St Joseph-LR021127CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 94021187.0173
Service Date: October 30, 2002
'lrerracan
8901 Carpenter Frwy, Ste #100
Dallas, Texas 75247
(214) 630-1010
Client: St. Joseph Village, Inc.
Attn: Joseph Dingman
13223 Glad Acres Drive
Dallas TX 75234
Report Date: November 27, 2002
Project: St. Joseph Village
1201 East Sandy Lake Rd
Coppell, TX 75019
Project Number: 94021187
Material Information
Specified Strength: 3000 psi (~ 28 Days
Batch Time: 8:95am Plant: 27
Supplier: Hanson
Truck No: 1880
Mix I.D. No.: 7724
Ticket No: 272224
Sample Information
Sample Time: 9:00am Date Cast: October 30, 2002
Technician: Michael P. Ardito
Weather Conditions: Cool, cloudy
Accumulative Yards: 90
Placement Method: Direct Discharge
Sample Locations: Sta. 17+00
Placement Location: Paving, Starleaf Road (~ Sta. 6+19 to Sra.
18+50
Field Test Data
Test
Result Specification Test Method
Slump, inches: 4.00 3-5 ASTM C-143
Air Content, %: 8.0 3-6 ASTM C-231
Concrete Temperature,° F: 65 55 - 95 ASTM C1064
Ambient Temperature, o F: 55 ASTM C-1064
Plastic Unit Weight, pcf:
Laboratory Test Data
Age at Maximum Compressive
Set Specimen Diameter Area Date Test Load Strength
No. ID (inches) (sq. inches) Tested (days) (lbs) (psi)
1 1 6.00 28.27 11/06/2002 7 105,190 3,720
1 2 6.00 28.27 11/06/2002 7 110,090 3,890
Average 3,810
1 3 6.00 28.27 11/27/2002 28 129,000 4,560
1 4 6.00 28.27 11/27/2002 28 135,050 4,780
Average 4,670
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.
Page 1 of 7 ~ LLW~0~-F~*~.y
,CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 94021187.0173
Service Date: October 30, 2002
'lrerracon
8901 Carpenter Frwy, Ste #100
Dallas, Texas 75247
(214) 630-1010
Client: St. Joseph Village, Inc.
Attn: Joseph Dingman
13223 Glad Acres Drive
Dallas TX 75234
Report Date: November 27, 2002
Project: St. Joseph Village
1201 East Sandy Lake Rd
Coppell, TX 75019
Project Number: 94021187
Material Information
Specified Strength: 3000 psi @ 28 Days
Batch Time: 9:47am Plant: 27
Supplier: Hanson
Truck No: 1015
Mix I.D. No.: 7724
Ticket No: 272235
Sample Information
Sample Time: 10:30am Date Cast: October 30, 2002
Technician: Michael P. Ardito
Weather Conditions: Cool, cloudy
Accumulative Yards: 200
Placement Method: Direct Discharge
Sample Locations: Sra. 15+00
Placement Location: S~e page I
Field Test Data
Test
Slump, inches:
Air Content, %:
Concrete Temperature,° F:
Ambient Temperature, o F:
Plastic Unit Weight, pcf:
Laboratory Test Data
Result Specification Test Method
2.50 3-5 ASTM C-143
6.9 3-6 ASTM C-231
71 55 - 95 ASTM C1064
65 ASTM C-1064
Set Specimen Diameter Area Date
No. ID (inches) (sq. inches) Tested
2 1 6.00 28.27 11/06/2002
2 2 6.00 28.27 11/06/2002
2 3 6.00 28.27 11/27/2002
2 4 6.00 28.27 11/27/2002
Age at Maximum Compressive
Test Load Strength
(days) (lbs) (psi)
7 128,040 4,530
7 133,060 4,710
Average 4,620
28 143,130 5,060
28 142,410 5,040
Average 5,050
Services - Obtain samples of fresh concrete at the placement.locations, perform required field tests and cast compressive
strength samples.
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.
Page 2 of 7 ~,-LLW~.0~-F~.. ~.~
,CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 94021187.0173
Service Date: October 30, 2002
'lrerr can
8901 Carpenter Frwy, Ste #100
Dallas, Texas 75247
(214) 630-1010
Client: St. Joseph Village, Inc.
Attn: Joseph Dingman
13223 Glad Acres Drive
Dallas TX 75234
Report Date: November 27, 2002
Project: St. Joseph Village
1201 East Sandy Lake Rd
Coppell, TX 75019
Project Number: 94021187
Material Information
Specified Strength: 3000 psi ~ 28 Days
Batch Time: 10:58am
Supplier: Hanson
Truck No: 1015
Mix I.D. No.: 7724
Plant: 27
Ticket No: 272242
Sample Information
Sample Time: 12:25pm Date Cast: October 30, 2002
Technician: Michael P. Ardito
Weather Conditions: Cool,cloudy
Accumulative Yards: 300
Placement Method: Direct Discharge
Sample Locations: Sta. 12+00
Placement Location: See page 1
Field Test Data
Test
Result Specification Test Method
Slump, inches: 4.50 3-5 ASTM C-143
Air Content, %: 7.5 3-6 ASTM C-231
Concrete Temperature,° F: 69 55 - 95 ASTM C1064
Ambient Temperature, o F: 60 ASTM C-1064
Plastic Unit Weight, pcf:
Laboratory Test Data
Age at Maximum Compressive
Set Specimen Diameter Area Date Test Load Strength
No. ID (inches) (sq. inches) Tested (days) (lbs) (psi)
3 1 6.00 28.27 11/06/2002 7 106,230 3,760
3 2 6.00 28.27 11/06/2002 7 107,980 3,820
Average 3,790
3 3 6.00 28.27 11/27/2002 28 162,700 5,750
3 4 6.00 28.27 11/27/2002 28 155,510 5,500
Average 5,630
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.
Page 3 of 7 o~ L~w~.o~-~
CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 94021187.0173
Service Date: October 30, 2002
'lrerracan
8901 Carpenter Frwy, Ste #100
Dallas, Texas 75247
(214) 630-1010
Client: St. Joseph Village, Inc.
Attn: Joseph Dingman
13223 Glad Acres Drive
Dallas TX 75234
Report Date: November 27, 2002
Project: St. Joseph Village
1201 East Sandy Lake Rd
Coppell, TX 75019
Project Number: 94021187
Material Information
Specified Strength: 3000 psi ~ 28 Days
Batch Time: 12:25pm
Supplier: Hanson
Truck No: 1089
Mix I.D. No.: 7724
Plant: 27
Ticket No: 320668
Sample Information
Sample Time: 1:50pm Date Cast: October 30, 2002
Technician: Michael P. Ardito
Weather Conditions: Cool, cloudy
Accumulative Yards: 400
Placement Method: Direct Discharge
Sample Locations: Sta. 9+00
Placement Location: See page 1
Field Test Data
Test Result Specification Test Method
Slump, inches: 3.50 3-5 ASTM C-143
Air Content, %: 5.5 3-6 ASTM C-231
Concrete Temperature,° F: 66 55 - 95 ASTM C1064
Ambient Temperature, o F: 60 ASTM C-1064
Plastic Unit Weight, pcf:
Laboratory Test Data
Age at Maximum Compressive
Set Specimen Diameter Area Date Test Load Strength
No. ID (inches) (sq. inches) Tested (days) (lbs) (psi)
4 1 6.00 28.27 11/06/2002 7 129,700 4,590
4 2 6.00 28.27 11/06/2002 7 130,570 4,620
Average 4,610
4 3 6.00 28.27 11/27/2002 28 162,230 5,740
4 4 6.00 28.27 11/27/2002 28 163,840 5,790
Average 5,770
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.
Page 4 of 7 o~ LL~',.O,-~,*~'~.~
CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 94021187.0173
Service Date: October 30, 2002
'll'erracan
8901 Carpenter Frwy, Ste #100
Dallas, Texas 75247
(214) 630-1010
Client: St. Joseph Village, Inc.
Attn: Joseph Dingman
13223 Glad Acres Drive
Dallas TX 75234
Report Date: November 27, 2002
Project: St. Joseph Village
1201 East Sandy Lake Rd
Coppell, TX 75019
Project Number: 94021187
Material Information
Specified Strength: 3000 psi (~ 28 Days
Batch Time: 1:26pm
Supplier: Hanson
Truck No: 1888
Mix I.D. No.: 7724
Plant: 27
Ticket No: 272257
Sample Information
Sample Time: 2:3§pm Date Cast: October 30, 2002
Technician: Michael P. Ardito
Weather Conditions: Cool, cloudy
Accumulative Yards: 500
Placement Method: Direct Discharge
Sample Locations: Sta. 8+00
Placement Location: See page 1
Field Test Data
Test Result Specification Test Method
Slump, inches: 2.75 3-5 ASTM C-143
Air Content, %: 5.1 3-6 ASTM C-231
Concrete Temperature, o F: 68 55 - 95 ASTM C1064
Ambient Temperature, o F: 57 ASTM C-1064
Plastic Unit Weight, pcf:
Laboratory Test Data
Age at Maximum Compressive
Set Specimen Diameter Area Date Test Load Strength
No. ID (inches) (sq. inches) Tested (days) (lbs) (psi)
5 1 6.00 28.27 11/06/2002 7 123,800 4,380
5 2 6.00 28.27 11/06/2002 7 125,890 4,450
Average 4,420
5 3 6.00 28.27 11/27/2002 28 147,440 5,210
5 4 6.00 28.27 11/27/2002 28 149,250 5,280
Average 5,250
Services - Obtain samples of fresh concrete at the placement locations, pedorm required field tests and cast compressive
strength samples.
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.
Page 5 of 7 Q~ LLW~,0,-~,
CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 94021187.0173
Service Date: October 30, 2002
31'erracan
8901 Carpenter Frwy, Ste #100
Dallas, Texas 75247
(214) 630-1010
Client: St. Joseph Village, Inc.
Attn: Joseph Dingman
13223 Glad Acres Drive
Dallas TX 75234
Report Date: November 27, 2002
Project: St. Joseph Village
1201 East Sandy Lake Rd
Coppell, TX 75019
Project Number: 94021187
Material Information
Specified Strength: 3000 psi (~ 28 Days
Batch Time: 2:45pm
Supplier: Hanson
Truck No: 890
Mix I.D. No.: 7724
Plant: 27
Ticket No: 320685
Sample Information
Sample Time: 4:30pm Date Cast: October 30, 2002
Technician: Michael P. Ardito
Weather Conditions: Cool, cloudy
Accumulative Yards: 600
Placement Method: Direct Discharge
Sample Locations: Sta. 7+00
Placement Location: See page 1
Field Test Data
Test
Result Specification Test Method
Slump, inches: 3.00 3-5 ASTM C-143
Air Content, %: 5.3 3-6 ASTM C-231
Concrete Temperature,° F: 65 55 - 95 ASTM C1064
Ambient Temperature, o F: 65 ASTM C-1064
Plastic Unit Weight, pcf:
Laboratory Test Data
Age at Maximum Compressive
Set Specimen Diameter Area Date Test Load Strength
No. ID (inches) (sq. inches) Tested (days) (lbs) (psi)
6 1 6.00 26.27 11/06/2002 7 159,380 5,640
6 2 6.00 28.27 11/06/2002 7 160,690 5,680
Average 5,660
6 3 6.00 28.27 11/27/2002 26 191,750 6,780
6 4 6.00 28.27 11/27/2002 28 197,110 6,970
Average 6,880
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.
Page 6 of 7
CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 94021187.0173
Service Date: October 30, 2002
ll'erracan
8901 Carpenter Fn,vy, Ste #100
Dallas, Texas 75247
(214) 630-1010
Client: St. Joseph Village, Inc.
Attn: Joseph Dingman
13223 Glad Acres Drive
Dallas TX 75234
Report Date: November 27, 2002
Project: St. Joseph Village
1201 East Sandy Lake Rd
Coppell, TX 75019
Project Number: 94021187
Material Information
Specified Strength: 3000 psi ~ 28 Days
Batch Time: 4:00pm
Supplier: Hanson
Truck No: 80
Mix I.D. No.: 7724
Plant: 27
Ticket No: 320690
Sample Information
Sample Time: 5:15pm Date Cast: October 30, 2002
Technician: Michael P. Ardito
Weather Conditions: Cool, cloudy
Accumulative Yards: 680
Placement Method: Direct Discharge
Sample Locations: Sta. 6+19
Placement Location: See page 1
Field Test Data
Test
Result Specification Test Method
Slump, inches: 3.00 3-5 ASTM C-143
Air Content, %: 5.0 3-6 ASTM C-231
Concrete Temperature,° F: 66 55 - 95 ASTM C1064
Ambient Temperature, o F: 57 ASTM C-1064
Plastic Unit Weight, pcf:
Laboratory Test Data
Age at Maximum Compressive
Set Specimen Diameter Area Date Test Load Strength
No. ID (inches) (sq. inches) Tested (days) (lbs) (psi)
7 1 6.00 28.27 11/06/2002 7 122,090 4,320
7 2 6.00 28.27 11/06/2002 7 112,880 3,990
Average 4,160
7 3 6.00 28.27 11/27/2002 28 134,140 4,740
7 4 6.00 28.27 11/27/2002 28 132,390 4,680
Average 4,710
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples. , ..........
....' '-....
~ LY~gOr~ J. COX
Technician: Michael P. Ardito
Repo~ Distribution: ...... ~-- "'-~ HBC/Terraco~
(1) St. Joseph Village, Inc. (1) City of Coppell Engineering
(1) hguirre Corporation (1) SI Andrews Management Reviewed by:
(1) Centex - Jobsite (1) St Andrews Management ~ Lyndon J/~ox, P.E.
(1) Ci~ of Coppell - Bldg Insp Princip~lEngineer
The tests were pedormed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This repoA is exclusively for t~ use of the client
indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitt~ herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the propeAies of other apparently similar or identical
materials.
Page 7 of 7