Loading...
Amberpoint BP 2-LR030304.-';ONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94021380.0232 Service Date: February 4, 2003 Client: Transwestern Commercial Services Attn: James Gaspard 5001 Spring Valley Rd Ste 600 W Dallas TX 75244 lrerracan 8901 Carpenter Frwy, Ste #100 Dallas, Texas 75247 (214) 630-1010 Report Date: Project: Staples 201 Nodhpoint Coppell, TX March 04,2003 Project Number: 94021380 Material Information Specified Strength: 4000 psi @ 28 Days Batch Time: 6:56am Plant: 1 Supplier: Potter Concrete Truck No: 113 Mix i.D. No.: 9349 Field Test Data Test Ticket No: 113452 Slump, inches: Air Content, %: Concrete Temperature,° F: Ambient Temperature, o F: Plastic Unit Weight, pcf: Sample Information Sample Time: 7:20am Date Cast: February 4, 2003 Technician: Jose A. Martinez Weather Conditions: Partly cloudy Placement Method: Direct Discharge Sample Locations: G.L. J 2 thru 5 Placement Location: Slab leaveout G.L. 2-thru 11 and from G.L.11, J thru A & from G.L, Athru 8 (See attached) Result Specification Test Method 5.00 4-5 ASTM C-143 1.5 N/A ASTM C-231 57 ASTM C1064 38 ASTM C-1064 Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Test Load Strength No. ID (inches) (sq. inches) Tested (days) (lbs) (psi) I 1 6.00 28.27 02/11/2003 7 139,750 4,940 1 2 6.00 28.27 02/11/2003 7 142,970 5,060 Average 5,000 I 3 6.00 28.27 03/04/2003 28 176,690 6,250 1 4 6.00 28.27 03/04/2003 28 174,130 6,160 Average 6,210 Comments: Not tested for plastic unit weight. Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Technician: Jose A. Martinez Report Distribution: (1) Transwestern Commercial Services (1) O'Brien & Assoc (1) Hill & Wilkinson LTD (2) Carler & Burgess (1) TechniStructures (1) Ciiy of Coppel] - Bldg Insp (1) City of Coppell - Constr Insp (1) Terracon Inc Reviewed by: HBCFFe~n Eugene Harbour Principal The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 1 of 1 o~-~w,,o~.~u~,.~.~ o