Freeport NIP(7.0)-LR030924RoneEngineers
A LEIGH COMPANY
Client: Duke Realty Services, LP
Attn: Mr. Jeff Langston
5495 Belt Line Road, Suite 360
Dallas TX 75254
CONTRACTOR:
CONCRETE SUPPLIER:
PLANT:
SPECIFICATION REQUIREMENTS
STRENGTH: 4000 psi 28 Days
SLUMP (in): 5" maximum
AIR 3 -6%
TEST METHOD: ASTM C-172
ASTM C -31
ASTM C -143
ASTM C -231
ASTM C -1064
ASTM C -138
ASTM C -39
CYLINDER
MARKED
SET NO.
1
1
1
MEASURED
SLUMP
(inches)
1 4.00
Duke Realty Services, LP
Potter
On site
DATE
TESTED
08/05/2003
2 4.00 08/26/2003
3 4.00 08/26/2003
1 4 Hold
Water added at site: 10 gallons
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77040
Corporate Phone: (214) 630.9745
CONCRETE COMPRESSIVE STRENGTH TEST
Project: Freeport 10
500 Freeport Parkway
Coppell, TX
Services: Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
PROJECT DATA
MIX DESIGN I.D.: 7752
PLACEMENT DATE: 07/29/2003
WEATHER CONDITIONS: Clear
TIME SAMPLED: 8:10am BATCH TIME: 7:568111
TEMPERATURE (F) AIR 78 F CONCRETE: 90 F
TRUCK NO: 112
AIR CONTENT 4.6
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12" (area 28 27 sq in
AGE
(days)
7
28
28
MAXIMUM
LOAD
(lbs. force)
100250
127205
130150
Average
Report No.:
Project No.:
Date of Service:
Report Date:
191554
037333
07/29/2003
09/24/2003
TICKET NO: 117656
UNIT WEIGHT (pci: NA
OVERALL PLACEMENT LOCATION:
North half of south parking lot, Building Column Line GO to LL
SAMPLE LOCATION: 10' west, 10' north of southeast
corner
COMPRESSIVE
STRENGTH
(psi)
3550
4500
4600
4550
FRACTURE
TYPE
Unbonded Cap
Unbonded Cap
Unbonded Cap
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and
reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Bone Engineers, Ltd.
01DD Pagel of 5
RoneEngineers
A LEIGH COMPANY
Client: Duke Realty Services, LP
Attn: Mr. Jeff Langston
5495 Belt Line Road, Suite 360
Dallas TX 75254
Project: Freeport 10
500 Freeport Parkway
Coppell, TX
Services: Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
CONTRACTOR:
CONCRETE SUPPLIER:
PLANT: On site
SPECIFICATION REQUIREMENTS
4000 psi 28 Days
5" maximum
3% 6%
ASTM C -172
ASTM C -31
ASTM C -143
ASTM C -231
ASTM C -1064
ASTM C -138
ASTM C -39
STRENGTH:
SLUMP (in):
AIR
TEST METHOD:
CYLINDER
MARKED
SET NO.
2 1
2 2
2 3
2 4
Duke Realty Services, LP
Potter
MEASURED
SLUMP DATE
(inches) TESTED
5.00 08/05/2003
5.00 08/26/2003
5.00 08/26/2003
5.00
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77040
Corporate Phone: (214) 630 -9745
CONCRETE COMPRESSIVE STRENGTH TEST
Report No.:
Project No.:
Date of Service:
Report Date:
191554
037333
07/29/2003
09/24/2003
PROJECT DATA
MIX DESIGN I.D.: 7752
PLACEMENT DATE: 07/29/2003
WEATHER CONDITIONS: Clear
TIME SAMPLED: 9:15am BATCH TIME: 9:OOam
TEMPERATURE (F) -AIR 82 F CONCRETE: 90 F
TRUCK NO: 1 12 TICKET NO: 117666
AIR CONTENT 3.9 UNIT WEIGHT (pct): NA
OVERALL PLACEMENT LOCATION:
North half of south parking lot, Building Column Line GG to LL
SAMPLE LOCATION: 75' west, 15' north of southeast
comer
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12" (area 28.27 sq. in.)
AGE
(days)
7
28
28
09/23/2003 56
MAXIMUM
LOAD
(Ibs. force)
Does not comply with specified strength.
COMPRESSIVE
STRENGTH
(psi)
86245 3050
104875
106355
Average
3710
3760
3740
117660 4160
FRACTURE
TYPE
Unbonded Cap
Unbonded Cap
Unbonded Cap
Unbonded Cap
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and
reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd.
OIDD Page 2 of 5
RoneEngineers
A LEIGH COMPANY
Client: Duke Realty Services, LP
Attn: Mr. Jeff Langston
5495 Belt Line Road, Suite 360
Dallas TX 75254
Project: Freeport 10
500 Freeport Parkway
Coppell, TX
Services: Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
CONTRACTOR:
CONCRETE SUPPLIER:
PLANT:
Duke Realty Services, LP
Potter
On site
SPECIFICATION REQUIREMENTS
STRENGTH: 4000 psi 28 Days
SLUMP (in): 5" maximum
AIR 3% 6%
TEST METHOD: ASTM C -172
ASTM C -31
ASTM C -143
ASTM C -231
ASTM C -1064
ASTM C -138
ASTM C -39
CYLINDER
MARKED
SET NO.
MEASURED
SLUMP
(inches)
3 1 4.50
DATE
TESTED
08/05/2003
3 2 4.50 08/26/2003
3 3 4.50 08/26/2003
3 4 Hold
CONCRETE COMPRESSIVE STRENGTH TEST
Report No.:
Project No.:
Date of Service:
Report Date:
PROJECT DATA
MIX DESIGN I.D.: 7752
PLACEMENT DATE: 07/29/2003
WEATHER CONDITIONS: Clear
TIME SAMPLED: 10: 10a111 BATCH TIME:
TEMPERATURE (F) AIR 84
TRUCK NO: 120
AIR CONTENT 4.6
191554
037333
07/29/2003
09/24/2003
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77040
Corporate Phone: (214) 630 -9745
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12" (area 28.27 sq. in.)
9:45am
F CONCRETE: 89 F
TICKET NO: 117675
UNIT WEIGHT (pct): NA
OVERALL PLACEMENT LOCATION:
North half of south parking lot, Building Column Line GG to LL
SAMPLE LOCATION: 125' west, 10' south of northeast
corner
AGE
(days)
7
28
28
MAXIMUM
LOAD
(lbs. force)
104335 3690
128025
129475
Average
COMPRESSIVE
STRENGTH
(psi)
4530
4580
4560
FRACTURE
TYPE
Unbonded Cap
Unbonded Cap
Unbonded Cap
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and
reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd.
01DD Page 3 of 5
RoneEngineers
A LEIGH COMPANY
Client: Duke Realty Services, LP
Attn: Mr. Jeff Langston
5495 Belt Line Road, Suite 360
Dallas TX 75254
Project:
Services:
CYLINDER
MARKED
SET NO.
Freeport 10
500 Freeport Parkway
Coppell, TX
Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
CONTRACTOR: Duke Realty Services, LP
CONCRETE SUPPLIER: Potter
PLANT: On site
SPECIFICATION REQUIREMENTS
STRENGTH: 4000 psi 28 Days
SLUMP (in): 5" maximum
AIR ("io): 3% 6%
TEST METHOD: ASTM C -172
ASTM C -31
ASTM C -143
ASTM C -231
ASTM C -1064
ASTM C -138
ASTM C -39
MEASURED
SLUMP
(inches)
DATE
TESTED
4 1 5.00 08/05/2003
4 2 5.00 08/26/2003
4 3 5.00 08/26/2003
4 4 5.00
PROJECT DATA
MIX DESIGN I.D.: 7752
PLACEMENT DATE: 07/29/2003
WEATHER CONDITIONS: Clear
TIME SAMPLED: 11:1 Sam BATCH TIME: 10:54am
TEMPERATURE (F) AIR 86 F CONCRETE: 90 F
TRUCK NO: 113 TICKET NO: 117686
AIR CONTENT 4.6 UNIT WEIGHT (pcf): NA
OVERALL PLACEMENT LOCATION:
North half of south parking lot, Building Column Line GG to LL
09/23/2003
CONCRETE COMPRESSIVE STRENGTH TEST
SAMPLE LOCATION: 30' east, 10' south of northwest
corner
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12" (area 28.27 sq. in.)
AGE
(days)
7
28
28
56
MAXIMUM
LOAD
(Ibs. force)
86775
110835
114300
Average
Does not comply with specified strength.
Water added at site: 5 gallons
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77040
Corporate Phone: (214) 630 -9745
Report No.:
Project No.:
Date of Service:
Report Date:
COMPRESSIVE
STRENGTH
(psi)
191554
037333
07/29/2003
09/24/2003
3070
3920
4040
3980
122670 4340
FRACTURE
TYPE
Unbonded Cap
Unbonded Cap
Unbonded Cap
Unbonded Cap
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which wee have no control. letters t a d
reports are for the exclusive use of the clients to whom they are addressed and shall 4 of 5 reproduced except in full without the written approval of Rone Engineers,
01DD
RoneEngineers
A LEIGH COMPANY
CONTRACTOR:
CONCRETE SUPPLIER:
PLANT:
SLUMP (in):
AIR
TEST METHOD:
CYLINDER
MARKED
SET NO.
5 1 5.00
5 2 5.00
5 3 5.00
5 4 5.00
Technician: Lanny Gist
Report Distribution:
(1) Duke Realty Services, LP
(1) Duke Realty Services, LP
(1) City of Coppell Engineering Dept.
(1) Potter Concrete
Client: Duke Realty Services, LP
Attn: Mr. Jeff Langston
5495 Belt Line Road, Suite 360
Dallas TX 75254
Project: Freeport 10
500 Freeport Parkway
Coppell, TX
Services: Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Duke Realty Services, LP
Potter
On site
SPECIFICATION REQUIREMENTS
STRENGTH: 4000 psi 28 Days
5" maximum
3 -6%
ASTM C -172
ASTM C -31
ASTM C -143
ASTM C -231
ASTM C -1064
ASTM C -138
ASTM C -39
MEASURED
SLUMP
(inches)
DATE
TESTED
08/05/2003
08/26/2003
08/26/2003
CONCRETE COMPRESSIVE STRENGTH TEST
PROJECT DATA
MIX DESIGN 1.D.: 7752
PLACEMENT DATE:
WEATHER CONDITIONS:
TIME SAMPLED: 12:00pm
TEMPERATURE (F) AIR
TRUCK NO: 120
AIR CONTENT 3.8
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12" (area 28.27 sq. in.)
09/23/2003 56
Started: 7:30am
AGE
(days)
7
28
28
Does not comply with specified strength.
(1) Pacheco Koch Consulting Engineers
(1) Engineering Analyst
(1) City of Coppell Bldg. Inspections
SAMPLE LOCATION:
Finished: 2:30pm
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77040
Corporate Phone: (214) 630-9745
Report No.:
Project No.:
Date of Service:
Report Date:
191554
037333
07/29/2003
09/24/2003
07/29/2003
Clear
BATCH TIME: 11:48am
92 F CONCRETE: 92 F
TICKET NO: 117694
UNIT WEIGHT (pcf): NA
OVERALL PLACEMENT LOCATION:
North half of south parking lot, Building Column Line GG to LL
MAXIMUM
LOAD
(Ibs. force)
86685
107300
109540
Average
10' east, 10' north of southwest
corner
119215
COMPRESSIVE
STRENGTH
(psi)
3070
3790
3870
3830
4220
K. Scott Watson, AET
CMT Operations Manager
FRACTURE
TYPE
Unbonded Cap
Unbonded Cap
Unbonded Cap
Unbonded Cap
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and
reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd.
OIDD Page 5 of 5
RoneEngineers
A LEIGH COMPANY
Client: Duke Realty Services, LP
Attn: Mr. Jeff Langston
5495 Belt Line Road, Suite 360
Dallas TX 75254
Project:
Services:
CONTRACTOR:
CONCRETE SUPPLIER:
PLANT:
SPECIFICATION REQUIREMENTS
STRENGTH: 4000 psi 28 Days
SLUMP (in): 5" maximum
AIR 3% 6%
TEST METHOD: ASTM C-172
ASTM C -31
ASTM C -143
ASTM C -231
ASTM C -1064
ASTM C -138
ASTM C -39
CYLINDER
MARKED
SET NO.
1 1
1 2
1 3
Freeport 10
500 Freeport Parkway
Coppell, TX
Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
PROJECT DATA
Duke Realty Services, LP MIX DESIGN I.D.: 7752
Potter PLACEMENT DATE: 08/26/2003
On site WEATHER CONDITIONS: Clear
TIME SAMPLED: 7:55am BATCH TIME: 7:35am
TEMPERATURE (F) AIR 80 F CONCRETE 88 F
TRUCK NO: 105 TICKET NO: 140
AIR CONTENT (o): 4.3 UNIT WEIGHT (pef): NA
OVERALL PLACEMENT LOCATION:
North half of north parking lot, building column line KK to QQ
MEASURED
SLUMP
(inches)
4.0
4.0
4.0
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12" (area 28.27 sq. in.)
DATE
TESTED
09/02/2003
09/23/2003
09/23/2003
1 4 Hold
Water added at site: 10 gallons
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77040
Corporate Phone: (214) 630-9745
CONCRETE COMPRESSIVE STRENGTH TEST
AGE
(days)
7
28
28
MAXIMUM
LOAD
(lbs. force)
119030
132795
137785
Average
Report No.:
Project No.:
Date of Service:
Report Date:
SAMPLE LOCATION: 15' west, 10' south of northeast
comer
COMPRESSIVE
STRENGTH
(psi)
4210
4700
4870
4790
193128
037333
08/26/2003
09/24/2003
FRACTURE
TYPE
Unbonded Cap
Unbonded Cap
Unbonded Cap
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and
reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd.
01DD Page 1 of 5
RoneEngineers
A LEIGH COMPANY
Client: Duke Realty Services, LP
Attn: Mr. Jeff Langston
5495 Belt Line Road, Suite 360
Dallas TX 75254
Project:
Services:
CONTRACTOR:
CONCRETE SUPPLIER:
PLANT:
SPECIFICATION REQUIREMENTS
STRENGTH: 4000 psi 28 Days
SLUMP (in): 5" maximum
AIR 3% 6%
TEST METHOD: ASTM C-172
ASTM C -31
ASTM C -143
ASTM C -231
ASTM C -1064
ASTM C -138
ASTM C -39
CYLINDER
MARKED
SET NO.
2 1
2 2
2 3
CONCRETE COMPRESSIVE STRENGTH TEST
Freeport 10
500 Freeport Parkway
Coppell, TX
Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Duke Realty Services, LP
Potter
On site
MEASURED
SLUMP DATE
(inches) TESTED
4.0 09/02/2003
4.0 09/23/2003
4.0 09/23/2003
2 4 Hold
PROJECT DATA
Report No.:
Project No.:
Date of Service:
Report Date:
MIX DESIGN I.D.: 7752
PLACEMENT DATE: 08/26/2003
WEATHER CONDITIONS: Clear
TIME SAMPLED: 9:OOam BATCH TIME: 8:3Sam
TEMPERATURE (F) AIR 81 F CONCRETE: 88 F
TRUCK NO: 1 TICKET NO: 148
AIR CONTENT 4.5 UNIT WEIGHT (pcf): NA
OVERALL PLACEMENT LOCATION:
North half of north parking lot, building column line KK to QQ
SAMPLE LOCATION: 50' west, 20' south of northeast
corner
RRPORT (W TESTS
Concrete Compressive Cylinder 6" x 12" (area 28.27 sq. in.)
AGE
(days)
7
28
28
MAXIMUM
LOAD
(lbs. force)
118455
135510
138325
Average
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77040
Corporate Phone: (214) 630-9745
COMPRESSIVE
STRENGTH
(psi)
193128
037333
08/26/2003
09/24/2003
FRACTURE
TYPE
4190 Unbonded Cap
4790 Unbonded Cap
4890 Unbonded Cap
4840
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and
reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd.
01DD Page 2 of 5
RoneEngineers
to
A LEIGH COMPANY
Client: Duke Realty Services, LP
Attn: Mr. Jeff Langston
5495 Belt Line Road, Suite 360
Dallas TX 75254
Project:
Services:
CONTRACTOR:
CONCRETE SUPPLIER:
PLANT:
SPECIFICATION REQUIREMENTS
STRENGTH: 4000 psi 28 Days
SLUMP (in): 5" maximum
AIR 3 -6%
TEST METHOD: ASTM C-172
ASTM C -31
CYLINDER
MARKED
SET NO.
3 1
3 2
3 3
Freeport 10
500 Freeport Parkway
Coppell, TX
Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Duke Realty Services, LP
Potter
On site
ASTM C -143
ASTM C -231
ASTM C -1064
ASTM C -138
ASTM C -39
MEASURED
SLUMP
(inches)
4.5
4.5
4.5
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12" (area 28.27 sq. in.)
DATE
TESTED
09/02/2003
09/23/2003
09/23/2003
3 4 Hold
AGE
(days)
7
28
28
CONCRETE COMPRESSIVE STRENGTH TEST
MAXIMUM
LOAD
(lbs. force)
116620
135415
143555
Average
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77040
Corporate Phone: (214) 630 -9745
Report No.:
Project No.:
Date of Service:
Report Date:
PROJECT DATA
MIX DESIGN I.D.: 7752
PLACEMENT DATE: 08/26/2003
WEATHER CONDITIONS: Clear
TIME SAMPLED: 10:10am BATCH TIME: 9:46am
TEMPERATURE (F) AIR 84 F CONCRETE: 88 F
TRUCK NO: 105 TICKET NO: 158
AIR CONTENT 4.0 UNIT WEIGHT (pcf): NA
OVERALL PLACEMENT LOCATION:
North half of north parking lot, building column line KK to QQ
SAMPLE LOCATION: 30' east, 20' south of northwest
corner
COMPRESSIVE
STRENGTH
(psi)
4120
4790
5080
4940
193128
037333
08/26/2003
09/24/2003
FRACTURE
TYPE
Unbonded Cap
Unbonded Cap
Unbonded Cap
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and
reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd.
OIDD Page of
RoneEngineers
A LEIGH COMPANY
Client: Duke Realty Services, LP
Attn: Mr. Jeff Langston
5495 Belt Line Road, Suite 360
Dallas TX 75254
Project:
Services:
CONTRACTOR: Duke Realty Services, LP
CONCRETE SUPPLIER: Potter
PLANT: On site
SPECIFICATION REQUIREMENTS
STRENGTH:
SLUMP (in):
AIR
TEST METHOD:
CYLINDER
MARKED
SET NO.
4 1
4 2
4 3
4000 psi 28 Days
5" maximum
3% 6%
ASTM C -172
ASTM C -31
ASTM C -143
ASTM C -231
ASTM C -1064
ASTM C -138
ASTM C -39
MEASURED
SLUMP
(inches)
5.0
5.0
5.0
DATE
TESTED
09/02/2003
4 4 Hold
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77040
Corporate Phone: (214) 630 -9745
CONCRETE COMPRESSIVE STRENGTH TEST
Report No.:
Project No.:
Date of Service:
Report Date:
193128
037333
08/26/2003
09/24/2003
Freeport 10
500 Freeport Parkway
Coppell, TX
Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
PROJECT DATA
MIX DESIGN I.D.: 7752
PLACEMENT DATE: 08/26/2003
WEATHER CONDITIONS: Clear
TIME SAMPLED 11' 15am BATCH TIME: 10:49am
TEMPERATURE (F) AIR 86 F CONCRETE: 89 F
TRUCK NO: 105 TICKET NO: 170
AIR CONTENT 4.3 UNIT WEIGHT (pcf): NA
OVERALL PLACEMENT LOCATION:
North half of north parking lot, building column line KK to QQ
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12" (area 28.27 sq. in.)
AGE
(days)
7
09/23/2003 28
09/23/2003 28
SAMPLE LOCATION: 5' east, 5' north of southwest
corner
MAXIMUM
LOAD
(Ibs. force)
102625
122460
122065
Average
COMPRESSIVE
STRENGTH
(Psi)
3630
4330
4320
4330
FRACTURE
TYPE
Unbonded Cap
Unbonded Cap
Unbonded Cap
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and
reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd.
01DD Page 4 of 5
RoneEngineers
A LEIGH COMPANY
Client: Duke Realty Services, LP
Attn: Mr. Jeff Langston
5495 Belt Line Road, Suite 360
Dallas TX 75254
Project:
Services:
CONTRACTOR:
CONCRETE SUPPLIER:
PLANT:
SPECIFICATION REQUIREMENTS
STRENGTH: 4000 psi 28 Days
SLUMP (in): 5" maximum
AIR 3 6%
TEST METHOD: ASTM C -172
ASTM C -31
ASTM C -143
ASTM C -231
ASTM C -1064
ASTM C -138
ASTM C -39
CYLINDER
MARKED
SET NO.
5 1
5 2
5 3
5 4
MEASURED
SLUMP
(inches)
5.0
5.0
5.0
5.0
Technician: Lanny Gist
Report Distribution:
(1) Duke Realty Services, LP
(1) Duke Realty Services, LP
(1) City of Coppell Engineering Dept.
(1) Potter Concrete
Duke Realty Services, LP
Potter
On site
DATE
TESTED
09/02/2003
09/23/2003
09/23/2003
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77040
Corporate Phone: (214) 630.9745
CONCRETE COMPRESSIVE STRENGTH TEST
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12" (area 28.27 sq. in.)
AGE
(days)
7
28
28
10/21/2003 56
MAXIMUM
LOAD
(lbs. force)
85685
107885
105035
Average
Does not comply with specified strength.
Started: 7:30am Finished: 2: 30pm
(1) Pacheco Koch Consulting Engineers
(1) Engineering Analyst
(1) City of Coppell Bldg. Inspections
Report No.:
Project No.:
Date of Service:
Report Date:
SAMPLE LOCATION: 15' south, 5' east of northwest
corner
COMPRESSIVE
STRENGTH
(psi)
193128
037333
08/26/2003
09/24/2003
Freeport 10
500 Freeport Parkway
Coppell, TX
Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
PROJECT DATA
MIX DESIGN I.D.: 7752
PLACEMENT DATE: 08/26/2003
WEATHER CONDITIONS: Clear
TIME SAMPLED: 12:30pm BATCH TIME: 11:SOam
TEMPERATURE (F) AIR 90 F CONCRETE: 90 F
TRUCK NO: 103 TICKET NO: 179
AIR CONTENT 4.7 UNIT WEIGHT (pcf): NA
OVERALL PLACEMENT LOCATION:
Northwest spproach, north parking lot
K. Scott Watson, AET
CMT Operations Manager
FRACTURE
TYPE
3030 Unbonded Cap
3820 Unbonded Cap
3710 Unbonded Cap
3770
Unbonded Cap
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and
reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd.
o1DD Page 5 of 5