Freeport NIP(7.0)-LR030808RoneEngineers
A. LEIGH COMPANY
Client: Duke Realty Services, LP
Attn: Mr. Jeff Langston
5495 Belt Line Road, Suite 360
Dallas TX 75254
Project:
Services:
CONTRACTOR: Duke Realty Services, LP
CONCRETE SUPPLIER: Potter
PLANT: On site
SPECIFICATION REQUIREMENTS
STRENGTH: 4000 psi 28 Days
SLUMP (in): 5" maximum
AIR 3% 6%
TEST METHOD: ASTM C -172
ASTM C -31
CYLINDER
MARKED
SET NO.
1 2
1 3
Freeport 10
500 Freeport Parkway
Coppell, TX
Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
ASTM C -143
ASTM C -231
ASTM C -1064
ASTM C -138
ASTM C -39
MEASURED
SLUMP DATE
(inches) TESTED
1 1 5.00 08/06/2003
5.00 08/27/2003
5.00 08/27/2003
4 5.00 09/24/2003
PROJECT DATA
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12" (area 28.27 sq. in.)
SAMPLE LOCATION: 10' west, 10' north of southeast
comer
AGE
(days)
7
28
28
56
MAXIMUM
LOAD
(lbs. force)
77500
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77040
Corporate Phone: (214) 630 -9745
CONCRETE COMPRESSIVE STRENGTH TEST
Report No.:
Project No.:
Date of Service:
Report Date:
MIX DESIGN I.D.: 7752
PLACEMENT DATE: 07/30/2003
WEATHER CONDITIONS: Partly cloudy
TIME SAMPLED: 7:O5am BATCH TIME: 6:49am
TEMPERATURE (F) AIR 83 F CONCRETE: 88 F
TRUCK NO: 105 TICKET NO: 117703
AIR CONTENT 4.3 UNIT WEIGHT (pcf): NA
OVERALL PLACEMENT LOCATION:
North half of north parking lot at northeast entrance.
COMPRESSIVE
STRENGTH
(psi)
191630
037333
07/30/2003
08/08/2003
FRACTURE
TYPE
2740 Unbonded Cap
Unbonded Cap
Unbonded Cap
Unbonded Cap
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and
reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd.
01 Page lof6
RoneEngineers
A LEIGH COMPANY
Client: Duke Realty Services, LP
Attn: Mr. Jeff Langston
5495 Belt Line Road, Suite 360
Dallas TX 75254
Project:
Services:
CONTRACTOR:
CONCRETE SUPPLIER•
PLANT:
SPECIFICATION REQUIREMENTS
STRENGTH: 4000 psi 28 Days
SLUMP (in): 5" maximum
AIR 3% 6%
TEST METHOD: ASTM C -172
ASTM C -31
ASTM C -143
ASTM C -231
ASTM C -1064
ASTM C -138
ASTM C -39
CYLINDER
MARKED
SET NO.
2 1
CONCRETE COMPRESSIVE STRENGTH TEST
Freeport 10
500 Freeport Parkway
Coppell, TX
Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Duke Realty Services, LP
Potter
On site
MEASURED
SLUMP DATE
(inches) TESTED
5.00 08/06/2003
2 2 5.00 08/27/2003
2 3 5.00 08/27/2003
2 4 5.00 09/24/2003
PROJECT DATA
REPORT OF TESTS
Report No.:
Project No.:
Date of Service:
Report Date:
MIX DESIGN I.D.: 7752
PLACEMENT DATE: 07/30/2003
WEATHER CONDITIONS: Partly cloudy
TIME SAMPLED: 8:10am BATCH TIME: 7:50am
TEMPERATURE (F) AIR 85 F CONCRETE: 88 F
TRUCK NO: 105 TICKET NO: 117715
AIR CONTENT 3.4 UNIT WEIGHT (pci): NA
OVERALL PLACEMENT LOCATION:
North half of north parking lot at northeast entrance
SAMPLE LOCATION: 10' east, 5' north of southwest
corner
Concrete Compressive Cylinder 6" x 12" (area 28.27 sq. in.)
AGE
(days)
7
28
28
56
MAXIMUM
LOAD
(Ibs. force)
84950
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77040
Corporate Phone: (214) 630 -9745
COMPRESSIVE
STRENGTH
(psi)
191630
037333
07/30/2003
08/08/2003
FRACTURE
TYPE
3000 Unbonded Cap
Unbonded Cap
Unbonded Cap
Unbonded Cap
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and
reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd.
01 Page 2 of 6
RoneEngineers
A LEIGH COMPANY
Client: Duke Realty Services, LP
Attn: Mr. Jeff Langston
5495 Belt Line Road, Suite 360
Dallas TX 75254
Project:
Services:
CONTRACTOR:
CONCRETE SUPPLIER:
PLANT:
Freeport 10
500 Freeport Parkway
Coppell, TX
Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Duke Realty Services, LP
Potter
On site
SPECIFICATION REQUIREMENTS
STRENGTH: 4000 psi 28 Days
SLUMP (in): 5" maximum
AIR 3% 6%
TEST METHOD: ASTM C -172
ASTM C -31
ASTM C -143
ASTM C -231
ASTM C -1064
ASTM C -138
ASTM C -39
CYLINDER
MARKED
SET NO.
MEASURED
SLUMP DATE
(inches) TESTED
3 1 5.00 08/06/2003
3 2 5.00 08/27/2003
3 3 5.00 08/27/2003
3 4 5.00 09/24/2003
CONCRETE COMPRESSIVE STRENGTH TEST
PROJECT DATA
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12" (area 28.27 sq. in.)
Report No.:
Project No.:
Date of Service:
Report Date:
MIX DESIGN I.D.: 7752
PLACEMENT DATE: 07/30/2003
WEATHER CONDITIONS: Partly cloudy
TIME SAMPLED: 8:55am BATCH TIME: 8:43am
TEMPERATURE (F) AIR 85 F CONCRETE: 89 F
TRUCK NO: 110 TICKET NO: 117725
AIR CONTENT 4.3 UNIT WEIGHT (pcf): NA
OVERALL PLACEMENT LOCATION:
South half of north parking lot, building column lines R to U
SAMPLE LOCATION: 15' north, 10' west of southeast
comer
AGE
(days)
7
28
28
56
MAXIMUM
LOAD
(lbs. force)
88575
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77040
Corporate Phone: (214) 630 -9745
COMPRESSIVE
STRENGTH
(psi)
191630
037333
07/30/2003
08/08/2003
FRACTURE
TYPE
3130 Unbonded Cap
Unbonded Cap
Unbonded Cap
Unbonded Cap
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and
reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd.
01 Page 3 of 6
RoneEngineers
A LEIGH COMPANY
Client: Duke Realty Services, LP
Attn: Mr. Jeff Langston
5495 Belt Line Road, Suite 360
Dallas TX 75254
Project: Freeport 10
500 Freeport Parkway
Coppell, TX
Services: Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
CONTRACTOR:
CONCRETE SUPPLIER:
PLANT:
SPECIFICATION REQUIREMENTS
STRENGTH:
SLUMP (in):
AIR
TEST METHOD:
CYLINDER
MARKED
SET NO.
4 3
Duke Realty Services, LP MIX DESIGN I.D.: 7752
Potter PLACEMENT DATE: 07/30/2003
On site
4000 psi 28 Days
5" maximum
3% 6% AIR CONTENT 4.6 UNIT WEIGHT (pct): NA
ASTM C -172
ASTM C -31
ASTM C -143
ASTM C 231
ASTM C -1064
ASTM C -138
ASTM C -39
MEASURED
SLUMP
(inches)
4 1 5.00 08/06/2003
4 2 5.00 08/27/2003
Concrete Compressive Cylinder 6" x 12" (area 28.27 sq. in.)
DATE
TESTED
5.00 08/27/2003
4 4 5.00 09/24/2003
Water added at site: 10 gallons
CONCRETE COMPRESSIVE STRENGTH TEST
PROJECT DATA
REPORT OF TESTS
WEATHER CONDITIONS: Partly cloudly
TIME SAMPLED: 9:5Oam BATCH TIME: 9:32am
TEMPERATURE (F) AIR 87 F CONCRETE: 89 F
TRUCK NO: 115 TICKET NO: 117725
OVERALL PLACEMENT LOCATION:
South half of north parking lot, building column lines R to U
SAMPLE LOCATION: 10' east, 10' north of southwest
comer
AGE
(days)
7
28
28
56
MAXIMUM
LOAD
(Ibs. force)
90905
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77040
Corporate Phone: (214) 630 -9745
Report No.:
Project No.:
Date of Service:
Report Date:
COMPRESSIVE
STRENGTH
(psi)
191630
037333
07/30/2003
08/08/2003
FRACTURE
TYPE
3210 Unbonded Cap
Unbonded Cap
Unbonded Cap
Unbonded Cap
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and
reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd.
01 Page 4 of 6
RoneEngineers
A LEIGH COMPANY
Client: Duke Realty Services, LP
Attn: Mr. Jeff Langston
5495 Belt Line Road, Suite 360
Dallas TX 75254
Project:
Services:
CONTRACTOR: Duke Realty Services, LP
CONCRETE SUPPLIER: Potter
PLANT: 011 site
SPECIFICATION REQUIREMENTS
STRENGTH:
SLUMP (in):
AIR
TEST METHOD:
CYLINDER
MARKED
SET NO.
Freeport 10
500 Freeport Parkway
Coppell, TX
Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
MEASURED
SLUMP
(inches)
5 1 4.50
5 2 4.50
5 3 4.50
5 4 4.50
4000 psi 28 Days
5" maximum
3% 6%
ASTM C -172
ASTM C -31
ASTM C -143
ASTM C -231
ASTM C -1064
ASTM C -138
ASTM C -39
DATE
TESTED
08/06/2003
08/27/2003
08/27/2003
09/24/2003
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77040
Corporate Phone: (214) 630-9745
CONCRETE COMPRESSIVE STRENGTH TEST
Report No.:
Project No.:
Date of Service:
Report Date:
191630
037333
07/30/2003
08/08/2003
PROJECT DATA
MIX DESIGN LD.: 7752
PLACEMENT DATE: 07/30/2003
WEATHER CONDITIONS: Partly cloudy
TIME SAMPLED: 10:55am BATCH TIME: 10:37am
TEMPERATURE (F) AIR 86 F CONCRETE: 90 F
TRUCK NO: 103 TICKET NO: 117746
AIR CONTENT 3.5 UNIT WEIGHT (pct): NA
OVERALL PLACEMENT LOCATION:
North half of south parking lot, building column line E to J
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12" (area 28 27 sq in.)
SAMPLE LOCATION: 20' south, 20' west of northeast
corner
28
28
56
MAXIMUM
LOAD
(Ibs. force)
86865
COMPRESSIVE
STRENGTH
(psi)
FRACTURE
TYPE
3070 Unbonded Cap
Unbonded Cap
Unbonded Cap
Unbonded Cap
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and
reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd.
01 Page 5 of 6
RoneEngineers
A LEIGH COMPANY
Client: Duke Realty Services, LP
Attn: Mr. Jeff Langston
5495 Belt Line Road, Suite 360
Dallas TX 75254
Project:
Services:
CONTRACTOR:
CONCRETE SUPPLIER:
PLANT:
SPECIFICATION REQUIREMENTS
STRENGTH:
SLUMP (in):
AIR
TEST METHOD:
CYLINDER
MARKED
SET NO.
6 1
Freeport 10
500 Freeport Parkway
Coppell, TX
Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
2
3
Technician: Lanny Gist
Report Distribution:
(1) Duke Realty Services, LP
(1) Duke Realty Services, LP
(1) City of Coppell Engineering Dept.
(1) Potter Concrete
Duke Realty Services, LP
Potter
On site
4000 psi 28 Days
5" maximum
ASTM C -172
ASTM C -31
ASTM C -143
ASTM C -231
ASTM C -1064
ASTM C -138
ASTM C -39
MEASURED
SLUMP DATE
(inches) TESTED
5.00 08/06/2003
5.00 08/27/2003
5.00 08/27/2003
6 4 5.00 09/24/2003
CONCRETE COMPRESSIVE STRENGTH TEST
Started: 7:00am
PROJECT DATA
REPORT OF TESTS
(1) Pacheco Koch Consulting Engineers
(1) Engineering Analyst
(1) City of Coppell Bldg. Inspections
OVERALL PLACEMENT LOCATION:
North half of south parking lot, building column line E to J
SAMPLE LOCATION: 10' south, 10' west of nort
corner
Concrete Compressive Cylinder 6" x 12" (area 28.27 sq. in.)
AGE
(days)
7
28
28
56
Finished: 2:30pm
MAXIMUM
LOAD
(lbs. force)
79505
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77040
Corporate Phone: (214) 630-9745
Report No.:
Project No.:
Date of Service:
Report Date:
MIX DESIGN I.D.: 7752
PLACEMENT DATE: 07/30/2003
WEATHER CONDITIONS: Partly cloudy
TIME SAMPLED: 11:4Oam BATCH TIME: 1 1:1 1 am
TEMPERATURE (F) AIR 90 P CONCRETE: 91 F
TRUCK NO: 114 TICKET NO: 117754
3% 6% AIR CONTENT 5.1 UNIT WEIGHT (pcf): N
COMPRESSIVE
STRENGTH
(psi)
2810
191630
037333
07/30/2003
08/08/2003
K. Scott Watson, AET
CMT Operations Manager
FRACTURE
TYPE
Unbonded Cap
Unbonded Cap
Unbonded Cap
Unbonded Cap
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and
reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd.
01 Page 6 of 6
Items Inspected:
Conforming
Non
Conforming
Items Inspected:
Conforming
Non
Conforming
Items Inspected:
Conforming
Non
Conforming
Placing Drawings
Approved
Bar Length
and Shape
L/
Column Ties Properly
Tied and Spaced
Bar Size
1.■
Proper Bar Placement
[,r
Stirrup Spacing and Type
Bar Grade
Properly Tied
L/
Lapped Splices
t•
Bars Clean
•a
Dowel Bars in Place
Welded Splices
----s
Form Clean
1/'
Proper Bar Supports
r/
Mechanical Splices
Number Bars
Proper Cover
1-
RoneEngineers
A LEIGH COMPANY
Client: Da li
Project: Fr repo t /0
Inspector's Signature:
2. 6,St
8908 Ambassador Row
Dallas, Texas 75247
(214) 630 -9745
Report of
Reinforcing Steel Inspection
Report No.: M‘03-`7
Project No.: 0 313 3 3
Date of Service: 7-30.- 3
Page of 'L
Locations and Items Inspected: Al r9' /1f' o f n/v r p vik e., /at- 4 f 1•1 a e f r 7 n i e,
S hfr/'I L 6 V Ji y` P'I/kir, /nt B i4 /O.r'i. G,',FS P 400 v A/e
NG/ e ff Soh 04 ?4% k r of S 1344 n /Ines L '/0 r
Discrepancies Comments: 51 ,ter »,/r c-c e l ie re d. pcncoi t a l..
(A4; 5 gdaled U r 1 eon ere le De2
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility fur variation in quality (composition
appearance. performance. etc.)or any other feature of similar subject matter provided by persons or conditions aver which we have no control. Our letters and reports are for the exclusive
use of the clients to whom they are addressed and shall not be reproduced except in full without the xritten approval of Pone Engineers, Inc.
121 North Rayner
Fort Worth, Texas 76111
(817) 831 -6211
Time: eitlaim to 71criit-
Client/Contractor Signature: Client/Contractor Copied with Results: Yes No