Callahan-LR030127FAR60 CONSULTANTS, INC. 11440 Reeder Rd. • Dallas, TX 75229 Tel. (214) 352-4100 • Fax (214) 352-4Sll COMPRESSIVE STRENGTH OF CONCRETE REPORT CLIENT: Bonner Associates PROJECT: Callahan Addition Connell. Texas Sample Date: 1-27-03 Project No.: M02-412 CONCRETE INFORMATION CONTRACTOR: TICKET NO.: AMBIENT TEMP. (°F): CONCRETE TEMP, (°F): TIME BATCHED: TIME SAMPLED: WEATHER CONDITION: LOCATION OF PLACEMENT: C3 Constructors 104138 CONCRETE SUPPLIER: Redi-Mix 54 PLANTITRUCK: 1/ 127 53 MIX ID NUMBER: 723 12:30 p.m. AIR (%) (ASTM C•173) 5.3 12:48 p.m. WATER ADDED (gal): 0 Partly cloudy SLUMP (inches) (ASTM c-1a3) 6 Paving, fire lane - 40' south by 6' east from southeast corner of building pad CONCRETE CYLINDER COMPRESSIVE STRENGTH TESTS Standard 6" x 12", 28.27 square inches CYLINDER NUMBER AGE (Days) DATE TESTED TOTAL LOAD (Pounds) COMPRESSIVE STRENGTH (PSI) SPECIFIED COMPRESSIVE STRENGTH tPsl) 1A 7 2-3-03 65000 2300 3000/28 da s 1B 28 2-24-03 80000 2830 1C 28 2-24-03 85000 3010 117 56 3-24-03 105000 3710 Specifications: Making & ASTM C-31 Testing Methods: ASTM C-143, ASTM C-39 Curin Remarks: 28 day average of 2920 psi does not comply with project requirements. Technician: Dan Rotty, EIT FARGO CONSULTANTS, INC. Distribution: Bonner Associates -Tim Bonner City of Coppell -Rick Odell C3 Constructors -Taylor Bames Checked By: f ~~`" ,.. i' Environmental Services ^ Geotechnica/ Engineering ^ Construction Materials Testing T~ROO OONBVLTANTB, INO. 11440 Reeder Rd. • Dallas, TX 75229 Tel. (214) 352-4100 • Fax (214) 352-481 I COMPRESSIVE STRENGTH OF CONCRETE REPORT CLIENT: Bonner Associates PROJECT: Callahan Addition Connell. Texas Sample Date: 1-27-03 Project No.: M02-412 CONCRETE INFORMATION ~ CONTRACTOR: TICKET NO.: AMBIENT TEMP. (°F): CONCRETE TEMP. (°F): TIME BATCHED: TIME SAMPLED: WEATHER CONDITION: LOCATION OF PLACEMENT: C3 Constructors 104168 CONCRETE SUPPLIER: Redi-Mix 54 PLANTITRUCK: 1 J 277 53 MIX ID NUMBER: 723 3:00 p.m. AIR (%~ (ASTM C-173) 3.8 3:19 p.m. WATER ADDED (gal): 0 Partly cloudy SLUMP (inches) (ASrM c-143) 4 Paving, fire lane - 50' south by 10' west from southwest corner of building pad CONCRETE CYLINDER COMPRESSIVE STRENGTH TESTS Standard 6" x 12",28.27 square inches CYLINDER NUMBER AGE (Days) DATE TESTED TOTAL LOAD (Pounds) COMPRESSIVE STRENGTH (psi) SPECIFIED COMPRESSIVE STRENGTH (psi) 2A 7 2-3-03 100000 3540 3000! 28 da s 26 28 2-24-03 135000 4780 2C 28 2-24-03 128500 4550 2D Hold - Specifications: Making 8 ASTM C-31 Tesing Methods: ASTM C-143, ASTM C-39 Curin Technician: Dan Rotty, EIT Distribution: Bonner Associates -Tim Bonner City of Coppell -Rick Odel] C3 Constructors -Taylor Barnes FARGO CONSULTANTS, INC. Checked By: Environmental Services ~ Geotechnical Engineering ~ Construction Malenals Testing i FAROO CONSULTANTS, INC. 11440 Reeder Rd. • Dallas, TX 75229 Tel. (214) 352-4100 • Fax (214) 352-481 I COMPRESSIVE STRENGTH OF CONCRETE REPORT CLIENT: Bonner Associates PROJECT: Callahan Addition Connell, Texas Sample Date: 1-27-03 Project No.: M02-412 CONCRETE INFORMATION ~ CONTRACTOR: TICKET NO.: AMBIENT TEMP. (°F): CONCRETE TEMP. (°F): TIME BATCHED: TIME SAMPLED: WEATHER CONDITION: LOCATION OF PLACEMENT: C3 Constructors 104138 CONCRETE SUPPLIER: Redi-Mix 54 PLANTITRUCK: 1/ 127 53 MIX ID NUMBER: 723 12:30 p.m. AIR (%) (ASTM C-173) 5.3 12:48 p.m. WATER ADDED (gal): 0 Partly cloudy SLUMP (inches) (ASTM C-143) 6 Paving, fire lane - 40' south by 6' east from southeast corner of building pad CONCRETE CYLINDER COMPRESSIVE STRENGTH TESTS Standard 6" x 12", 28.27 square inches CYLINDER NUMBER AGE (Days) DATE TESTED TOTAL LOAD (Pounds) COMPRESSIVE STRENGTH (Psi) SPECIFIED COMPRESSIVE STRENGTH (Psi) 1A 7 2-3-03 65000 2300 3000128 da s 1B 28 2-24-03 80000 2830 1C 28 2-24-03 85000 3010 1 D 56 3-24-03 Specifications: Making & ASTM C-31 Testing Methods: ASTM C-143, ASTM C-39 Curing: Remarks: 28 day average of 2920 psi does not comply with project requirements. Technician: Dan Rotty, EIT Distribution: Bonner Associates -Tim Bonner City of Coppell -Rick Odell C3 Constructors -Taylor Barnes FARGO CONSULTANTS, INC. Checked By: ~ Environmenfa/ Services ^ Geotechnica/ Engineering ^ Construction Materia/s Testing i FAROO CONSULTANTS, INC. ] 1440 Reeder Rd. • Dallas, TX 75229 Tel. (214) 352-4100 • Fax (214) 352-4811 COMPRESSIVE STRENGTH OF CONCRETE REPORT CLIENT: Bonner Associates Sample Date: 1-27-03 PROJECT: Callahan Addition Project No.: M02-412 Copoell. Texas CONCRETE INFORMATION CONTRACTOR: C3 Constructors TICKET NO.: 104168 CONCRETE SUPPLIER: Redi-Mix AMBIENT TEMP. (°F): S4 PLANT/TRUCK: 11277 CONCRETE TEMP. (°F): 53 MIX ID NUMBER: 723 TIME BATCHED: 3:00 p.m. AIR (%) (ASTM C-173) 3.8 TIME SAMPLED: 3:19 p.m. WATER ADDED (gal): 0 WEATHER CONDITION: Partly cloudy SLUMP (inches) (ASTM c-~a3) 4 LOCATION OF PLACEMENT: Paving, fire lane - 50' so uth by 10' west from southwest corner of building pad CONCRETE CYLINDER COMPRESSIVE STRENGTH TESTS Standard 6" x 12", 28.27 square inches CYLINDER NUMBER AGE (Days) DATE TESTED TOTAL LOAD (Pounds) COMPRESSIVE STRENGTH (psi) SPECIFIED COMPRESSIVE STRENGTH (psi) 2A 7 2-3-03 100000 3540 3000! 28 da s 2B 28 2-24-03 2C 28 2-24-03 2D Hold - Specifications: Making & ASTM C-31 Testing Methods: ASTM C-143, ASTM C-39 Curin Technician: Dan Rotty, EIT Distribution: Bonner Associates -Tim Bonner City of Coppell -Rick Odell C3 Constructors -Taylor Barnes FARGO CONSULTANTS, INC. Checked By:~~~ Environmental Services ^ Geotechnical Engineering /Construction Materia/s Testing i FAR60 CONSULTANTS, INC. 11440 Reeder Rd. • Dallas, TX 75229 Tel. (2l4) 352-4100 • Fax (214) 352-4811 COMPRESSIVE STRENGTH OF CONCRETE REPORT CLIENT: Bonner Associates PROJECT: Callahan Addition Copnell, Texas Sample Date: 1-27-03 Project No.: M02-412 CONCRETE INFORMATION ~ CONTRACTOR: TICKET NO.: AMBIENT TEMP. (°F): CONCRETE TEMP. (°F): TIME BATCHED: TIME SAMPLED: WEATHER CONDITION: LOCATION OF PLACEMENT: C3 Constructors 104138 CONCRETE SUPPLIER: Redi-Mix 54 PLANT/TRUCK: 1/ 127 53 MIX ID NUMBER: 723 12:30 p. m. AIR (%) (ASTM C-173) 5.3 12:48 p. m. WATER ADDED (gal): 0 Partly cloudy SLUMP (inches) (ASTM c-ta3- 6 Paving, fire lane - 40' south by 6' east from southeast corner of building pad CONCRETE CYLINDER COMPRESSIVE STRENGTH TESTS Standard 6" x 12", 28.27 square inches CYLINDER NUMBER AGE (Days) DATE TESTED TOTAL LOAD (Pounds) COMPRESSIVE STRENGTH (psi) SPECIFIED COMPRESSIVE STRENGTH (psi) 1A 7 2-3-03 65000 2300 3000128 da s 1 B 28 2-24-03 1 C 28 2-24-03 1 D Hold - Specifications: Making 8 ASTM C-31 Testing Methods: ASTM C-143, ASTM C-39 Curin Technician: Dan Rotty, EIT Distribution: Bonner Associates -Tim Bonner City of Coppell -Rick Odell C3 Constructors -Taylor Barnes FARGO CONSULTANTS, INC. Checked By:~ Environmental Services ^ Geotechnica/ Engineering ~ Construction Materia/s Testing