PA0101-LR020926ALPHA TESTING, INC. 2209 Wisconsin St.. Suite 100 Dollop, Texos 7~229 972/620-8~11 - 972/263-4937 (Metro) FAX: ~72/406-8023 TESTED FOR JMC CONSTRUCTION McKINNEY, TEXAS REPORT OF FIELD COMPACTION TESTS DATE: 09~26~02 PROJECT COPPELL TRAIL SECTIONS COPPELL, TEXAS OUR REPORT NO.: 02660-18 TEST DATA: TEST ~ ELEV. · SO.IL ID OPTIMUM klAXlMUM LAB IN PLACE IN PLACE PERCENT NO. DATEDEPTH~ NUMBER MOISTURE DRY DENSITY MOISTURE DRY DENSITY COMPACTION COMMENT* % PCF % PCF 18 09/26/02 FG 1 17.0 108 21.0 106 99 1-A 19 09126/02 FG 1 17.0 108 20.2 107 99 1 -A TEST LOCATION: 18 SIDEWALK SECTION #3 AT STATION 15+00 19 SIDEWALK SECTION #3 AT STATION 12+00 CC: SCHRICKEL, ROLLINS AND ASSOCIATES, INC.; THE CITY OF COPPELL 1 FILL * A IN PLACE PERCENT MOISTURE AND PERCENT COMPACTION COMPLY WITH SPECIFICATIONS . 2 NATURAL SUBGRADE B. PERCENT COMPACTION DOES NOT COMPLY WITH SPECIFICATIONS Re~ully~ 3 LIME STABILIZED C. PERCENT ,N PLACE MOISTURE DOES NOT COMPLY W,TH SPEC,FICATIONS 4. CEMENT TREATED D RETEST ~" "~ A~.~ Our test results & reports ace for the exclulli~ use of the Client (and thew des*gnated recipients on file in our office) and shall not be reproduced and/or distributelJ e._~.pt.-~th express approval of ALPHA. The use of our name & lest results mus~ receNe our written approval Test results & reports apply only to the samples tested and/or observed, and are not indicative of the qualities of apparently identical or similar specimens Geotechnical Engineering · Construction Materials Testing · Environmental Engineering · Consulting