St Joseph-LR021202CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 94021187.0175
Service Date: October 31,2002
']rerracan
8901 Carpenter Frwy, Ste #100
Dallas, Texas 75247
(214) 630-1010
Client: St. Joseph Village, Inc.
Attn: Joseph Dingman
13223 Glad Acres Drive
Dallas TX 75234
Report Date: December 02, 2002
Project: St. Joseph Village
1201 East Sandy Lake Rd
Coppell, TX 75019
Project Number: 94021187
Material Information
Specified Strength: 3000 psi ~ 28 Days
Batch Time: 8:00am Plant: 29
Supplier: Hanson
Truck No: 1029
Mix I.D. No.: 7724
Ticket No: 320708
Sample Information
Sample Time: 9:00am Date Cast: October 31,2002
Technician: Michael P. Ardito
Weather Conditions: Cool, cloudy
Accumulative Yards: 100
Placement Method: Direct Discharge
Sample Locations: Sta. 5+00
Placement Location: Paving, Star Leaf Street @ Sra. 1+00 to
Sra. 6+19
Field Test Data
Test
Result
Slump, inches: 3.50
Air Content, %: 5.1
Concrete Temperature,o F: 65
Ambient Temperature, o F: 49
Plastic Unit Weight, pcf:
Laboratory Test Data
Specification Test Method
3-5 ASTM C-143
3-6 ASTM C-231
55 - 95 ASTM C1064
ASTM C-1064
Age at
Maximum Compressive
Set Specimen Diameter Area Date Test Load Strength
No. ID (inches) (sq. inches) Tested (days) (lbs) (psi)
1 1 6.00 28.27 11/07/2002 7 133,110 4,710
1 2 6.00 28.27 11/07/2002 7 128,310 4,540
Average 4,630
1 3 6.00 28.27 11/28/2002 28 150,450 5,320
1 4 6.00 28.27 11/28/2002 28 155,320 5,490
Average 5,410
Services - Obtain samples of fresh concrete at the placement locations, perrorm required field tests and cast compressive
strength samples.
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the crient
indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the propedies of other apparently similar or identical
materials.
Page 1 of 3 e?~ ~..~
,CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 94021187.0175
Service Date: October 31,2002
'll'erracan
8901 Carpenter Frwy, Ste #100
Dallas, Texas 75247.
(214) 630-1010
Client: St. Joseph Village, Inc.
Attn: Joseph Dingman
13223 Glad Acres Drive
Dallas TX 75234
Report Date: December 02, 2002
Project: St. Joseph Village
1201 East Sandy Lake Rd
Coppell, TX 75019
Project Number: 94021187
Material Information
Specified Strength: 3000 psi @ 28 Days
Batch Time: 9:16am Plant: 29
Supplier: Hanson
Truck No: 923
Mix I.D. No.: 7724
Ticket No: 272283
Sample Information
Sample Time: 10:30am Date Cast: October 31,2002
Technician: Michael P. Ardito
Weather Conditions: Cool, cloudy
Accumulative Yards: 200
Placement Method: Direct Discharge
Sample Locations: Sra. 3+00
Placement Location: See page 1.
Field Test Data
Test
Result Specification Test Method
Slump, inches: 3.50 3-5 ASTM C-143
Air Content, %: 5.8 3-6 ASTM C-231
Concrete Temperature, o F: 66 55 - 95 ASTM C1064
Ambient Temperature, o F: 49 ASTM C-1064
Plastic Unit Weight, pcf:
Laboratory Test Data
Age at Maximum Compressive
Set Specimen Diameter Area Date Test Load Strength
No. ID (inches) (sq. inches) Tested (days) (lbs) (psi)
2 1 6.00 28.27 11/07/2002 7 134,600 4,760
2 2 6.00 28.27 11/07/2002 7 137,060 4,850
Average 4,810
2 3 6.00 28.27 11/28/2002 28 166,780 5,900
2 4 6.00 28.27 11/28/2002 28 173,060 6,120
Average 6,010
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This repod is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.
Page 2 of 3 0~-~LW~0~-F~...~
CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 94021187.0175
Service Date: October 31,2002
lr'erracan
8901 Carpenter Frwy, Ste #100
Dallas, Texas 75247
(214) 630-1010
Client: St. Joseph Village, Inc.
Attn: Joseph Dingman
13223 Glad Acres Drive
Dallas TX 75234
Report Date: December 02, 2002
Project: St. Joseph Village
1201 East Sandy Lake Rd
Coppell, TX 75019
Project Number: 94021187
Material Information
Specified Strength: 3000 psi @ 28 Days
Batch Time: Plant: 29
Supplier: Hanson
Truck No: 1029
Mix I.D. No.: 7724
Ticket No: 320737
Sample Information
Sample Time: 11:35am Date Cast: October 31,2002
Technician: Michael P. Ardito
Weather Conditions: Cool, cloudy
Accumulative Yards: 300
Placement Method: Direct Discharge
Sample Locations: Sta. 1+00
Placement Location: See page 1.
Field Test Data
Test Result Specification Test Method
Slump, inches: 3.50 3-5 ASTM C-143
Air Content, %: 5.6 3-6 ASTM C-231
Concrete Temperature,° F: 64 55 - 95 ASTM C1064
Ambient Temperature, o F: 51 ASTM C-1064
Plastic Unit Weight, pcf:
Laboratory Test Data
Age at Maximum Compressive
Set Specimen Diameter Area Date Test Load Strength
No. ID (inches) (sq. inches) Tested (days) (lbs) (psi)
3 1 6.00 28.27 11/07/2002 7 131,030 4,630
3 2 6.00 28.27 11/07/2002 7 130,900 4,630
Average 4,630
3 3 6.00 28.27 11/28/2002 28 163,710 5,790
3 4 6.00 28.27 11/28/2002 28 153,440 5,430
Average 5,610
Services - Obtain samples of fresh concrete at the placement locations, perform required field ~e.st'~'d.,~t~ compressive
strength samples.
.--%,,..... ~-....,j-
; LYNDON d. COX
~, ....~ .......................... :.-..-~
Technician: Michael P. Ardito
Repod Distribution: ,,~ HBC~rrac~,
(1) St. Joseph Village, Inc. (1) City of Coppell Engineering
(1) Aguirre Corporation (1) St Andrews Management Reviewed by:
(1) Cenlex- Jobsite (1) St Andrews Management f Lyndon J, ~ox, P.E.
(1) City of Coppell - B]dg Insp /, Principal" -1 ]-i~ngineer
/
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for th~se of the client
indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of ether apparently similar or identical
materials.
Page 3 of 3