Securelock-CS030624eresa fiumer Re: Securlock Self Storage D esign Qu estions Page 1
From: Teresa Turner
To: tporter @daa- civil.com
Date: 6/24/03 3:57:00 PM
Subject: Re: Securlock Self Storage Design Questions
I just spoke with Ken and here's what I have for you......
1. The maximum invert in the fire lane is 6 ". You can use the full 24' width of the fire lane for capacity.
You just need to show the calculations to verify that the capacity is there.
2. We are currently revising our citywide water master plan and a 12" waterline is proposed within the SH
121 frontage road right -of -way. This will be required to be built along the entire length of the Securelock
property from Northpoint Drive. It will also eliminate any need for easements across the proposed
restaurant site to loop your fire line. Ken believes that TOOT will provide you with a timely permit for the
waterline construction.
3. Since TxDOT requires an 8" fall into the property from the driveway, Ken will require the drive approach
to be constructed with concrete. Asphalt will not hold up with the suface flow of the drainage across the
drive.
4. Ken said that he needs more information on the retention ( ?) pond. He is not comfortable with making
a decision on something so conceptual. He is also curious as to exactly what it is if it's not detention (with
an outfall) or retention (with some circulation). Is it standing stagnant water?
Please let me know if you have questions. Thanks
Teresa
Tim:
Ken has the drawing on his desk. I spoke with him this morning and he will be out of the office this week
Wed. - Fri. so he said he will make some time for me today or tomorrow to discuss this project.
wouldn't think you would need an 8" S.S. I would think that a 6" would suffice. It's usually a good idea to
include a profile in the plans, especially for such a long run as what you will probably need.
I will get in touch with you before the end of the day tomorrow - once I tie Ken down to discuss the
drainage issues.
Teresa
>>> "Tim Porter" < tporter(@daa- civil.com 6/23/03 11:37:53 AM >>>
Hello again. I'm sorry to bug you once again but, I figure any questions
I can ask up front will save us both some time in the end.
I wanted to ask if you had a chance to ask Ken his opinion of the storm
drainage situation at the Securlock Site. I think you were able to run
off a copy of my thoughts so you could set them in front of Ken.
Also, do we need 8" sanitary sewer on this site? If so, do I need to
profile it for you?
Just let me know
e Teresa Turner Re: Secur lock S effStor 2 age Des ign Quest � Page 2
Thanks!
Timothy J. Porter, P.E.
Dowdey, Anderson, and Associates, Inc.
972.931.0694