Amberpoint BP-LR030402FIELD DENSITY TESTING
Report Number: 94021029.0349
Service Date: March 24, 2003
'lrerracan
8901 Carpenter Frwy, Ste #100
Dallas, Texas 75247
(214) 630-1010
Client: Transwestern Commercial Services
Attn: Jim Gaspard
5001 Spring Valley Rd Ste 600 W
Dallas TX 75244
Report Date: April 02,~.003
Project,:Amberpoint Building N(~, 1· ·
Amberpoint Bus. Pk. @ Coppell
Coppell, TX
Project Number: 94021029
Material Information
Material Laboratory
No. Test Method
Description and Classification
Lab Test Data Project Requirements
Optimum Max. Lab Water
Water Dry Unit Content Minimum Dry
Content Weight Range Unit Weight
(%) (pcf) (%) (% compaction)
1. 210290004 ASTM D-698 Dk brown clay
Field Test Data
Test
No. Test Location
22.4 99.9 -1/+3 95
Probe Water Dry Unit Dry Unit
Lift/ Mat. Depth Content Weight Weight
Elevation No. (inches) (%) (pcf) (% compaction)
Parking Lot Subgrade
348 75' N & 20' W of NW building corner
349 75' N & 100' E of NW building corner
350 75' N & 200' E of NW building corner
351 75' N & 150' W of NE building corner
352 75' N & 20' W of NE building corner
353 75' N & 80' E of NE building corner
At Grade I 6 21.6 95.6 (~' 96
At Grade 1 6 23.4 95.4 f 95
At Grade 1 6 24.6 96.3 96
At Grade 1 6 24.1 95.0 95
At Grade 1 6 23.2 96.4 ! 96
At Grade 1 6 23.9 96.1 ~ 96
Comments:
Test results on this report meet project specification.
Services - Perform in-place density and moisture content tests to determine degree of compaction and material moisture
condition.
Field Test Method~,STM D2922, ASTM D3017
Gauge ID:
Field Results Reported To: Brian w/Hill & Wilkinson, Ltd.
Technician: Bradford T. Rengstorff
Report Distribution:
(1) Transwestern Commercial Services (1) State Farm Insurance Co
(1) TechniStructures (1) Hill & Wilkinson Ltd
(1) O'Brien & Assoc (1) Hill & Wilkinson Ltd
(1) Halff Assoc Inc (1) Halff Assoc Inc
Reviewed by:
HBCFFerr~
Euge~Harbour
Principal
The tests were performed in general accordance with applicable ASTM. AASHTO. or DOT test methods. This report is exclusively for the use of the client
indicated above and shah not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.
Page 1 of 1 07.~<s,,o,.F~,.~.v