Freeport NIP(7.0)-LR030828RoneEngineers
A LEIGH COMPANY
Client: Duke Realty Services, LP
Attn: Mr. Jeff Langston
5495 Belt Line Road, Suite 360
Dallas TX 75254
Project:
Services:
CONTRACTOR:
CONCRETE SUPPLIER:
PLANT:
SPECIFICATION REQUIREMENTS
STRENGTH:
SLUMP (in):
AIR
TEST METHOD:
CYLINDER
MARKED
SET NO.
1 1
1 2
1 3
1 4
CONCRETE COMPRESSIVE STRENGTH TEST
Freeport 10
500 Freeport Parkway
Coppell, TX
Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Duke Realty Services, LP
Potter
On site
4000 psi 28 Days
5" maximum
3% 6%
ASTM C -172
ASTM C -31
ASTM C -143
ASTM C -231
ASTM C -1064
ASTM C -138
ASTM C -39
PROJECT DATA
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12" (area 28.27 sq. in.)
MEASURED
SLUMP DATE
(inches) TESTED
5.00 08/06/2003
5.00 08/27/2003
5.00 08/27/2003
5.00
AGE
(days)
7
28
28
MAXIMUM
LOAD
(lbs. force)
77500
102425
100365
Average
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77040
Corporate Phone: (214) 630 -9745
Report No.:
Project No.:
Date of Service:
Report Date:
MIX DESIGN I.D.: 7752
PLACEMENT DATE: 07/30/2003
WEATHER CONDITIONS: Partly cloudy
TIME SAMPLED: 7:O5am BATCH TIME: 6:49am
TEMPERATURE (F) AIR 83 F CONCRETE: 88 F
TRUCK NO: 105 TICKET NO: 117703
AIR CONTENT 4.3 UNIT WEIGHT (pct): NA
OVERALL PLACEMENT LOCATION:
North half of north parking lot at northeast entrance.
SAMPLE LOCATION: 10' west, 10' north of southeast
corner
COMPRESSIVE
STRENGTH
(psi)
2740
3620
3550
3590
191630
037333
07/30/2003
08/28/2003
FRACTURE
TYPE
Unbonded Cap
Unbonded Cap
Unbonded Cap
09/24/2003 56 Unbonded Cap
Does not comply with specified strength.
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and
reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd.
01 Page 1 of 6
RoneEngineers
A LEIGH COMPANY
Client: Duke Realty Services, LP
Attn: Mr. Jeff Langston
5495 Belt Line Road, Suite 360
Dallas TX 75254
Project:
Services:
CONTRACTOR: Duke Realty Services, LP
CONCRETE SUPPLIER: Potter
PLANT: On site
SPECIFICATION REQUIREMENTS
STRENGTH: 4000 psi 28 Days
SLUMP (in): 5" maximum
AIR (°/0): 3% 6%
TEST METHOD: ASTM C -172
ASTM C -31
CYLINDER
MARKED
SET NO.
2 1
2 2
2 3
2 4
ASTM C -143
ASTM C -231
ASTM C -1064
ASTM C -138
ASTM C -39
MEASURED
SLUMP
(inches)
5.00
5.00
5.00
5.00
SAMPLE LOCATION:
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12" (area 28.27 sq. in.)
DATE
TESTED
08/06/2003
08/27/2003
08/27/2003
AGE
(days)
7
28
28
MAXIMUM
LOAD
(lbs. force)
84950
104715
108245
Average
Does not comply with specified strength.
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77040
Corporate Phone: (214) 630 -9745
CONCRETE COMPRESSIVE STRENGTH TEST
Report No.:
Project No.:
Date of Service:
Report Date:
Freeport 10
500 Freeport Parkway
Coppell, TX
Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
PROJECT DATA
MIX DESIGN I.D.: 7752
PLACEMENT DATE: 07/30/2003
WEATHER CONDITIONS: Partly cloudy
TIME SAMPLED: 8:1 Oam BATCH TIME: 7:50am
TEMPERATURE (F) AIR 85 F CONCRETE: 88 P
TRUCK NO: 105 TICKET NO: 117715
AIR CONTENT 3.4 UNIT WEIGHT (pct): NA
OVERALL PLACEMENT LOCATION:
North half of north parking lot at northeast entrance
10' east, 5' north of southwest
corner
COMPRESSIVE
STRENGTH
(psi)
3000
3700
3830
3770
191630
037333
07/30/2003
08/28/2003
FRACTURE
TYPE
Unbonded Cap
Unbonded Cap
Unbonded Cap
09/24/2003 56 Unbonded Cap
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and
reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd.
pi Page 2 of 6
RoneEngineers
A LEIGH COMPANY
Client: Duke Realty Services, LP
Attn: Mr. Jeff Langston
5495 Belt Line Road, Suite 360
Dallas TX 75254
Project: Freeport 10
500 Freeport Parkway
Coppell, TX
Services: Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
CONTRACTOR:
CONCRETE SUPPLIER:
PLANT:
SPECIFICATION REQUIREMENTS
STRENGTH:
SLUMP (1o):
AIR
TEST METHOD:
CYLINDER
MARKED
SET NO.
3 1 5.00
3 4 5.00
Duke Realty Services, LP
Potter
On site
4000 psi 28 Days
5" maximum
3 -6%
ASTM C -172
ASTM C -31
ASTM C -143
ASTM C -231
ASTM C -1064
ASTM C -138
ASTM C -39
MEASURED
SLUMP
(inches)
3 2 5.00 08/27/2003
3 3 5.00 08/27/2003
CONCRETE COMPRESSIVE STRENGTH TEST
PROJECT DATA
SAMPLE LOCATION:
REPORT (W TESTS
Concrete Compressive Cylinder 6" x 12" (area 28.27 sq. in.)
DATE
TESTED
08/06/2003
AGE
(days)
7
28
28
09/24/2003 56
MIX DESIGN I.D.: 7752
PLACEMENT DATE: 07/30/2003
WEATHER CONDITIONS: Partly cloudy
TIME SAMPLED: 8:55am BATCH TIME: 8:43am
TEMPERATURE (F) AIR 85 F CONCRETE: 89 F
TRUCK NO: 110 TICKET NO: 117725
AIR CONTENT 4.3 UNIT WEIGHT (pct): NA
OVERALL PLACEMENT LOCATION:
South half of north parking lot, building column lines R to U
Does not comply with specified stren
MAXIMUM
LOAD
(lbs. force)
88575
114445
110160
Average
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77040
Corporate Phone: (214) 630 -9745
Report No.:
Project No.:
Date of Service:
Report Date:
15' north, 10' west of southeast
corner
COMPRESSIVE
STRENGTH
(psi)
191630
037333
07/30/2003
08/28/2003
3130 Unbonded Cap
FRACTURE
TYPE
nbonded Cap
nbonded Cap
Unbonded Cap
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and
reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd.
01 Page 3 of 6
RoneEngineers
A LEIGH COMPANY
Client: Duke Realty Services, LP
Attn: Mr. Jeff Langston
5495 Belt Line Road, Suite 360
Dallas TX 75254
Project:
Services:
CONTRACTOR:
CONCRETE SUPPLIER:
PLANT:
SPECIFICATION REQUIREMENTS
STRENGTH:
SLUMP (in):
AIR
TEST METHOD:
CYLINDER
MARKED
SET NO.
4 1
4 2
4 3
MEASURED
SLUMP DATE
(Inches) TESTED
5.00 08/06/2003
5.00 08/27/2003
5.00 08/27/2003
4 4 5.00 09/24/2003
AGE
(days)
7
28
28
MAXIMUM
LOAD
(lbs. force)
90905
109280
114520
Average
Does not comply with specified strength.
Water added at site: 10 gallons
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77040
Corporate Phone: (214) 630 -9745
CONCRETE COMPRESSIVE STRENGTH TEST
Report No.:
Project No.:
Date of Service:
Report Date:
191630
037333
07/30/2003
08/28/2003
Freeport 10
500 Freeport Parkway
Coppell, TX
Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
PROJECT DATA
Duke Realty Services, LP MIX DESIGN I.D.: 7752
Potter PLACEMENT DATE: 07/30/2003
On site WEATHER CONDITIONS: Partly cloudly
TIME SAMPLED: 9:50am BATCH TIME: 9:32am
TEMPERATURE (F) AIR 87 F CONCRETE: 89 F
TRUCK NO: 1 TICKET NO: 117725
AIR CONTENT 4.6 UNIT WEIGHT (pct): NA
OVERALL PLACEMENT LOCATION:
South half of north parking lot, building column lines R to U
4000 psi 28 Days
5" maximum
3 -6%
ASTM C -172
ASTM C -31
ASTM C -143
ASTM C -231
ASTM C -1064
ASTM C -138 SAMPLE LOCATION: 10' east, 10' north of southwest ASTM C -39 REPORT OF TESTS comer
Concrete Compressive Cylinder 6" x 12" (area 28.27 sq. in.)
COMPRESSIVE
STRENGTH
(psi)
3210
3860
4050
3960
FRACTURE
TYPE
Unbonded Cap
Unbonded Cap
Unbonded Cap
56 Unbonded Cap
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and
reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rene Engineers, Ltd.
01 Page 4 of 6
RoneEngineers
A LEIGH COMPANY
Client: Duke Realty Services, LP
Attn: Mr. Jeff Langston
5495 Belt Line Road, Suite 360
Dallas TX 75254
Project:
Services:
Freeport 10
500 Freeport Parkway
Coppell, TX
Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
CONTRACTOR: Duke Realty Services, LP
CONCRETE SUPPLIER: Potter
PLANT: On site
SPECIFICATION REQUIREMENTS
STRENGTH: 4000 psi 28 Days
SLUMP (in): 5" maximum
AIR Web 3% -6%
TEST METHOD:. ASTM C -172
ASTM C -31
ASTM C -143
ASTM C -231
ASTM C -1064
ASTM C -138
ASTM C -39
CYLINDER
MARKED
SET NO.
MEASURED
SLUMP
(Inches)
5 1 4.50
5 2 4.50 08/27/2003
5 3 4.50 08/27/2003
5 4 4.50
DATE
TESTED
08/06/2003
CONCRETE COMPRESSIVE STRENGTH TEST
PROJECT DATA
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12" (area 28.27 sq. in.)
Report No.:
Project No.:
Date of Service:
Report Date:
MIX DESIGN I.D.: 7752
PLACEMENT DATE: 07/30/2003
WEATHER CONDITIONS:. Partly cloudy
TIME SAMPLED: 10:55am BATCH TIME: 10:37am
TEMPERATURE (F) AIR 86 P CONCRETE: 90 F
TRUCK NO: 103 TICKET NO: 117746
AIR CONTENT 3.5 UNIT WEIGHT (pcf): NA
OVERALL PLACEMENT LOCATION:
North half of south parking lot, building column line E to J
SAMPLE LOCATION: 20' south, 20' west of northeast
corner
AGE
(days)
7
28
28
MAXIMUM
LOAD
(Ibs. force)
86865
109570
109950
Average
Does not comply with specified strength.
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77040
Corporate Phone: (214) 630 -9745
COMPRESSIVE
STRENGTH
(psi)
3070
3870
3890
3880
191630
037333
07/30/2003
08/28/2003
FRACTURE
TYPE
Unbonded Cap
Unbonded Cap
Unbonded Cap
09/24/2003 56 Unbonded Cap
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and
reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd.
01 Page 5 of 6
RoneEngineers
A LEIGH COMPANY
Client: Duke Realty Services, LP
Attn: Mr. Jeff Langston
5495 Belt Line Road, Suite 360
Dallas TX 75254
Project:
Services:
CONTRACTOR:
CONCRETE SUPPLIER:
PLANT:
SPECIFICATION REQUI
STRENGTH:
SLUMP (in):
AIR
TEST METHOD:
CYLINDER
MARKED
SET NO.
6 1 5.00
6 2 5.00
6 3 5.00
6 4 5.00
Technician: Lanny Gist
Report Distribution:
(I) Duke Realty Services, LP
(1) Duke Realty Services, LP
(1) City of Coppell Engineering Dept.
(1) Potter Concrete
Duke Realty Services, LP
Potter
On sit
000 psi 28 Da
5" maximum
ASTM C -172
ASTM C -31
ASTM C -143
ASTM C -231
ASTM C -1064
ASTM C -138
ASTM C -39
MEASURED
SLUMP
(inches)
DATE
TESTED
08/06/2003
08/27/2003
08/27/2003
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77040
Corporate Phone: (214) 630 -9745
CONCRETE COMPRESSIVE STRENGTH TEST
Freeport 10
500 Freeport Parkway
Coppell, TX
Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
PROJECT DATA
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12" (area 28.27 sq. in.)
09/24/2003 56
Started: 7:OOam
(I) Pacheco Koch Consulting Engineers
(I) Engineering Analyst
(1) City of Coppell Bldg. Inspections
MIX DESIGN I.D.: 7752
PLACEMENT DATE: 07/30/2003
WEATHER CONDITIONS: Partly cloudy
TIME SAMPLED: 11:4Oam BATCH TIME: 11:1lam
TEMPERATURE (F) AIR 90 F CONCRETE: 91 F
TRUCK NO: 114 TICKET NO: 117754
AIR CONTENT 5.1 UNIT WEIGHT (pci): NA
OVERALL PLACEMENT LOCATION:
North half of south parking lot, building column line E to J
SAMPLE LOCATION: 10' south, 10' west of northeast
corner
AGE
(days)
7
28
28
Finished: 2:30pm
MAXIMUM
LOAD
(lbs. force)
79505
104235
98245
Average
Does not comply with specified strength.
Report No.:
Project No.:
Date of Service:
Report Date:
COMPRESSIVE
STRENGTH
(psi)
191630
037333
07/30/2003
08/28/2003
FRACTURE
TYPE
2810 Unbonded Cap
3690
Scott Watson, AET
CMT Operations Manager
Unbonded Cap
Unbonded Cap
Unbonded Cap
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and
reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd.
01 Page 6 of 6