Structural Steel Inspection
Report of Inspection
On this date, a Rone Engineers, Ltd. representative(s) arrived on site as
scheduled to perform Structural Steel Inspection. The results are attached.
Technician Time: 11:45 AM 3:30 PM
Technician: D, Wilcher CAWI- 02040654
Report Distribution:
(1) Duke Realty Services, LP
(1) Duke Realty Services, LP
(1) City of Coppell Engineering Dept.
(1) Pacheco Koch Consulting Engineers
(1) Engineering Analyst
(1) City of Coppell Bldg. Inspections
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77040
Corporate Phone: (214) 630 -9745
REPORT OF STRUCTURAL STEEL INSPECTION
Report No.:
Project No.:
Date of Service:
Report Date:
601726
037333
07/14/2003
08/05/2003
Rone Engineers, Lt
M. Tupa, C 94030831
Certified Welding Inspector
ICBO# 97537531
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and
reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd.
99DF Page 1 of 1
Client:
Duke Realty Services, LP
Report
601726
Project:
Freeport 10
Project
037333
500 Freeport Parkway
Date of Service:
07/14/03
Coppell, TX
RoneEngineers
to
A LEIGH COMPANY
Drawings Utilized:
*Discrepancies Comments:
Mike Tupa
Certified Welding Inspector
CWI #94030831
REPORT OF
STRUCTURAL STEEL INSPECTION
8908 Ambassador Row
Dallas, Texas 75247
214.630.9745 FAX 214.630.9819
Service: Perform a Structural Steel Inspection as detailed below.
Structural
Locations and Items Inspected: 1. Bar joist inspection at grid location A.3 to H and 10 through 15
2. W.Q.T.'s review documentation
Rone Engineers arrived at the above location as per the request of Michael Cox, the superintendent for Duke
Construction Company, the general contractor, to begin monitoring the steel erection by Ramco Steel
Erectors. The results of today's inspection are listed as follows:
I. W.Q.T.'s not on file for review. After conversation with the steel erection superintendent, the
W.Q.T.'s will be provided on the next inspection. Rone will carry this item as open until such time as
proper W.Q.T.'s are provided for review. (non compliant)
II. Bar joist inspection of the roof framing at grid location A.3 to H and 10 through 15 is as follows;
A. *At this time, all joist seat welds were not de- slagged which is non compliant with AWS D1.1 -02
code requirements. After a conversation with the superintendent for Duke Construction Company
and the structural engineer, Steve Burns with Engineering Analysts and Ramco Steel Erectors
who stated that the welds at the joist bearing plates will not be de- slagged as per written directive
by the structural engineer. Rone has been instructed by the structural engineer to simply verify
that there appears to be fillet welds installed on each side of the joist seat. Rone has agreed to
inspect per the inspection criteria given as long as written documentation is provided by the
structural engineer accepting the responsibility for visual acceptance criteria that can not be
performed by Rone Engineers as per AWS D1.1 -02. Until documentation has been received and
Page 2 of 3
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in
quality (composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no
control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written
approval of Rone Engineers, Ltd.
Client:
Duke Realty Services, LP
Report
601726
Project:
Freeport 10
Project
037333
500 Freeport Parkway
Date of Service:
07/14/03
Coppell, TX
RoneEngineers
A LEIGH COMPANY
REPORT OF
STRUCTURAL STEEL INSPECTION
8908 Ambassador Row
Dallas, Texas 75247
214.630.9745 FAX 214.630.9819
reviewed, this item will be open per AWS D1.1 -02 code and specification requirements. (non
compliant)
III. The horizontal bridging was installed and welded as per the job specifications and SJI specifications
and AWS D1.1 -02, compliant.
IV. The diagonal x- bracing was installed and welded as per the SJI specifications and AWS D1.1 -02 code
requirements, and AISC specifications for the snug -tight tensioning method concerning the bolted
connection locations, compliant.
V. The perimeter edge angle was installed and field welded. The welds were not de- slagged in all
locations. Rone is simply verifying there appears to be welded attachments to the bar joist and embeds.
RFI documentation is required from the structural engineer of record on the non deslagging of the fillet
field welds to determine the visual weld profile per A.W.S. code requirements. This item of concern
will remain an open issue until documentation is received and reviewed.
*Note: Rone is in receipt of the RFI's for bar joist wall pockets that were field modified to accept the
bar joists.The RFI's are included in today's report.
Mike Tupa
Certified Welding Inspector
CWI #94030831
Page 3 of 3
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in
quality (composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no
control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written
approval of Rone Engineers, Ltd.