Freeport NIP(7.0)-LR030825RoneEngineers
to
A LEIGH COMPANY
Client: Duke Realty Services, LP
Attn: Mr. Jeff Langston
5495 Belt Line Road, Suite 360
Dallas TX 75254
Project:
Services:
CONTRACTOR:
CONCRETE SUPPLIER:
PLANT:
SPECIFICATION REQUIREMENTS
STRENGTH:
SLUMP (in):
AIR
TEST METHOD:
CYLINDER
MARKED
SET NO.
1
1
1
1
2
3
Freeport 10
500 Freeport Parkway
Coppell, TX
Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Duke Realty Services, LP
Potter
On site
4000 psi 28 Days
5" maximum
3 -6%
ASTM C -172
ASTM C -31
ASTM C -143
ASTM C -231
ASTM C -1064
ASTM C -138
ASTM C -39
MEASURED
SLUMP DATE
(inches) TESTED
5.0 08/01/2003
5.0 08/22/2003
5.0 08/22/2003
1 4 Hold
CONCRETE COMPRESSIVE STRENGTH TEST
PROJECT DATA
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12" (area 28.27 sq. in.)
Report No.:
Project No.:
Date of Service:
Report Date:
MIX DESIGN I.D.: 7752
PLACEMENT DATE: 07/25/2003
WEATHER CONDITIONS: Clear
TIME SAMPLED. 7:30am BATCH TIME: 7:14am
TEMPERATURE (F) AIR 80 F CONCRETE: 86 F
TRUCK NO: 105 TICKET NO: 117583
AIR CONTENT 3.9 UNIT WEIGHT (pcf): NA
OVERALL PLACEMENT LOCATION:
South half of north parking lot, Building Column Lines KK to LL
SAMPLE LOCATION: 20' south, 10' west of northeast
corner
AGE
(days)
7
28
28
MAXIMUM
LOAD
(lbs. force)
87350
118030
116295
Average
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77040
Corporate Phone: (214) 630 -9745
COMPRESSIVE
STRENGTH
(Psi)
3090
4170
4110
4140
191402
037333
07/25/2003
08/25/2003
FRACTURE
TYPE
Unbonded Cap
Unbonded Cap
Unbonded Cap
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and
reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd.
O1DD Page 1 of 7
RoneEngineers
A LEIGH COMPANY
Client: Duke Realty Services, LP
Attn: Mr. Jeff Langston
5495 Belt Line Road, Suite 360
Dallas TX 75254
Project:
Services:
CONTRACTOR:
CONCRETE SUPPLIER:
PLANT:
SPECIFICATION REQU
STRENGTH:
SLUMP (in):
AIR
TEST METHOD:
CYLINDER
MARKED
SET NO.
2 1
Freeport 10
500 Freeport Parkway
Coppell, TX
Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Duke Realty Services, LP
Potter
On site
IREMENTS
4000 psi 28 Days
5" maximum
3 -6%
ASTM C -172
ASTM C -31
ASTM C -143
ASTM C -231
ASTM C -1064
ASTM C -138
ASTM C -39
MEASURED
SLUMP
(inches)
2 2 5.0 08/22/2003
2 3 5.0 08/22/2003
2 4 5.0 09/19/2003
CONCRETE COMPRESSIVE STRENGTH TEST
PROJECT DATA
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12" (area 28.27 sq. in.)
DATE
TESTED
5.0 08/01/2003
Does not comply with specified strength.
Water added at site: 5 gallons
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77040
Corporate Phone: (214) 630 -9745
Report No.:
Project No.:
Date of Service:
Report Date:
191402
037333
07/25/2003
08/25/2003
MIX DESIGN I.D.: 7752
PLACEMENT DATE: 07/25/2003
WEATHER CONDITIONS• Clear
TIME SAMPLED: 8:20am BATCH TIME: 8:01am
TEMPERATURE (F) AIR 82 F CONCRETE: 84 F
TRUCK NO: 1 TICKET NO: 117592
AIR CONTENT 4.0
OVERALL PLACEMENT LOCATION:
North half of south parking lot between Building Column Lines Y to GG
SAMPLE LOCATION: 20' east, 15' south of northwest
comer
AGE
(days)
7
28
28
56
MAXIMUM
LOAD
(lbs. force)
86500
109125
107600
Average
UNIT WEIGHT (pcf): NA
COMPRESSIVE
STRENGTH
(psi)
3060
3860
3810
3840
FRACTURE
TYPE
Unbonded Cap
Unbonded Cap
Unbonded Cap
Unbonded Cap
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and
reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd.
OIDD Page 2 of 7
RoneEngineers
to
A LEIGH COMPANY
Client: Duke Realty Services, LP
Attn: Mr. Jeff Langston
5495 Belt Line Road, Suite 360
Dallas TX 75254
Project: Freeport 10
500 Freeport Parkway
Coppell, TX
Services: Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
CONTRACTOR: Duke Realty Services, LP
CONCRETE SUPPLIER: Potter
PLANT: On site
SPECIFICATION REQUIREMENTS
STRENGTH:
SLUMP (in):
MR
TEST METHOD:
CYLINDER
MARKED
SET NO.
3
3
3
3
1
2
3
4
4000 psi 28 Days
5" maximum
3 -6%
ASTM C -172
ASTM C -31
ASTM C -143
ASTM C -231
ASTM C -1064
ASTM C -138
ASTM C -39
MEASURED
SLUMP DATE
(inches) TESTED
5.0 08/01/2003
5.0 08/22/2003
5.0 08/22/2003
5.0 09/19/2003
CONCRETE COMPRESSIVE STRENGTH TEST
PROJECT DATA
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12" (area 28.27 sq. in.)
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77040
Corporate Phone: (214) 630-9745
Report No.:
Project No.:
Date of Service:
Report Date:
191402
037333
07/25/2003
08/25/2003
MIX DESIGN I.D.: 7752
PLACEMENT DATE: 07/25/2003
WEATHER CONDITIONS: Clear
TIME SAMPLED: 9: loam BATCH TIME: 8:49am
TEMPERATURE (F) MR 84 F CONCRETE: 86 F
TRUCK NO: 101 TICKET NO: 117599
AIR CONTENT 3.2 UNIT WEIGHT (pet): NA
OVERALL PLACEMENT LOCATION:
North half of south parking lot between Building Column Lines Y to GG
SAMPLE LOCATION: 10' north, 10' east of southwe
corner
AGE
(days)
7
28
28
56
MAXIMUM
LOAD
(lbs. force)
83940
108995
102220
Average
Does not comply with specified strength.
/I
COMPRESSIVE
STRENGTH
(psi)
2970 Unbonded Cap
3850
3610
3730
7
FRACTURE
TYPE
Unbonded Cap
Unbonded Cap
Unbonded Cap
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and
reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd.
O1DD Page 3 of 7
RoneEngineers
A LEIGH COMPANY
Client: Duke Realty Services, LP
Attn: Mr. Jeff Langston
5495 Belt Line Road, Suite 360
Dallas TX 75254
Project:
Services:
CONTRACTOR:
CONCRETE SUPPLIER.
PLANT:
SPECIFICATION REQU
STRENGTH:
SLUMP (in):
AIR (%n):
TEST METHOD:
CYLINDER
MARKED
SET NO.
4 1
4
4
2
3
Freeport 10
500 Freeport Parkway
Coppell, TX
Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Duke Realty Services, LP
Potter
On site
MENTS
4000 psi 28 Days
5" max
6%
STM C -172
ASTM C -31
ASTM C -143
ASTM C -231
ASTM C -1064
ASTM C -138
ASTM C -39
MEASURED
SLUMP
(inches)
4.5
4.5
4.5
Concrete Compressive Cylinder 6" x 12" (area 28.27 sq. in.)
DATE
TESTED
08/01/2003
08/22/2003
08/22/2003
4 4 Hold
CONCRETE COMPRESSIVE STRENGTH TEST
PROJECT DATA
REPORT OF TESTS
AGE
(days)
7
28
28
MAXIMUM
LOAD
(Ibs. force)
96136
119135
119085
Average
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77040
Corporate Phone: (214) 630 -9745
Report No.:
Project No.:
Date of Service:
Report Date:
SAMPLE LOCATION: 100' east, 20' south of northwest
comer
COMPRESSIVE
STRENGTH
(Psi)
3400
4210
4210
4210
191402
037333
07/25/2003
08/25/2003
MIX DESIGN LD.: 7752
PLACEMENT DATE: 07/25/2003
WEATHER CONDITIONS: Clear
TIME SAMPLED: 10:O5am BATCH TIME: 9:45am
TEMPERATURE (F) AIR 85 F CONCRETE: 88 F
TRUCK NO: 104 TICKET NO: 117610
AIR CONTENT 3.5 UNIT WEIGHT (pct): NA
OVERALL PLACEMENT LOCATION:
North half of south parking lot between Building Column Lines Y to GG
FRACTURE
TYPE
Unbonded Cap
Unbonded Cap
Unbonded Cap
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and
reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd.
01DD Page 4 of 7
RoneEngineers
w
A LEIGH COMPANY
Client: Duke Realty Services, LP
Attn: Mr. Jeff Langston
5495 Belt Line Road, Suite 360
Dallas TX 75254
Project:
Services:
Freeport 10
500 Freeport Parkway
Coppell, TX
Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
CONTRACTOR: Duke Realty Services, LP
CONCRETE SUPPLIER: Potter
PLANT: On site
SPECIFICATION REQUIREMENTS
STRENGTH:
SLUMP (in):
AIR
TEST METHOD:
CYLINDER
MARKED
SET NO.
5 4
4000 psi 28 Days
5" maximum
3 -6%
ASTM C -172
ASTM C -31
ASTM C -143
ASTM C -231
ASTM C -1064
ASTM C -138
ASTM C -39
MEASURED
SLUMP
(inches)
DATE
TESTED
5 1 5.0 08/01/2003
5 2 5.0 08/22/2003
5 3 5.0 08/22/2003
Hold
CONCRETE COMPRESSIVE STRENGTH TEST
PROJECT DATA
MIX DESIGN I.D.: 7752
PLACEMENT DATE: 07/25/2003
WEATHER CONDITIONS: Clear
TIME SAMPLED: 11:OOam
TEMPERATURE (F) AIR
TRUCK NO: 115
AIR CONTENT 3.5
SAMPLE LOCATION:
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12" (area 28.27 sq. in.)
AGE
(days)
7
28
28
MAXIMUM
LOAD
(ibs. force)
96185
115760
111955
Average
Does not comply with specified strength.
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77040
Corporate Phone: (214) 630-9745
Report No.:
Project No.:
Date of Service:
Report Date:
191402
037333
07/25/2003
08/25/2003
BATCH TIME: 10:41 am
86 F CONCRETE: 89 F
TICKET NO: 117620
UNIT WEIGHT (pcf): NA
OVERALL PLACEMENT LOCATION:
North half of south parking lot between Building Column Lines Y to 00
150' east, 10' north of southwest
comer
COMPRESSIVE
STRENGTH
(Psi)
3400
4090
3960
4030
FRACTURE
TYPE
Unbonded Cap
Unbonded Cap
Unbonded Cap
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and
reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd.
01DD Page of
RoneEngineers
A LEIGH COMPANY
Client: Duke Realty Services, LP
Attn: Mr. Jeff Langston
5495 Belt Line Road, Suite 360
Dallas TX 75254
Project:
Services:
CONTRACTOR:
CONCRETE SUPPLIER:
PLANT:
SPECIFICATION REQUIREMENTS
STRENGTH: 4000 psi 28 Days
SLUMP (in): 5" maximum
AIR 3% 6%
TEST METHOD: ASTM C -172
ASTM C -31
ASTM C -143
ASTM C -231
ASTM C -1064
ASTM C -138
ASTM C -39
CYLINDER
MARKED
SET NO.
Duke Realty Services, LP
Potter
On site
MEASURED
SLUMP
(inches)
DATE
TESTED
6 1 4.5 08/01/2003
6 2 4.5 08/22/2003
6 3 4.5 08/22/2003
6 4 Hold
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77040
Corporate Phone: (214) 630 -9745
CONCRETE COMPRESSIVE STRENGTH TEST
Concrete Compressive Cylinder 6" x 12" (area 28.27 sq. in.)
Report No.:
Project No.:
Date of Service:
Report Date:
Freeport 10
500 Freeport Parkway
Coppell, TX
Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
PROJECT DATA
REPORT OF TESTS
191402
037333
07/25/2003
08/25/2003
MIX DESIGN I.D.: 7752
PLACEMENT DATE: 07/25/2003
WEATHER CONDITIONS: Clear
TIME SAMPLED: 12: 10p111 BATCH TIME. 11
TEMPERATURE (F) AIR 88 F CONCRETE: 90 F
TRUCK NO: 101 TICKET NO: 117633
AIR CONTENT 3.1 UNIT WEIGHT (pcf): NA
OVERALL PLACEMENT LOCATION:
North half of south parking lot between Building Column Lines Y to GG
SAMPLE LOCATION: 200' east, 10' south of northwest
corner
AGE
(days)
7
28
28
MAXIMUM
LOAD
(Ibs. force)
94040
116280
115900
Average
COMPRESSIVE
STRENGTH
(Psi)
3330
4110
4100
4110
FRACTURE
TYPE
Unbonded Cap
Unbonded Cap
Unbonded Cap
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and
reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd.
OIDD Page6of7
RoneEngineers
A LEIGH COMPANY
Client: Duke Realty Services, LP
Attn: Mr. Jeff Langston
5495 Belt Line Road, Suite 360
Dallas TX 75254
Project: Freeport 10
500 Freeport Parkway
Coppell, TX
Services: Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
CONTRACTOR: Duke Realty Services, LP
CONCRETE SUPPLIER: Potter
PLANT: On site
SPECIFICATION REQUIREMENTS
STRENGTH:
SLUMP (in):
AIR
TEST METHOD:
CYLINDER
MARKED
SET NO.
MEASURED
SLUMP
(inches)
7 1 5.0
7 2 5.0
7 3 5.0
7 4 5.0
Technician: Lanny Gist
Report Distribution:
(1) Duke Realty Services, LP
(1) Duke Realty Services, LP
(1) City of Coppell Engineering Dept.
(1) Potter Concrete
4000 psi 28 Days
5" maximum
3 -6%
ASTM C -172
ASTM C -31
ASTM C -143
ASTM C -231
ASTM C -1064
ASTM C -138
ASTM C -39
DATE
TESTED
08/01/2003
08/22/2003
08/22/2003
CONCRETE COMPRESSIVE STRENGTH TEST
Started: 7:OOam
PROJECT DATA
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12" (area 28 27 sq in
AGE
(days)
7
28
28
Does not comply with specified strength.
(1) Pacheco Koch Consulting Engineers
(1) Engineering Analyst
(1) City of Coppell Bldg. Inspections
Finished: 2:30pm
MAXIMUM
LOAD
(lbs. force)
86245
107520
105785
Average
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77040
Corporate Phone: (214) 630 -9745
Report No.:
Project No.:
Date of Service:
Report Date:
SAMPLE LOCATION: 225' east, 10' north of southwest
corner
COMPRESSIVE
STRENGTH
(Psi)
3050
3800
3740
3770
191402
037333
07/25/2003
08/25/2003
MIX DESIGN I.D.: 7752
PLACEMENT DATE: 07/25/2003
WEATHER CONDITIONS: Clear
TIME SAMPLED: 1:10pm BATCH TIME: 12:Slpm
TEMPERATURE (F) AIR 90 F CONCRETE: 92 F
TRUCK NO: 105 TICKET NO: 117641
AIR CONTENT 4.0 UNIT WEIGHT (pcf): NA
OVERALL PLACEMENT LOCATION:
North half of south parking lot between Building Column Lines Y to GO
K. Scott Watson, AET
CMT Operations Manager
FRACTURE
TYPE
Unbonded Cap
Unbonded Cap
Unbonded Cap
09/19/2003 56 Unbonded Cap
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and
reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rorie Engineers, Ltd.
OIDD Page 7 of 7
RoneEngineers
A LEIGH COMPANY
Client: Duke Realty Services, LP
Attn: Mr. Jeff Langston
5495 Belt Line Road, Suite 360
Dallas TX 75254
Project:
Services:
Freeport 10
500 Freeport Parkway
Coppell, TX
Reinforcing Steel Inspection
On this date, a Rone Engineers, Ltd. representative(s) arrived on site as
scheduled to perform Reinforcing Steel Inspection. The results are attached.
Technician Time: 8:30am 11:30am
Page 1 of 3
Technician: Lanny Gist
Report Distribution:
(1) Duke Realty Services, LP
(I) Duke Realty Services, LP
(1) City of Coppell Engineering Dept.
(1) Pacheco Koch Consulting Engineers
REPORT OF REINFORCING STEEL INSPECTION
Report of Inspection
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77040
Corporate Phone: (214) 630 -9745
Report No.:
Project No.:
Date of Service:
Report Date:
192851
037333
08/20/2003
08/25/2003
(1) Engineering Analyst
(I) City of Coppell Bldg. Inspections K. Scott Watson, AET
CMT Operations Manager
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and
reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd.
99DD Paee 1 of 1
Items Inspected:
Conforming
Non
Conforming
Items Inspected:
Conforming
Non
Conforming
Items Inspected:
Conforming
Non
Conforming
Placing Drawings
Approved
1,--^
Bar Length
and Shape
l+'
Column Ties Properly
Tied and Spaced
Bar Size
Proper Bar Placement
1/
Stirmp Spacing and Type
Bar Grade
[/a
Properly Tied
[i-
Lapped Splices
L/
Bars Clean
Dowel Bars in Place
Welded Splices
Form Clean
Proper Bar Supports
Mechanical Splices
Bars
Proper Cover
1i
RoneEngineers
A LEIGH COMPANY
Client: vre
Project: F e epor/ jig
8908 Ambassador Row
Dallas, Texas 75247
(214) 630 -9745
Report of
Reinforcing Steel Inspection
Report No.: f q S
Project No.: 03 7 3 3 3
Date of Service: e-cAp -v
Page of 3-
Discrepancies Comments: 5- rota 6 e< pi, or' 7 to Cf P
lOre Pprl Fars/1 C A4i /5 M Yd ad/42% f v i, r7 /)&r
LIMITATIONS: The tem results presented herein were prepared based upon the speailic vm pies provided for testing, We assume no responsibility for variation in quality (composition
appearance, performance. etc) or any other feature orsimil ,subject matter provided by panona or conditions over which we have no control. Our letters and reports are for the esclmive
use of the clients m whom they are addressed and shall no be reproduced except in full without the written approval of none Engineers, Inc,
121 North Rayner
Fort Worth, Texas 76111
(817) 831 -6211
Locations and Items Inspected: ecbt Lgne q nomi nl,E u nd 5
415
Inspector's Signature: L 4; 5 Time: to
Client/Contractor Signature: Client/Contractor Copied with Results: Yes No
Items Inspected:
Conforming
Non
Conforming
Items Inspected:
Conforming
Non
Conforming
Items Inspected:
Conforming
Non
Conforming
Placing Dmwings
Approved
Bar Length
and Shape
p
Column Ties Properly
Tied and Spaced
.---•-t
Bar Size
L.
Proper Bar Placement
L/•
Stirrup Spacing and Type
Bar Grade
Properly Tied
Lapped Splices
L---
Bars Clean
t-
Dowel Bars in Place
Z`•
Welded Splices
-._e
Form Clean
Proper Bar Supports
Mechanical Splices
Number Bars
4.-
Proper Cover
RoneEngineers
A LEIGH COMPANY
Client: Duke
Project: rreepo1 iU
Locations and Items Inspected: 8Z-A9 leetre O cri
r f�
Discrepancies Comments: C f, '7 0 c'daieol t r,
Inspector's Signature: 2- 6 ;5/
8908 Ambassador Row
Dallas, Texas 75247
(214) 630 -9745
Time: oo to fl
LIMITATIONS'. The test results presented herein were prepared hued epee the specific samples provided fortesting. We assume no responsibility f variation in quality (composition
appearance, performance, etc.) or any other feature of similar subject matter provided by persons &conditions over which ae have no rental. Our letters and reports are for the exclusive
use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Race Engineers, Inc.
121 North Rayner
Fort Worth, Texas 76111
(817) 831 -6211
Report of
Reinforcing Steel Inspection
Report No.: l rj ZSS
Project No.: 0 3 3 9 3
Date of Service: 8 do- a
Page 3 of
0 0"/ erriA p
Client/Contractor Signature: Client/Contractor Copied with Results: Yes No