Freeport NIP(7.0)-LR030829RoneEngineers A LEIGH COMPANY Client: Duke Realty Services, LP Attn: Mr. Jeff Langston 5495 Belt Line Road, Suite 360 Dallas TX 75254 Project: Freeport 10 500 Freeport Parkway Coppell, TX Services: Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. CONTRACTOR: Duke Realty Services, LP CONCRETE SUPPLIER: Potter PLANT: On site SPECIFICATION REQUIREMENTS STRENGTH: 4000 psi 28 Days SLUMP(in): 5" maximum AIR 3% 6% TEST METHOD: ASTM C -172 CYLINDER MARKED SET NO. 1 1 ASTM C -31 ASTM C -143 ASTM C -231 ASTM C -1064 ASTM C -138 ASTM C -39 MEASURED SLUMP (inches) 1 1 5.0 2 5.0 3 5.0 4 5.0 Concrete Compressive Cylinder 6" x 12" (area 28.27 sq. in.) DATE TESTED 08/28/2003 09/18/2003 09/18/2003 10/16/2003 PROJECT DATA REPORT OF TESTS SAMPLE LOCATION: Southeast parking area, 20' east, 20' south of northwest comer AGE (days) 7 28 28 56 MAXIMUM LOAD (lbs. force) 74650 8908 Ambassador Row, Dallas, TX 75247 2696 Gravel Drive, Fort Worth, TX 76118 6300 Rothway, Ste. 150, Houston, TX 77040 Corporate Phone: (214) 630 -9745 CONCRETE COMPRESSIVE STRENGTH TEST Report No.: Project No.: Date of Service: Report Date: MIX DESIGN LD.: 7752 PLACEMENT DATE: 08/21/2003 WEATHER CONDITIONS: Clear TIME SAMPLED: 7:35am BATCH TIME: 7:15am TEMPERATURE (F) AIR 8 1 F CONCRETE: 86 F TRUCK NO: 107 TICKET NO: 11 AIR CONTENT 4.7 UNIT WEIGHT (pcf): NA OVERALL PLACEMENT LOCATION: South half of east fire lane and parking area, southeast comer of building COMPRESSIVE STRENGTH (psi) 192917 037333 08/21/2003 08/29/2003 FRACTURE TYPE 2640 Unbonded Cap Unbonded Cap Unbonded Cap Unbonded Cap LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd. 01DD Page 1 of 5 RoneEngineers A LEIGH COMPANY Client: Duke Realty Services, LP Attn: Mr. Jeff Langston 5495 Belt Line Road, Suite 360 Dallas TX 75254 Project: Services: CONTRACTOR: CONCRETE SUPPLIER: PLANT: Freeport 10 500 Freeport Parkway Coppell, TX Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. SPECIFICATION REQUIREMENTS Duke Realty Services, LP Potter On site STRENGTH: 4000 psi 28 Days SLUMP (in): 5" maximum AIR TEST METHOD: ASTM C -172 ASTM C -31 ASTM C -143 ASTM C -231 ASTM C -1064 ASTM C -138 ASTM C -39 CYLINDER MARKED SET NO. 2 1 4.5 3% 6% AIR CONTENT 5.2 UNIT WEIGHT (pct): NA MEASURED SLUMP (inches) Concrete Compressive Cylinder 6" x 12" (area 28.27 sq. in.) DATE TESTED 08/28/2003 2 2 4.5 09/18/2003 2 3 4.5 09/18/2003 2 4 4.5 10/16/2003 PROJECT DATA REPORT OF TESTS SAMPLE LOCATION: East fire lane, 20' south of north header AGE (days) 7 28 28 56 MAXIMUM LOAD (lbs. force) 93170 8908 Ambassador Row, Dallas, TX 75247 2696 Gravel Drive, Fort Worth, TX 76118 6300 Rothway, Ste. 150, Houston, TX 77040 Corporate Phone: (214) 630 -9745 CONCRETE COMPRESSIVE STRENGTH TEST Report No.: Project No.: Date of Service: Report Date: OVERALL PLACEMENT LOCATION: South half of east fire lane and parking area, southeast comer of building MIX DESIGN 1.D.: 7752 PLACEMENT DATE: 08/21/2003 WEATHER CONDITIONS: Clear TIME SAMPLED: 9'OOam BATCH TIME: 8:34am TEMPERATURE (F) AIR 82 F CONCRETE: 88 F TRUCK NO: 107 TICKET NO: 19 COMPRESSIVE STRENGTH (Psi) 192917 037333 08/21/2003 08/29/2003 FRACTURE TYPE 3290 Unbonded Cap Unbonded Cap Unbonded Cap Unbonded Cap LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd. 01DD Page 2 of 5 RoneEngineers A LEIGH COMPANY Client: Duke Realty Services, LP Attn: Mr. Jeff Langston 5495 Belt Line Road, Suite 360 Dallas TX 75254 Project: Freeport 10 500 Freeport Parkway Coppell, TX Services: Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. CONTRACTOR: Duke Realty Services, LP CONCRETE SUPPLIER: Potter PLANT: On site SPECIFICATION REQUIREMENTS STRENGTH: SLUMP (in): AIR TEST METHOD: CYLINDER MARKED SET NO. 3 1 3 2 3 3 4000 psi 28 Days 5" maximum 3% 6% ASTM C -172 ASTM C -31 ASTM C -143 ASTM C -231 ASTM C -1064 ASTM C -138 ASTM C -39 MEASURED SLUMP (inches) DATE TESTED 4.0 08/28/2003 4.0 09/18/2003 4.0 09/18/2003 3 4 4.0 10/16/2003 Water added at site: 10 gallons CONCRETE COMPRESSIVE STRENGTH TEST PROJECT DATA REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" (area 28.27 sq. in.) AGE (days) 7 28 28 56 MAXIMUM LOAD (Ibs. force) 98490 8908 Ambassador Row, Dallas, TX 75247 2696 Gravel Drive, Fort Worth, TX 76118 6300 Rothway, Ste. 150, Houston, TX 77040 Corporate Phone: (214) 630 -9745 Report No.: Project No.: Date of Service: Report Date: 192917 037333 08/21/2003 08/29/2003 MIX DESIGN I.D.: 7752 PLACEMENT DATE: 08/21/2003 WEATHER CONDITIONS: Clear TIME SAMPLED: 10:SOam BATCH TIME: 10:25am TEMPERATURE (F) AIR 85 F CONCRETE: 89 F TRUCK NO: 113 TICKET NO: 30 AIR CONTENT 4.9 UNIT WEIGHT (pcf): NA OVERALL PLACEMENT LOCATION: South half of east fire lane and parking area, southeast corner of building SAMPLE LOCATION: East fire lane, 200' south of north header COMPRESSIVE STRENGTH (Psi) FRACTURE TYPE 3480 Unbonded Cap Unbonded Cap Unbonded Cap Unbonded Cap LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd. 01DD Page 3 of 5 RoneEngineers A LEIGH COMPANY Client: Duke Realty Services, LP Attn: Mr. Jeff Langston 5495 Belt Line Road, Suite 360 Dallas TX 75254 Project: Services: Freeport 10 500 Freeport Parkway Coppell, TX Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. CONTRACTOR: Duke Realty Services, LP CONCRETE SUPPLIER: Potter PLANT: On site SPECIFICATION REQUIREMENTS STRENGTH: SLUMP (in): AIR TEST METHOD: CYLINDER MARKED SET NO. 4 2 4 3 4000 psi 28 Days 5" maximum 3 -6% ASTM C -172 ASTM C -31 ASTM C -143 ASTM C -231 ASTM C -1064 ASTM C -138 ASTM C -39 MEASURED SLUMP (inches) DATE TESTED 4 1 4.5 08/28/2003 4.5 09/18/2003 4.5 09/18/2003 4 4 4.5 10/16/2003 Water added at site: 10 gallons CONCRETE COMPRESSIVE STRENGTH TEST PROTECT DATA REPORT OF TESTS Report No.: Project No.: Date of Service: Report Date: MIX DESIGN I.D.: 7752 PLACEMENT DATE: 08/21/2003 WEATHER CONDITIONS: Clear TIME SAMPLED: 12:OOpm BATCH TIME: 11:26am TEMPERATURE (F) AIR 90 F CONCRETE: 90 F TRUCK NO: 1 14 TICKET NO: 38 AIR CONTENT 5.1 UNIT WEIGHT (pcf): NA OVERALL PLACEMENT LOCATION: South half of east fire lane and parking area, southeast corner of building SAMPLE LOCATION: East fire lane, 300' south of north header Concrete Compressive Cylinder 6" x 12" (area 28.27 sq. in.) AGE (days) 7 28 28 56 MAXIMUM LOAD (lbs. force) 94370 8908 Ambassador Row, Dallas, TX 75247 2696 Gravel Drive, Fort Worth, TX 76118 6300 Rothway, Ste. 150, Houston, TX 77040 Corporate Phone: (214) 630 -9745 COMPRESSIVE STRENGTH (Psi) 192917 037333 08/21/2003 08/29/2003 FRACTURE TYPE 3340 Unbonded Cap Unbonded Cap Unbonded Cap Unbonded Cap LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd. 01DD Page 4 of 5 RoneEngineers ts A LEIGH COMPANY Client: Duke Realty Services, LP Attn: Mr. Jeff Langston 5495 Belt Line Road, Suite 360 Dallas TX 75254 Project: Services: CONTRACTOR: CONCRETE SUPPLIER: PLANT: SPECIFICATION REQUIREMENTS STRENGTH: SLUMP (in): AIR TEST METHOD: CYLINDER MARKED SET NO. MEASURED SLUMP (inches) 5 1 4.25 5 2 4.25 5 3 4.25 5 4 4.25 Technician: Lanny Gist Report Distribution: (1) Duke Realty Services, LP (1) Duke Realty Services, LP (1) City of Coppell Engineering Dept. (I) Potter Concrete Duke Realty Services, LP Potter On site 4000 psi 28 Days 5" maximum 3 -6% ASTM C -172 ASTM C -31 ASTM C -143 ASTM C -231 ASTM C -1064 ASTM C -138 ASTM C -39 DATE TESTED 08/28/2003 09/18/2003 09/18/2003 10/16/2003 8908 Ambassador Row, Dallas, TX 75247 2696 Gravel Drive, Fort Worth, TX 76118 6300 Rothway, Ste. 150, Houston, TX 77040 Corporate Phone: (214) 630 -9745 CONCRETE COMPRESSIVE STRENGTH TEST PROJECT DATA REPORT OF TESTS OVERALL PLACEMENT LOCATION: East fire lane Concrete Compressive Cylinder 6" x 12" (area 28.27 sq AGE (days) 7 28 28 56 Started: 6:30am Finished: 4:OOpm (1) Pacheco Koch Consulting Engineers (1) Engineering Analyst (1) City of Coppell Bldg. Inspections in.) MAXIMUM LOAD (lbs. force) 129525 Report No.: Project No.: Date of Service: Report Date: Freeport 10 500 Freeport Parkway Coppell, TX Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. MIX DESIGN I.D.: 7752 PLACEMENT DATE: 08/21/2003 WEATHER CONDITIONS: Clear TIME SAMPLED. 2' 30pm BATCH TIME: NA TEMPERATURE (F) AIR 99 F CONCRETE: 101 F TRUCK NO: NA TICKET NO: NA AIR CONTENT 4.2 UNIT WEIGHT (pet): NA SAMPLE LOCATION: 25' north of north header COMPRESSIVE STRENGTH (Psi) 4580 192917 037333 08/21/2003 08/29/2003 K. Scott r atson, AET CMT Operations Manager FRACTURE TYPE Unbonded Cap Unbonded Cap Unbonded Cap Unbonded Cap LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd. OIDD Page 5 of 5