Freeport NIP(7.0)-LR030813RoneEngineers
A LEIGH COMPANY
Project:
Services:
M/D No.
1
TEST
NO
Dark Brown Clay
Technician: Lanny Gist
Report Distribution:
(1) Duke Realty Services, LP
(1) Duke Realty Services, LP
(1) City of Coppell Engineering Dept.
(1) Pacheco Koch Consulting Engineers
Client: Duke Realty Services, LP
Attn: Mr. Jeff Langston
5495 Belt Line Road, Suite 360
Dallas TX 75254
Freeport 10
500 Freeport Parkway
Coppell, TX
Perform In -Place Density Test in accordance with ASTM Standards.
CONTRACTOR: Duke Realty Services, LP
Test Methods: ASTM D 2922
ASTM D 3017
Description
TEST LOCATION
Fill
1 East firelane, 150' south of the northeast
corner building, subgrade
Fill
2 East firelane, 100' south of the northeast
corner building, 1st lift
Fill
3 East firelane, 50' south of the northeast
corner building, 2nd lift
PROJECT DATA
Gauge: polder 3430
Gauge Serial No: 31705
Test Mode: DT
MOISTURE DENSITY RELATIONS
Maximum
Moisture Density pef
19.5
FIELD DENSITY TESTS
Test results on this report meet project specification.
Started: 6:30AM
PROBE
DEPTH
(1) Engineering Analyst
(1) City of Coppell Bldg. Inspections
WD
No.
6" 1
6" 1
6" 1
Finished: 2:OOPM
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77040
Corporate Phone: (214) 630 -9745
IN -PLACE DENSITY TESTING
Current: 707
Previous: 711
104.5
19.6
20.1
20.8
Report No.:
Project No.:
Date of Service:
Report Date:
192146
037333
08/05/2003
08/13/2003
Standard Counts
Moisture Density
Optimum
Rone
119.4
124.4
126.0
Current: 2736
Previous: 2733
Project Requirements
Moisture Density
MOISTURE WET DENSITY DRY DENSITY
(Pee (WO
99.8
103.6
104.3
Scott Watson, AET
CMT Operations Manager
95 min
DENSITY
max)
96
99
100
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and
reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd.
07DF Page 1 of 1
RoneEngineers
A LEIGH COMPANY
Client: Duke Realty Services, LP
Attn: Mr. Jeff Langston
5495 Belt Line Road, Suite 360
Dallas TX 75254
Project:
Services:
CONTRACTOR: Duke Realty Services, LP
Test Methods:
M/D No.
1
TEST
NO
Perform In -Place Density Test in accordance with ASTM Standards.
ASTM D -2922
ASTM D -3017
Dark Brown Clay
Backfill
1 Office leave
final
Backfill
2 Office leave
final
Backfill
3 Office leave
final
Backfill
4 Office leave
final
Description
TEST LOCATION
out, building column line C -6,
out, building column line C-4,
out, building column line D -3,
out, building column line C -1,
Gauge: Troxler 3430
Gauge Serial No: 31705
Test Mode: DT
Technician: Lanny Gist Started: 12:0OP
Report Distribution:
(I) Duke Realty Services, LP
(1) Duke Realty Services, LP
(1) City of Coppell Engineering Dept.
(I) Pacheco Koch Consulting Engineers
PROJECT DAT
MOISTURE DENSITY RELATIONS
Maximum
Moisture Density pcf
FIELD DENSITY TESTS
PROBE
DEPTH
(1) Engineering Analyst
(1) City of Coppell Bldg. Inspections
M/D
No.
6" 1
6" 1
6" 1
6" 1
Finished: 2:OOPM
IN -PLACE DENSITY TESTING
Report No.:
Project No.:
Date of Service:
Report Date:
Standard Counts
Moisture Density
Current: 702 Current: 2740
Previous: 707 Previous: 2736
19.5 104.5 +3 or above 92 96
MOISTURE WET DENSITY DRY DENSITY DENSITY
(pen (pcfj max)
23.1 119.5
23.7 121.2
22.7 122.0
24.0 119.8
Test results on this report meet project specification.
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77040
Corporate Phone: (214) 630 -9745
192209
037333
08/06/2003
08/13/2003
Project Requirements
Moisture Density
K. Scott Watson, AET
CMT Operations Manager
97.1 93
98.0 94
99.4 95
96.6 92
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and
reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd.
07DF Page 1 of 1
RoneEngineers
A LEIGH COMPANY
Client: Duke Realty Services, LP
Attn: Mr. Jeff Langston
5495 Belt Line Road, Suite 360
Dallas TX 75254
Project:
Services:
CONTRACTOR:
CONCRETE SUPPLIER:
PLANT:
STRENGTH:
SLUMP (In):
AIR
TEST METHOD:
CYLINDER
MARKED
SET NO.
1 1
1 2
1 3
Freeport 10
500 Freeport Parkway
Coppell, TX
Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
SPECIFICATION REQUIREMENTS
Duke Realty Services, LP
Potter
On Site
4000 psi 28 Days
5" maximum
3 -6%
ASTM C -172
ASTM C -31
ASTM C -143
ASTM C -231
ASTM C -1064
ASTM C -138
ASTM C -39
Concrete Compressive Cylinder 6" x 12" (area 28.27 sq. in.)
MEASURED
SLUMP DATE
(Inches) TESTED
4.5 07/22/2003
4:5 08/12/2003
4.5 08/12/2003
1 4 Hold
CONCRETE COMPRESSIVE STRENGTH TEST
PROJECT DATA
REPORT OF TESTS
Report No.:
Project No.:
Date of Service:
Report Date:
MIX DESIGN I.D.: 7752
PLACEMENT DATE: 07/15/2003
WEATHER CONDITIONS: Clear
TIME SAMPLED: 7:25am BATCH TIME. 7.14am
TEMPERATURE (F) AIR 76 F CONCRETE: 88 F
TRUCK NO: 119 TICKET NO: 117217
AIR CONTENT 3.7 UNIT WEIGHT (pct): NA
OVERALL PLACEMENT LOCATION:
South parking lot, south half, building column line GG to MM
SAMPLE LOCATION: 30' east, 15' north, southwest
corner
AGE
(days)
7
28
28
MAXIMUM
LOAD
(Ibs. force)
101375
123660
127305
Average
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77040
Corporate Phone: (214) 630 -9745
COMPRESSIVE
STRENGTH
(psi)
3580
4370
4500
4440
190770
037333
07/15/2003
08/13/2003
FRACTURE
TYPE
Unbonded Cap
Unbonded Cap
Unbonded Cap
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and
reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd.
OIDD Page 1 of 5
RoneEngineers
A LEIGH COMPANY
CYLINDER
MARKED
SET NO.
Project:
Services:
Client: Duke Realty Services, LP
Attn: Mr. Jeff Langston
5495 Belt Line Road, Suite 360
Dallas TX 75254
Freeport 10
500 Freeport Parkway
Coppell, TX
Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
CONTRACTOR: Duke Realty Services, LP
CONCRETE SUPPLIER: Potter
PLANT: On Site
SPECIFICATION REQUIREMENTS
STRENGTH: 4000 psi 28 Days
SLUMP (in): 5" maximum
AIR
TEST METHOD:
ASTM C -172
ASTM C -31
ASTM C -143
ASTM C -231
ASTM C -1064
ASTM C -138
ASTM C -39
MEASURED
SLUMP
(inches)
2 1 5.0
DATE
TESTED
07/22/2003
2 2 5.0 08/12/2003
2 3 5.0 08/12/2003
2 4
Hold
CONCRETE COMPRESSIVE STRENGTH TEST
PROJECT DATA
REPORT OF TESTS
Report No.:
Project No.:
Date of Service:
Report Date:
MIX DESIGN I.D,: 7752
PLACEMENT DATE: 07/15/2003
WEATHER CONDITIONS: Clear
TIME SAMPLED: 8:02am BATCH TIME: 7:1 Oam
TEMPERATURE (F) AIR 80 F CONCRETE: 89 F
TRUCK NO: 118 TICKET NO: 117226
3% 6% AIR CONTENT (36): 3.9 UNIT WEIGHT (pet): NA
OVERALL PLACEMENT LOCATION:
South parking lot, south half, building column line OO to MM
SAMPLE LOCATION: 25, north, 10' west, southeast
corner
Concrete Compressive Cylinder 6" x 12" (area 28.27 sq. in.)
AGE
(days)
7
28
28
MAXIMUM
LOAD
(Ibs. force)
97755
123555
120150
Average
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77040
Corporate Phone: (214) 630 -9745
COMPRESSIVE
STRENGTH
(psi)
3460
4370
4250
4310
190770
037333
07/15/2003
08/13/2003
FRACTURE
TYPE
Unbonded Cap
Unbonded Cap
Unbonded Cap
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and
reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd.
OIDD Page 2 of 5
RoneEngineers
A LEIGH COMPANY
Client: Duke Realty Services, LP
Attn: Mr. Jeff Langston
5495 Belt Line Road, Suite 360
Dallas TX 75254
Project:
Services:
CONTRACTOR:
CONCRETE SUPPLIER:
PLANT:
SPECIFICATION REQUIREMENTS
STRENGTH:
SLUMP (In):
AIR (°A):
TEST METHOD:
CYLINDER
MARKED
SET NO.
3 1
3 2
3 3
Freeport 10
500 Freeport Parlcway
Coppell, TX
Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Duke Realty Services, LP
Potter
On Site
4000 psi 28 Days
5" maximum
ASTM C -172
ASTM C -31
ASTM C -143
ASTM C -231
ASTM C -1064
ASTM C -138
ASTM C -39
Concrete Compressive Cylinder 6" x 12" (area 28.27 sq. in.)
MEASURED
SLUMP DATE
(inches) TESTED
5.0 07/22/2003
5:0 08/12/2003
5.0 08/12/2003
3 4 Hold
CONCRETE COMPRESSIVE STRENGTH TEST
PROJECT DATA
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77040
Corporate Phone: (214) 630 -9745
Report No.:
Project No.:
Date of Service:
Report Date:
190770
037333
07/15/2003
08/13/2003
MIX DESIGN I.D.: 7752
PLACEMENT DATE: 07/15/2003
WEATHER CONDITIONS: Clear
TIME SAMPLED: 9:05am BATCH TIME: 8:52am
TEMPERATURE (F) AIR 82 F CONCRETE: 88 F
TRUCK NO: 119 TICKET NO: 117235
3% 6% AIR CONTENT 4.1 UNIT WEIGHT (pct): NA
OVERALL PLACEMENT LOCATION:
South parking lot, south half, building column line OO to MM
SAMPLE LOCATION: 20' north, 100' east, southwest
comer
REPORT OF TESTS
AGE
(days)
7
28
28
MAXIMUM
LOAD
(lbs. force)
89260
118855
111125
Average
Does not comply with specified strength.
COMPRESSIVE
STRENGTH
(psi)
3160
4200
3930
4070
FRACTURE
TYPE
Unbonded Cap
Unbonded Cap
Unbonded Cap
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and
reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd.
01DD Page 3 of 5
RoneEngineers
A LEIGH COMPANY
Client: Duke Realty Services, LP
Attn: Mr. Jeff Langston
5495 Belt Line Road, Suite 360
Dallas TX 75254
Project: Freeport 10
500 Freeport Parkway
Coppell, TX
Services: Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
CONTRACTOR: Duke Realty Services, LP
CONCRETE SUPPLIER: Potter
PLANT: On Site
SPECIFICATION REQUIREMENTS
STRENGTH: 4000 psi 28 Days
SLUMP (in): 5" maximum
AIR
TEST METHOD: ASTM C -172
ASTM C -31
ASTM C -143
ASTM C -231
ASTM C -1064
ASTM C -138
ASTM C -39
CYLINDER
MARKED
SET NO.
4 1 5.0
3% 6% AIR CONTENT 4.0 UNIT WEIGHT (pci): NA
MEASURED
SLUMP
(inches)
DATE
TESTED
07/22/2003
4 2 5.0 08/12/2003
4 3 5.0 08/12/2003
4 4 Hold
PROJECT DATA
REPORT OF TESTS
OVERALL PLACEMENT LOCATION:
South parking lot, south half, building column line GG to MM
SAMPLE LOCATION: 130' east, 10' south, northwest
comer
Concrete Compressive Cylinder 6" x 12" (area 28.27 sq. in.)
AGE
(days)
7
28
28
MAXIMUM
LOAD
(Ibs. force)
87595
114850
119195
Average
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77040
Corporate Phone: (214) 630 -9745
CONCRETE COMPRESSIVE STRENGTH TEST
Report No.:
Project No.:
Date of Service:
Report Date:
MIX DESIGN I.D.: 7752
PLACEMENT DATE: 07/15/2003
WEATHER CONDITIONS: Clear
TIME SAMPLED. 10'00an1 BATCH TIME: 9:43am
TEMPERATURE (F) AIR 84 F CONCRETE: 89 F
TRUCK NO: 1 17 TICKET NO: 117245
COMPRESSIVE
STRENGTH
(psi)
190770
037333
07/15/2003
08/13/2003
FRACTURE
TYPE
3100 Unbonded Cap
4060 Unbonded Cap
4220 Unbonded Cap
4140
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and
reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd.
01DD Page 4 of 5
RoneEngineers
A LEIGH COMPANY
Client: Duke Realty Services, LP
Attn: Mr. Jeff Langston
5495 Belt Line Road, Suite 360
Dallas TX 75254
Project: Freeport 10
500 Freeport Parkway
Coppell, TX
Services: Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
CONTRACTOR: Duke Realty Services, LP
CONCRETE SUPPLIER: Potter
PLANT: On Site
SPECIFICATION REQUIREMENTS
STRENGTH: 4000 psi 28 Days
SLUMP (in): 5" maximum
AIR 3% 6%
TEST METHOD: ASTM C -172
ASTM C -31
CYLINDER
MARKED
SET NO.
5 4
ASTM C -143
ASTM C -231
ASTM C -1064
ASTM C -138
ASTM C -39
MEASURED
SLUMP
(inches)
5 1 4.5
5 2 4.5
5 3 4.5
Technician: Lanny Gist
Report Distribution:
(1) Duke Realty Services, LP
(1) Duke Realty Services, LP
(1) City of Coppell Engineering Dept.
(1) Potter Concrete
Concrete Compressive Cylinder 6" x 12" (area 28.27 sq. in.)
DATE
TESTED
07/22/2003
08/12/2003
08/12/2003
Hold
CONCRETE COMPRESSIVE STRENGTH TEST
REPORT (W TESTS
Started: 6:30am
PROJECT DATA
(I) Pacheco Koch Consulting Engineers
(1) Engineering Analyst
(1) City of Coppell Bldg. Inspections
MIX DESIGN I.D.: 7752
PLACEMENT DATE: 07/15/2003
WEATHER CONDITIONS: Clear
TIME SAMPLED: 10:55am BATCH TIME: 10:38am
TEMPERATURE (F) AIR 88 F CONCRETE: 90 F
TRUCK NO: 115 TICKET NO: 117253
AIR CONTENT 3.2 UNIT WEIGHT (pct): NA
OVERALL PLACEMENT LOCATION:
South parking lot, south half, building column line GG to MM
SAMPLE LOCATION:
AGE
(days)
7
28
28
Finished: 3:30pm
MAXIMUM
LOAD
(lbs. force)
90385
115085
118490
Average
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77040
Corporate Phone: (214) 630-9745
Report No.:
Project No.:
Date of Service:
Report Date:
175' east, 20' north, southwest
corner
COMPRESSIVE
STRENGTH
(psi)
3200
4070
4190
4130
190770
037333
07/15/2003
08/13/2003
K. Scott Watson, AET
CMT Operations Manager
FRACTURE
TYPE
Unbonded Cap
Unbonded Cap
Unbonded Cap
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and
reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd.
01DD Page 5 of 5