Amberpoint BP 2-LR030211MORTAR COMPRESSIVE STRENGTH TEST Report Number: 94021380.0236 Service Date: January 31, 2003 'll'erracan 8901 Carpenter Frwy, Ste #100 Dallas, Texas 75247 (214) 630-1010 Client: Transwestern Commercial Services Attn: James Gaspard 5001 Spring Valley Rd Ste 600 W Dallas TX 75244 Report Date: Project: Staples 201 Northpoint Coppell, TX Project Number: 94021380 February 11,2003 Contractor: Hill & Wilkinson Mortar Supplier: Plant: Site Mixed Specification Requirements: Strength: 1800 psi @ 28 Days Test Methods: ASTM C109 · ASTM C270 PROJECT DATA Mortar Mix I.D.: Type S Placement Date: 01/31/2003 Batch Time: 8:#0am Time Sampled: 9:00am By: Bradford T. Rengstorff Weather Conditions: Clear Temperature (F) - Air 58 °F Mortar: 61 °F Truck No: Ticket No: Sample Size: 2 x 2 x 2 Sample Location: See placement location Placement Location: CMU wall along A.4/5.7 Cube Marked Set No. REPORT OF TESTS Measured Measured Maximum Compressive Slump Flow Date Age Load Strength (inches) (seconds) Tested (days) (lbs. force) (psi) 1 1 9.50 02/07/2003 7 6700 1 2 9.50 02/28/2003 28 1 3 9.50 02/28/2003 28 1,680 Services- Obtain a sample of masonry mortar used during construction and cast 2 inch cube specimens for compressive strength determination, Technician: Bradford T. Rengstorff Report Distribution: (1) Transwestern Commercial Services {1) O'Brien & Ass(x: (1) Hill & Wilkinson LTD (1) TechniStructures (2) Carter & Burgess Inc (1) City of Coppell- Constr Insp (1) City of Coppell- Bldg Insp (1) State Farm Insurance Co Reviewed by: Eugene Harbour Principal The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 1 of 1 ~LLW.~-~,~y coNCRETE COMPRESSIVE STRENGTH TEST · Report Number: 94021380.0184 Service Date: January 10, 2003 lrerracan 8901 Carpenter Frwy, Ste #100 Dallas, Texas 75247 (214) 630-1010 Client: Transwestern Commercial Services Attn: James Gaspard 5001 Spring Valley Rd Ste 600 W Dallas TX 75244 Report Date: Project: Staples 201 Northpoint Coppell, TX Project Number: 94021380 February 11, 2003 Material Information Specified Strength: 4000 psi @ 28 Days Batch Time: 7:08am Plant: 1 Supplier: Potter Concrete Truck No: 112 Mix I.D. No.: 7753 Ticket No: 113109 Sample Information Sample Time: 7:43am Date Cast: January 10, 2003 Technician: Jose A~ Martinez Weather Conditions: Clear Accumulative Yards: 40 Placement Method: Pump Sample Locations: See placement location Placement Location: Paving E of building (See attached sketch) Field Test Data Test Slump, inches: Air Content, %: Concrete Temperature, o F: Ambient Temperature, o F: Plastic Unit Weight, pcf: Laboratory Test Data Result 5.00 7.4 6O 40 Set Specimen Diameter Area No. ID (inches) (sq. inches) 1 1 6.00 28.27 1 2 6.00 28.27 1 3 6.00 28.27 I 4 6.00 28.27 Specification Test Method 4-5 ASTM C-143 4-8 ASTM C-231 ASTM C1064 ASTM C-1064 Age at Maximum Compressive Date Test Load Strength Tested (days) (lbs) (psi) 01/17/2003 7 96,800 3,420 01/17/2003 7 94,790 3,350 Average 3,390 02/07/2003 28 117,040 4,140 02/07/2003 28 123,880 4,380 Avera~le 4,260 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 1 of 5 o,.LL~.e,-r~.,.~.~ coNcRETE COMPRESSIVE STRENGTH TEST Report Number: 94021380~0184 Service Date: January 10, 2003 'll'erracan 8901 Carpenter Frwy, Ste #100 Dallas, Texas 75247 (214) 630-1010 Client: Transwestern Commercial Services Attn: James Gaspard 5001 Spring Valley Rd Ste 600 W Dallas TX 75244 Report Date: Project: Staples 201 Northpoint Coppell, TX Project Number: 94021380 February 11,2003 Material Information Specified Strength: 4000 psi @ 28 Days Batch Time: 8:10am Plant: 1 Supplier: Potter Concrete Truck No: 106 Mix I.D. No.: 7753 Ticket No: 113120 Sample Information Sample Time: 8:34am Date Cast: January 10, 2003 Technician: Jose A. Martinez Weather Conditions: Clear Accumulative Yards: 110 Placement Method: Pump Sample Locations: See page 1 Placement Location: See page 1 Field Test Data Test Slump, inches: Air Content, %: Concrete Temperature, o F: Ambient Temperature, o F: Plastic Unit Weight, pcf: Laboratory Test Data Result 5.25 7.8 59 4O Set Specimen Diameter Area No. ID (inches) (sq. inches) 2 1 6.00 28.27 2 2 6.00 28.27 2 3 6.0O 28.27 2 4 6.00 28.27 Specification Test Method 4-5 ASTM C-143 4-8 ASTM C-231 ASTM C 1064 ASTM C-1 O64 Age at Maximum Compressive Date Test Load Strength Tested (days) (Ihs) (psi) 01/17/2003 7 97,700 3,450 01/17/2003 7 95,590 3,380 Average 3,420 02/07/2003 28 128,970 4,560 02/07/2003 28 126,570 4,480 Average 4,520 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This repod is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 2 of 5 coNCRETE COMPRESSIVE STRENGTH TEST Report Number: 94021380.0184 Service Date: January 10, 2003 'lrerracan 8901 Carpenter Frwy, Ste #100 Dallas, Texas 75247 (214) 630-1010 Client: Transwestern Commercial Services Attn: James Gaspard 5001 Spring Valley Rd Ste 600 W Dallas TX 75244 Report Date: Project: Staples 201 Northpoint Coppell, TX Project Number: 94021380 February 11,2003 Material Information Specified Strength: 4000 psi @ 28 Days Batch Time: 9:33am Plant: 1 Supplier: Potter Concrete Truck No: 112 Mix I.D. No.: 7753 Ticket No: 113136 Sample Information Sample Time: 10:55am Date Cast: January 10, 2003 Technician: Jose A. Martinez Weather Conditions: Clear Accumulative Yards: 220 Placement Method: Pump Sample Locations: See page 1 Placement Location: See page 1 Field Test Data Test Result Specification Test Method Slump, inches: 4.75 4-5 ASTM C-143 Air Content, %: 6.6 4-8 ASTM C-231 Concrete Temperature, o F: 61 ASTM C1064 Ambient Temperature, o F: 45 ASTM C-1064 Plastic Unit Weight, pcf: Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Test Load Strength No. ID (inches) (sq. inches) Tested (days) (lbs) (psi) 3 1 6.00 28.27 01/17/2003 7 120,020 4,240 3 2 6.00 28.27 01/17/2003 7 117,000 4,140 Average 4,190 3 3 6.00 28.27 02/07/2003 28 148,920 5,270 3 4 6.00 28.27 02/07/2003 28 152,250 5,380 Average 5,330 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 3 of 5 coNCRETE cOMPRESSIVE STRENGTH TEST · Report Number: 94021380.0184 Service Date: January 10, 2003 Client: Transwestern Commercial Services Attn: James Gaspard 5001 Spring Valley Rd Ste 600 W Dallas TX 75244 lrerracan 8901 Carpenter Frwy, Ste #100 Dallas, Texas 75247 (214) 630-1010 Report Date: Project: Staples 201 Northpoint Coppeli, TX February 11,2003 Project Number: 94021380 Material Information Specified Strength: 4000 psi @ 28 Days Batch Time: 10:31am Plant: 1 Supplier: Potter Concrete Truck No: 101 Mix I.D. No.: 7753 Ticket No: 113147 Sample Information Sample Time: 12:02pm Date Cast: January 10, 2003 Technician: Jose A. Martinez Weather Conditions: Clear Accumulative Yards: 310 Placement Method: Pump Sample Locations: See page 1 Placement Location: See page 1 Field Test Data Test Result Specification Test Method 5.00 4-5 ASTM C-143 5.7 4-8 ASTM C-231 66 ASTM C1064 48 ASTM C-1064 Slump, inches: Air Content, %: Concrete Temperature, o F: Ambient Temperature, o F: Plastic Unit Weight, pcf: Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Test Load Strength No. ID (inches) (sq. inches) Tested (days) (lbs) (psi) 4 1 6.00 28.27 01/17/2003 7 114,360 4,040 4 2 6.00 28.27 01/17/2003 7 109,750 3,880 Average 3,960 4 3 6.00 28.27 02/07/2003 28 140,710 4,980 4 4 6.00 28.27 02/07/2003 28 150,170 5,310 Average 5,150 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identicat materials. Page 4 of 5 o~-L~o,.~, coNcRETE COMPRESSIVE STRENGTH TEST · Report Number: 94021380.0184 Service Date: January 10, 2003 Client: Transwestern Commercial Services Attn: James Gaspard 5001 Spring Valley Rd Ste 600 W Dallas TX 75244 Report Date: Project: Staples 201 Northpoint Coppell, TX Project Number: 94021380 'lrerracon 8901 Carpenter Frwy, Ste #100 Dallas, Texas 75247 (214) 630-1010 February 11,2003 Material Information Specified Strength: 4000 psi @ 28 Days Batch Time: 1:00pm Plant: 1 Supplier: Potter Concrete Truck No: 105 Mix i.D. No.: 7753 Ticket No: 113159 Sample Information Sample Time: 1:43pm Date Cast: January 10, 2003 Technician: Jose A. Martinez Weather Conditions: Clear Accumulative Yards: 410 Placement Method: Pump Sample Locations: See page 1 Placement Location: See page 1 Field Test Data Test Result Specification Test Method Slump, inches: 5.25 4-5 ASTM C-143 Air Content, %: 5.7 4-8 ASTM C-231 Concrete Temperature, o F: 66 ASTM C1064 Ambient Temperature, o F: 49 ASTM C-1064 Plastic Unit Weight, pcf: Laboratory Test Data Age at Set Specimen Diameter Area Date Test No. ID (inches) (sq. inches) Tested (days) 5 1 6.00 28.27 01/17/2003 7 5 2 6.00 28.27 01/17/2003 5 3 6.00 28.27 02/07/2003 5 4 6.00 28.27 02/07/2003 Maximum Compressive Load Strength (lbs) (psi) 116,100 4,110 7 123,570 4,370 Average 4,240 28 153,150 5,420 28 153,500 5,430 Average 5,430 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Technician: Jose A. Martinez Report Distribution: (1) Transwestern Commercial Services (1) O'Bden & Assoc (1) Hill & Wilkinson LTD (1} TechniStructures (2) CaKer & Burgess Inc (1) City of Coppell - Constr Insp (1) City of Coppell - Bldg Insp (1) State Farm Insurance Co Reviewed by: H BC/~ Eugene Harbour Principal The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 5 of 5 .,-L~W'~O,-F~.~.~ PROJECT: JOB NO. '~ Comp. By Page of CHECKED BY: 'lrerracan o d coNCRETE COMPRESSIVE STRENGTH TEST · Report Number: 94021380.0225 Service Date: January 31,2003 Client: Transwestern Commercial Services Attn: James Gaspard 5001 Spring Valley Rd Ste 600 W Dallas TX 75244 Report Date: Project: Staples 201 Northpoint Coppell, TX Project Number: 94021380 'll'erracan 8901 Carpenter Frwyl Ste #100 Dallas, Texas 75247 (214) 630-1010 February 11,2003 Material Information Specified Strength: 4000 psi @ 28 Days Batch Time: 3:58am Plant: 1 Supplier: Potter Concrete Truck No: 104 Mix I.D. No.: 7753 Ticket No: ~ 13417 Sample Information Sample Time: 4:30am Date Cast: January 31, 2003 Technician: Jose A. Martinez Weather Conditions: Cloudy Accumulative Yards: 30 Placement Method: Direct Discharge Sample Locations: See placement location Placement Location: Paving S of building (See attachments) Field Test Data Test Result 5.00 7.0 61 51 Slump, inches: Air Content, %: Concrete Temperature, o F: Ambient Temperature, o F: Plastic Unit Weight, pcf: Specification Test Method 3 - 5" ASTM C-143 4 - 6% ASTM C-231 55 - 95 ASTM C1064 ASTM C-1064 Laboratory Test Data Age at Set Specimen Diameter Area Date Test No. ID (inches) (sq. inches) Tested (days) 1 1 6.00 28.27 0210712003 7 1 2 6.00 28.27 02~07~2003 7 Average 1 3 02/2812003 28 1 4 02/28/2003 28 Maximum Compressive Load Strength (lbs) (psi) 96,940 · 3,430 98,500 3,480 3,460 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 1 of 4 coNCRETE COMPRESSIVE STRENGTH TEST · Report Number: 94021380.0225 Service Date: January 31,2003 'll'erracan 8901 Carpenter Frwy, Ste #100 Dallas, Texas 75247 (214) 630-1010 Client: Transwestern Commercial Services Attn: James Gaspard 5001 Spring Valley Rd Ste 600 W Dallas TX 75244 Report Date: Project: Staples 201 Northpoint Coppell, TX February 11,2003 Project Number: 94021380 Material Information Specified Strength: 4000 psi @ 28 Days Batch Time: 5:33am Plant: 1 Supplier: Potter Concrete Truck No: 115 Mix I.D. No,: 7753 Ticket No: 113425 Sample Information Sample Time: 5:55am Date Cast: January 31, 2003 Technician: Jose A. Martinez Weather Conditions: Cloudy Accumulative Yards: 110 Placement Method: Direct Discharge Sample Locations: See page 1 Placement Location: See page 1 Field Test Data Test Slump, inches: Air Content, %: Concrete Temperature, o F: Ambient Temperature, o F: Plastic Unit Weight, pcf: Result Specification Test Method 5.00 3 - 5" ASTM C-143 7.5 4 - 6% ASTM C-231 61 55 - 95 ASTM C1064 51 ASTM C-1064 Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Test Load Strength No. ID (inches) (sq. inches) Tested (days) (lbs) (psi) 2 I 6.00 28.27 02/07/2003 7 102,010 3,610 2 2 6.00 28.27 02/07/2003 7 97,100 3,430 Average 3,520 2 3 02/28/2003 28 2 4 02/28/2003 28 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This repod is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 2 of 4 01'LL~Ol'Fu~ur' CONCRETE COMPRESSIVE STRENGTH TEST · Report Number: 94021380.0225 Service Date: January 31, 2003 'll'erracan 8901 Carpenter Frwy, Ste #100 Dallas, Texas 75247 (214) 630-1010 Client: Transwestern Commercial Services Attn: James Gaspard 5001 Spring Valley Rd Ste 600 W Dallas TX 75244 Report Date: Project: Staples 201 Northpoint Coppell, TX February 11,2003 Project Number: 94021380 Material Information Specified Strength: 4000 psi @ 28 Days Batch Time: 7:05am Plant: 1 Supplier: Potter Concrete Truck No: 104 Mix I.D. No.: 7753 Ticket No: 113435 Sample Information Sample Time: 7:30am Date Cast: January 31, 2003 Technician: Jose A. Martinez Weather Conditions: Cloudy Accumulative Yards: 210 Placement Method: Direct Discharge Sample Locations: See page 1 Placement Location: See page 1 Field Test Data Test Result Specification Test Method Slump, inches: 5.25 3 - 5" ASTM C-143 Air Content, %: 6.0 4 - 6% ASTM C-231 Concrete Temperature, e F: 61 55 - 95 ASTM C1064 Ambient Temperature, o F: 50 ASTM C-1064 Plastic Unit Weight, pcf: Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Test Load Strength No. ID (inches) (sq. inches) Tested (days) (lbs) (psi) 3 1 6.00 28.27 02/07/2003 7 124,390 4,400 3 2 6.00 28.27 02/07/2003 7 123,990 4,380 Average 4,390 3 3 02/28/2003 28 3 4 02/28/2003 28 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 3 of 4 o~-~L~,o~-~. coNcRETE COMPRESSIVE STRENGTH TEST · Report Number: 94021380.0225 Service Date: January 31, 2003 Client: Transwestern Commercial Services Attn: James Gaspard 5001 Spring Valley Rd Ste 600 W Dallas TX 75244 'lrerracan 8901 Carpenter Frwy, Ste #100 Dallas, Texas 75247 (214) 630-1010 Report Date: Project: Staples 201 Northpoint Coppell, TX February 11, 2003 Project Number: 94021380 Material Information Specified Strength: 4000 psi @ 28 Days Batch Time: 8:41am Plant: 1 Supplier: Potter Concrete Truck No: 110 Mix I.D. No.: 7753 Ticket No: 113445 Sample Information Sample Time: 8:58am Date Cast: January 31, 2003 Technician: Jose A. Martinez Weather Conditions: Partly cloudy Accumulative Yards: 310 Placement Method: Direct Discharge Sample Locations: 90' S of NW corner of bldg. & 40' W Placement Location: See page 1 Field Test Data Test Result 5.00 7.6 68 59 Slump, inches: Air Content, %: Concrete Temperature, o F: Ambient Temperature, o F: Plastic Unit Weight, pcf: Laboratory Test Data Specification Test Method 3 - 5" ASTM C-143 4 - 6% ASTM C-231 55 - 95 ASTM C1064 ASTM C-1064 Age at Test (days) Set Specimen Diameter Area Date No. ID (inches) (sq. inches) Tested 4 I 6.00 28.27 02/07/2003 7 92,310 4 2 6.00 28.27 02/07/2003 7 94,570 Average 4 3 02/28/2003 28 4 4 02/28/2003 28 Maximum Compressive Load Strength (lbs) (psi) 3,260 3,340 3,300 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Technician: Jose A. Martinez Report Distribution: (1) Transwestern Commercial Services (1) O'Brien & Assoc (1) Hill & Wilkinson LTD (1) TechniStructures H BCfT,~_~._~ (2) Car~er & Burgess Inc (1) City of Coppell - Constr Insp Reviewed by: (1) City of Coppell - Bldg Insp Eugene Harbour (1} State Farm Insurance Co Principal The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 4 of 4 ~ ~.,,.r~.~.~ o 0 .> Q PROJECT: JOB NO. ~c~O~'l~O'O~'~ Date 1//,.~I /o~, Comp. By Form 112--5-93 'll'erracon Page of CHECKED BY: · FIELD DENSITY TESTING Report Number: 94021380.0228 Service Date: February 1,2003 Client: Transwestern Commercial Services Attn: James Gaspard 5001 Spring Valley Rd Ste 600 W Dallas TX 75244 Report Date: Project: Staples 201 Northpoint Coppell, TX 'lrerracan 8901 Carpenter Frwy, Ste#100 Dallas, Texas 75247 (214) 630-1010 February 11,2003 Project Number: 94021380 Material Information Lab Test Data Project Requirements Optimum Max. Lab Water Water Dry Unit Content Minimum Dry Material Laboratory Content Weight Range Unit Weight No. Test Method Description and Classification (%) (pct') (%) (% compaction) 1. 213800009 ASTM D 698 Lt brown silty clay 19.2 103.8 -1/+3 95 2.213800010 ASTM D 698 Brown clay 22.7 98.7 =/> +3 92 Field Test Data Probe Water Dry Unit Dry Unit Test Lift/ Mat. Depth Content Weight Weight No. Test Location Elevation No. (inches) (%) (pct') (% compaction) Leaveout Backfill 1032 Grid line J/5.0 1st 2 6 26.0 93.9 95 1033 Grid line J/3.5 1st 2 6 25.7 93.4 95 1034 Grid line J/2.0 1st 2 6 27.3 92.6 94 Ramp Backfill 1035 Grid line 11.5/H.8 1st 1 6 20.8 104.6 100+ 1036 Grid line 11.5/H.8 2nd 1 6 19.6 103.1 99 Comments: Test results on this report meet project specification. Services - Perform in-place density and moistQre content tests to determine degree of compaction and material moisture condition. Field Test MethodASTM D2922, ASTM D3017 Gauge ID: Field Results Reported To: Brian w/Hill & Wilkinson Technician: Bradford T. Rengstodf Report Distribution: (1) Transwestern Commercial Services (2) Cadet & Burgess lnc (1) O'Brien & Assoc (1) City of Coppel[ - Constr Insp (1) Hill & Wilkinson LTD (1) City of Coppell - Bldg Insp (1) TechniStructures (1) State Farm Insurance Co Reviewed by: HBCfTe~~ Eugene Harbour Principal The tests were performed in genera[ accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 1 of 1 0, L~W~"07~,K'~