1007 Grid line A.5/11
1008 Grid line C/11
1009 Grid line D.5/11
1010 Grid line F/11
1011 Grid line G.5/11
Parking Lot Subgrade
1012 40' S of grid line N11
1013 40' S of grid line N9
1014 40' S of grid line N7.5
1015 50' S and 70' W of grid line Nll
Probe
Depth
(inches)
2nd 1 6
2nd 1 6
2nd 1 6
2nd 1 6
2nd 1 6
at Grade 2 6
at Grade 2 6
at Grade 2 6
at Grade 2 6
Water Dry Unit Dry Unit
Content Weight Weight
(%) (pcf) (% compaction)
26.3 91.7 93
27.3 92.6 94
26.8 92.5 94
28.3 91.8 93
28.1 93.4 95
18.7 100.7 97
18.5 103.4 100
19.2 103.6 100
18.3 104.2 100
Comments:
Test results on this report meet project specification.
Services - Perform in-place density and moisture content tests to
condition.
Field Test Method:ASTM D2922, ASTM D3017
Gauge ID:
Field Results Reported To: Brian w/Hill & Wilkinson
Technician: Bradford T. Rengstorff
Report Distribution:
(1) Transwestem Commercial Services (2) Car~er & Burgess Inc
(1) O'Brien & Assoc (1) City of Coppell - Constr Insp
(1) Hill & Wilkinson LTD (1) City of Coppe{I - Bldg Insp
(1) TechniStructures (1) State Farm Insurance Co
degree of compaction and material moisture
Reviewed by:
Eugene Harbour
Principal
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.
Page I of 1