Amberpoint BP 2-LR030214CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94021380.0197 Service Date: January 15, 2003 Client: Transwestern Commercial Services Attn: James Gaspard 5001 Spring Valley Rd Ste 600 W Dallas TX 75244 Material Information - ' ~'~ Specified Strength: 4000 psi (~ 28 Days Batch Time: 8:55am Supplier: Potter Concrete Truck No: 111 /Ticket No: 113183 Mix I.D. No.: 7753 Coppell, TX lrerracon 8901 Carpenter Frwy, Ste #100 Dallas, Texas 75247 (214) 630-1010 February 14, 2003 Project Number: 94021380 Sample Information Sample Time: 10:10am Date Cast:January 15, 2003 Technician: Melvin L. Searles Weather Conditions: Cloudy, cold Accumulative Yards: 10 Placement Method: Direct Discharge Sample Locations: See placement location Placement Location: Archatectural leaveout in SE approach to Northpoint Field Test Data Test Slump, inches: Air Content, %: Concrete Temperature, o F: Ambient Temperature, o F: Plastic Unit Weight, pcf: Laboratory Test Data Result Specification Test Method 4.50 4-5 ASTM C-143 4.0 4-8 ASTM C-231 60 ASTM C1064 45 ASTM C-1064 Age at Maximum Compressive Set Specimen Diameter Area Date Test Load Strength No. ID (inches) (sq. inches) ~ Tested (days) (lbs) (psi) I 1 6.00 28.27 /~"~ 01/22/2003 7 122,380 4,330 1 2 6.00 28.27 ~I 01/22/2003 7 131,320 4,640 Average 4,490 1 3 6.00 28.27 02/12/2003 28 149,020 5,270 1 4 6.00 28.27 02/12/2003 28 162,780 5,760 Average 5,520 1 5 Hold Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Technician: Melvin L. Searles Report Distribution: (1) Transwestern Commercial Services (1) O'Brien & Assoc (1) Hill & Wilkinson LTD (2) Carter & Burgess inc (1) TechniStructures (1) City of Coppell - Bldg Insp (1) City of Coppe[I - Constr [nsp (1) HBC Engineering Inc Reviewed by: Eugene Harbour Principal The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terraccn. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 1 of I a~-LLw,,~-r~.. CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94021380.0192 Service Date: January 14, 2003 Client: Transwestern Commercial Services Attn: James Gaspard 5001 Spring Valley Rd Ste 600 W Dallas TX 75244 Report Date: Project: Staples 201 Northpoint Coppell, TX Project Number: 94021380 lrerracan 8901 Carpenter Frwy, Ste #100 Dallas, Texas 75247 (214) 630-I 010 February 14, 2003 Material Information Specified Strength: 3500 psi @ 28 Days Batch Time: 11:45am Plant: 1 Supplier: Potter Concrete Truck No: 109 Mix I.D. No.: 9337 Ticket No: 113166 Sample Information Sample Time: 12:10pm Date Cast:January 14, 2003 Technician: Jose A. Martinez Weather Conditions: Clear Accumulative Yards: 10 Placement Method: Direct Discharge Sample Locations: Bottom half of panel #2 Placement Location: Panels 1 thru 4 Field Test Data Test Slump, inches: Air Content, %: Concrete Temperature,° F: Ambient Temperature, o F: Plastic Unit Weight, pcf: Laboratory Test Data Result 5.00 1.6 60 65 Set Specimen Diameter Area No. ID (inches) (sq. inches) 1 1 6.00 28.27 1 2 6.00 28.27 1 3 6.00 28.27 I 4 6.00 28.27 1 5 6.00 28.27 1 6 6.00 28,27 Specification Test Method 4-5 ASTM C-143 N/A ASTM C-231 ASTM C 1064 ASTM C-1064 Services - Age at Maximum Compressive Date Test Load Strength Tested (days) (lbs) (psi) 01/17/2003 3 57,950 2,050 01/17/2003 3 57,650 2,040 Average 2,050 01/21/2003 7 101,250 3,580 01/21/2003 7 104,420 3,690 Average 3,640 02/11/2003 28 131,870 4,660 02/11/2003 28 137,160 4,850 Average 4,760 Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Technician: Jose A. Martinez Report Distribution: (1) Transwestern Commercial Services (1) O'Brien & Assoc (1) Hill & Wilkinson LTD (2) Carter & Burgess lnc (1) TechniStructures (1) City of Coppell - Oldg Insp (1) City of Coppell - Constr Insp (1) HBC Engineering Inc Reviewed by: HBCfTe~ Eugene Harbour Principal The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical Page 1 of 1 CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94021380.0232 Service Date: February 4, 2003 Client: Transwestern Commercial Services Attn: James Gaspard 5001 Spring Valley Rd Ste 600 W Dallas TX 75244 Report Date: Project: Staples 201 Northpoint · Coppell, TX Project Number: 94021380 lrerracan 8901 Carpenter Frwy, Ste #100 Dallas, Texas 75247 (214) 630-1010 February 14, 2003 Material Information Specified Strength: 4000 psi @ 28 Days Batch Time: 6:56am Plant: 1 Supplier: Potter Concrete Truck No: 113 Mix I.D. No.: 9349 Ticket No: 113452 Sample Information sample Time: 7:20am Date Cast: February 4, 2003 Technician: Jose A. Martinez Weather Conditions: Partly cloudy Placement Method: Direct Discharge Sample Locations: G.L. J 2 thru 5 Placement Location: Slab leaveout G.L. 2-thru 11 and from G.L.11, J thru A & from G.L, Athru 8 (See attached) Field Test Data Test Result Specification Test Method 5.00 4-5 ASTM C-143 1.5 N/A ASTM C-231 57 ASTM C1064 38 ASTM C-1064 Slump, inches: Air Content, %: Concrete Temperature, o F: Ambient Temperature, o F: Plastic Unit Weight, pcf: Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Test Load Strength No. ID (inches) (sq. inches) Tested (days) (lbs) (psi) 1 1 6.00 28.27 02/11/2003 7 139,750 4,940 I 2 6.00 28.27 02/11/2003 7 142,970 5,060 Average 5,000 I 3 03/04/2003 28 1 4 03/04/2003 28 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Technician: Jose A. Martinez Report Distribution: (1) Transwestern Commercial Services (1) O'Bden & Assoc (1) Hill & Wilkinson LTD (2) Cadet & Burgess Inc (1) TechniStructures (1) ~ity of Coppell - Bldg Insp (1) City of Coppell - Constr Insp (1) HBC Engineering thc Reviewed by: Eugene Harbour Principal The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials, o, LLW~O~-F~,. Page 1 of 1 o~ 0 CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94021380.0234 Service Date: February 5, 2003 Client: Transwestern Commercial Services Attn: James Gaspard 5001 Spring Valley Rd Ste 600 W Dallas TX 75244 Report Date: Project: Staples 201 Northpoint Coppell, TX Project Number: 94021380 'lrerracan 8901 Carpenter Frwy, Ste #100 Dallas, Texas 75247 (214) 630-1010 February 14, 2003 Material Information Specified Strength: 4000 psi @ 28 Days Batch Time: Supplier: Hanson Truck No: 923 Mix I.D. No.: 9349 Plant: 27 Ticket No: 472592 Sample Information Sample Time: 8:50am Date Cast: February 5, 2003 Technician: Jose A. Martinez Weather Conditions: Cloudy Accumulative Yards: 10 Placement Method: Direct Discharge Sample Locations: See placement location Placement Location: Block out on G.L. 11 columns Diamond's mezzanine area (See attached sheets) Field Test Data Test Result Specification Test Method Slump, inches: 5.00 4-5 ASTM C-143 Al{ Content, %: 3.2 N/A ASTM C-231 Concrete Temperature,° F: 58 ASTM C1064 Ambient Temperature, o F: 55 ASTM C-1064 Plastic Unit Weight, pcf: Laboratory Test Data Age at Set Specimen Diameter Area Date Test No. ID (inches) (sq. inches) Tested (days) 1 1 6.00 28.27 02/12/2003 7 1 2 6. O0 28.27 02/12/2003 7 Average 1 3 03/05/2003 28 1 4 03/05/2003 28 Maximum Compressive Load Strength (lbs) (psi) 137,000 4,840 134,750 4,770 4,8~10 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. The tests were performed in general accordance with applicable ASTM AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. O~-L~W~.O~-F~. Page 1 of 4 CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94021380.0234 Service Date: February 5, 2003 Client: Transwestern Commercial Services Attn: James Gaspard 5001 Spring Valley Rd Ste 600 W Dallas TX 75244 Report Date: Project: Staples 201 Northpoint Coppell, TX Project Number: 94021380 'll'erracan 8901 Carpenter Frwy, Ste #100 Dallas, Texas 75247 (214) 630-1010 February 14, 2003 Material Information Specified Strength: 4000 psi @ 28 Days Batch Time: 8:59am Supplier: Hanson Truck No: 1015 Mix I.D. No.: 9349 Plant: 27 Ticket No: 472599 Sample Information sample Time: 9:38am Date Cast: February 5, 2003 Technician: Jose A. Martinez Weather Conditions: Cloudy Accumulative Yards: 30 Placement Method: Pump Sample Locations: Between G.L. A & 3.9 to 3 Placement Location: First floor mezzanine Field Test Data Test Slump, inches: Air Content, %: Concrete Temperature,° F: Ambient Temperature, o F: Plastic Unit Weight, pcf: Result Specification Test Method 5.00 4-5 ASTM C-143 2.6 N/A ASTM C-231 57 ASTM C1064 55 ASTM C-1064 Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Test Load Strength No. ID (inches) (sq. inches) Tested (days) (lbs) (psi) 2 1 6.00 28.27 02/12/2003 7 143,990 5,090 2 2 6.00 28.27 02/12/2003 7 141,030 4,990 Average 5,040 2 3 03/05/2003 28 2 4 03/05/2003 28 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the propedies of other apparently similar or identical materials. Page 2 of 4 e~.~w~o~...~.K.~ CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94021380.0234 Service Date: February 5, 2003 Client: Transwestem Commercial Services Attn: James Gaspard 5001 Spring Valley Rd Ste 600 W Dallas TX 75244 Report Date: Project: Staples 201 Northpoint Coppell, TX Project Number: 94021380 'lrerracan 8901 Carpenter Frwy, Ste #100 Dallas, Texas 75247 (214) 630-1010 February 14, 2003 Material Information Specified Strength: 4000 psi ~ 28 Days Batch Time: Supplier: Hanson Truck No: 648 Mix I.D. No.: 9349 Plant: 27 Ticket No: 499630 Sample Information sample Time: 1:30pm Date Cast: February 5, 2003 Technician: Jose A. Martinez Weather Conditions: Cloudy Accumulative Yards: 120 Placement Method: Direct Discharge Sample Locations: Hydraulic Pads to Diamond's Placement Location: Blockout around elevator pit generator pad Diamond's on A.5 Sample location: Hydraulic pads & Diamonds 1.5/2.0/2.513.013.513.9, G.L.B 1.5/2.5/2.9 & pads for hydraulic lifts on G.L. Field Test Data Test Slump, inches: Air Content, %: Concrete Temperature,c F: Ambient Temperature, o F: Plastic Unit Weight, pcf: Laboratory Test Data Result 4.75 2.2 60 49 Set Specimen Diameter Area No. ID (inches) (sq. inches) 3 1 6.00 28.27 3 2 6.00 28.27 3 3 Specification Test Method 4-5 ASTM C-143 N/A ASTM C-231 ASTM C1064 ASTM C-1064 Age at Maximum Compressive Date Test Load Strength Tested (days) (lbs) (psi) 02/12/2003 7 132,830 4,700 02/12/2003 7 136,870 4,840 Average 4,770 03/05/2003 28 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 3 of 4 01'LLW~R01'FUI~e Key ,CONCRETE COMPRESSIVE STRENGTH TEST Client: Transwestem Commercial Services 'll'erracan Project Number:94021380 Report Number: 94021380.0234 Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Test Load Strength No. ID (inches) (sq. inches) Tested (days) (lbs) (psi) 3 4 03/05/2003 28 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Technician: Jose A. Martinez Report Distribution: (1) Transwestern Commercial Services (1) O'Brien & Assoc (1) Hill & Wilkinson LTD (2) Carter & Burgess Inc (1) TechniStructures (1) City of Coppell - Bidg Insp (1) City of Coppell - Constr Insp (1) HBC Engineering Inc Reviewed by: HBC/Ter~ Eugene Harbour Principal The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the propedies of other apparently similar or identical materials. Page 4 of 4 o~ LLW'.O,-F~,-. o 0 0