Freeport NIP(7.0)-LR030919RoneEngineers
A LEIGH COMPANY
Client: Duke Realty Services, LP
Attn: Mr. Jeff Langston
5495 Belt Line Road, Suite 360
Dallas TX 75254
Project:
Services:
CONTRACTOR:
CONCRETE SUPPLIER:
PLANT:
SPECIFICATION REQUIREMENTS
STRENGTH: 4000 psi 28 Days
SLUMP (in): 5" maximum
AIR 3% 6%
TEST METHOD: ASTM C -172
ASTM C -31
ASTM C -143
ASTM C -231
ASTM C -1064
ASTM C -138
ASTM C -39
CYLINDER
MARKED
SET NO.
1 1
1 2
1 3
I 4
Freeport 10
500 Freeport Parkway
Coppell, TX
Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Duke Realty Services, LP
Potter
On site
MEASURED
SLUMP
(inches)
5.0
5.0
5.0
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12" (area 28.27 sq. in.)
DATE
TESTED
08/28/2003
09/18/2003
09/18/2003
5.0 10/16/2003
CONCRETE COMPRESSIVE STRENGTH TEST
SAMPLE LOCATION: Southeast parking area, 20' east,
20' south of northwest corner
AGE
(days)
7
28
28
MAXIMUM
LOAD
(lbs. force)
74650
96350
99525
Average
Does not comply with specified strength.
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77040
Corporate Phone: (214) 630-9745
Report No.:
Project No.:
Date of Service:
Report Date:
COMPRESSIVE
STRENGTH
(psi)
2640
3410
3520
3470
192917
037333
08/21/2003
09/19/2003
PROJECT DATA
MIX DESIGN I.D.: 7752
PLACEMENT DATE: 08/21/2003
WEATHER CONDITIONS: Clear
TIME SAMPLED: 7:35am BATCH TIME: 7:1Sam
TEMPERATURE (F) AIR 81 F CONCRETE: 86 F
TRUCK NO: 107 TICKET NO: 11
AIR CONTENT 4.7 UNIT WEIGHT (pct): NA
OVERALL PLACEMENT LOCATION:
South half of east fire lane and parking area, southeast corner of building
FRACTURE
TYPE
Unbonded Cap
Unbonded Cap
Unbonded Cap
56 Unbonded Cap
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and
reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd.
OIDD Page 1 of 5
RoneEngineers
A LEIGH COMPANY
Client: Duke Realty Services, LP
Attn: Mr. Jeff Langston
5495 Belt Line Road, Suite 360
Dallas TX 75254
Project: Freeport 10
500 Freeport Parkway
Coppell, TX
Services: Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
CONTRACTOR:
CONCRETE SUPPLIER:
PLANT:
SPECIFICATION REQUIREMENTS
STRENGTH: 4000 psi 28 Days
SLUMP (in): 5" maximum
AIR 3% 6%
TEST METHOD: ASTM C -172
ASTM C -31
ASTM C -143
ASTM C -231
ASTM C -1064
ASTM C -138
ASTM C -39
CYLINDER
MARKED
SET NO.
2 1
2 2
2 3
2 4
Duke Realty Services, LP
Potter
On site
MEASURED
SLUMP
(inches)
4.5
4.5
4.5
Concrete Compressive Cylinder 6" x 12" (area 28.27 sq. in.)
DATE
TESTED
08/28/2003
09/18/2003
09/18/2003
Hold
AGE
(days)
7
28
28
MAXIMUM
LOAD
(Ibs. force)
93170
111225
116585
Average
CONCRETE COMPRESSIVE STRENGTH TEST
Does not comply with specified strength.
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77040
Corporate Phone: (214) 630 -9745
Report No.:
Project No.:
Date of Service:
Report Date:
192917
037333
08/21/2003
09/19/2003
PROJECT DATA
MIX DESIGN I.D.: 7752
PLACEMENT DATE: 08/21/2003
WEATHER CONDITIONS: Clear
TIME SAMPLED: 9:OOam BATCH TIME: 8:34am
TEMPERATURE (F) AIR 82 F CONCRETE: 88 F
TRUCK NO: 107 TICKET NO: 19
AIR CONTENT 5.2 UNIT WEIGHT (pct): NA
OVERALL PLACEMENT LOCATION:
South half of east fire lane and parking area, southeast corner of building
SAMPLE LOCATION: East fire lane, 20' south of north
header
REPORT OF TESTS
COMPRESSIVE
STRENGTH
(psi)
3290
3930
4120
4030
FRACTURE
TYPE
Unbonded Cap
Unbonded Cap
Unbonded Cap
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided
sf for testing.
gd We as su m no r e sp o si bil it y co varition in
in quality
(composition, appearance, performance, etc.) or any other feature of similar subject matter provided by p e
reports are for the exclusive use of the clients to whom they are addressed and shall 2 f e s reproduced except in full without the written approval of Rone Engineers, Ltd.
RoneEngineers
A LEIGH COMPANY
Client:
Project:
Services:
Duke Realty Services, LP
Attn: Mr. Jeff Langston
5495 Belt Line Road, Suite 360
Dallas TX 75254
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77040
Corporate Phone: (214) 630-9745
CONCRETE COMPRESSIVE STRENGTH TEST
Report No.:
Project No.:
Date of Service:
Report Date:
192917
037333
08/21/2003
09/19/2003
Freeport 10
500 Freeport Parkway
Coppell, TX
Obtain s samples the fresh concrete at t
laboratory for can g placement and teti locations, perform with app a standard cast compressive strength samples and bring
PROJECT DATA
MIX DESIGN I.D.: 7752
PLACEMENT DATE: 08/21/2003
WEATHER CONDITIONS: Clear
TIME SAMPLED: 10:50am BATCH TIME: 10:25 am
TEMPERATURE (F) AIR 85 F CONCRETE: 89 F
TICKET NO: 30
UNIT WEIGHT tact): NA
CONTRACTOR: Duke Realty Services, LP
CONCRETE SUPPLIER: Potter
PLANT: On site
SPECIFICATION REQUIREMENTS
STRENGTH: 4000 psi 28 Days
SLUMP (in): 5" maximum
AIR 3% 6%
TEST METHOD:
ASTM C -172
ASTM C -31
ASTM C -143
ASTM C -231
ASTM C -1064
ASTM C -138
ASTM C -39
CYLINDER MEASURED
MARKED SLUMP DATE
SET NO. (inches) TESTED
3 1 4.0 08/28/2003
3 2 4 09/18/2003
3 3 4 09/18/2003
3 4
Hold
Water added at site: 10 gallons
TRUCK NO: 1 1
AIR CONTENT /o): 4.9
OVERALL PLACEMENT LOCATION:
South half of east fire lane and parking area, southeast corner of building
SAMPLE LOCATION:
t 1 1
Concrete Compressive Cylinder 6" x 12" (area 28.27 sq. in.)
AGE
(days)
7
28
28
MAXIMUM
LOAD
(lbs. force)
98490
130800
123185
Average
East fire lane, 200' south of
north header
COMPRESSIVE
STRENGTH
(psi)
3480
4630
4360
4500
FRACTURE
TYPE
Unbonded Cap
Unbonded Cap
Unbonded Cap
LIMITATIONS: appearance, Tae test performance, presented e or any other prepared
e of similar subject specific tter provid d persons or conditions ons over which we have no control Our letters and
(composition, r the exclusive
reports are for lusive use of the clients to whom they are addressed and P shall not
3 of 5 reproduced except in full without the written approval of Rone Engineers, Ltd.
nrnn
RoneEngineers
A LEIGH COMPANY
Client: Duke Realty Services, LP
Attn: Mr. Jeff Langston
5495 Belt Line Road, Suite 360
Dallas TX 75254
Project:
Services:
CONTRACTOR: Duke Realty Services, LP
CONCRETE SUPPLIER: Potter
PLANT: On site
SPECIFICATION REQUIREMENTS
STRENGTH: 40001151 28 Days
SLUMP (in): 5" maximum
AIR 3% 6%
TEST METHOD: ASTM C -172
ASTM C -31
ASTM C -143
ASTM C -231
ASTM C -1064
ASTM C -138
ASTM C -39
CYLINDER
MARKED
SET NO.
4
4 2
4 3
4 4
Freeport 10
500 Freeport Parkway
Coppell, TX
Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
MEASURED
SLUMP
(inches)
4.5
4.5
4.5
East fire lane, 300' south of
north header
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12" (area 28.27 sq. in.)
DATE
TESTED
08/28/2003
09/18/2003
09/18/2003
Hold
Water added at site: 10 gallons
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77040
Corporate Phone: (214) 630 -9745
CONCRETE COMPRESSIVE STRENGTH TEST
SAMPLE LOCATION:
AGE
(days)
7
28
28
MAXIMUM
LOAD
(lbs. force)
94370
122520
128265
Average
Report No.:
Project No.:
Date of Service:
Report Date:
192917
037333
08/21/2003
09/19/2003
PROJECT DATA
MIX DESIGN I.D.: 7752
PLACEMENT DATE: 08/21/2003
WEATHER CONDITIONS: Clear
TIME SAMPLED: 12.00pm BATCH TIME: 11:26am
TEMPERATURE (F) AIR 90 F CONCRETE: 90 F
TRUCK NO: 114 TICKET NO: 38
AIR CONTENT 5.1 UNIT WEIGHT (pre: NA
OVERALL PLACEMENT LOCATION:
South half of east fire lane and parking area, southeast corner of building
COMPRESSIVE
STRENGTH
(psi)
3340
4330
4540
4440
FRACTURE
TYPE
Unbonded Cap
Unbonded Cap
Unbonded Cap
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and
reports are for the exclusive use of the clients to whom they are addressed and P reproduced except in full without the written approval of Rone Engineers, Ltd.
Page 4 of 5
RoneEngineers
EZEIN
Client: Duke Realty Services, LP
Attn: Mr. Jeff Langston
5495 Belt Line Road, Suite 360
Dallas TX 75254
Project:
Freeport 10
500 Freeport Parkway
Coppell, TX
Services: Obtain s samples off fresh concrete
for curing the placement
and testing locations, perform i uird field le standar cast compressive strength samples and bring
PROJECT DATA
MIX DESIGN LD.: 7752
PLACEMENT DATE: 08/21/2003
WEATHER CONDITIONS: Clear
BATCH TIME: NA
TIME SAMPLED: 2:30pm
TEMPERATURE (F) AIR 99 F CONCRETE: 101 F
TRUCK NO: NA TICKET NO: NA
AIR CONTENT 4.2 UNIT WEIGHT (pcf): NA
OVERALL PLACEMENT LOCATION:
East fire lane
CONTRACTOR:
CONCRETE SUPPLIER:
PLANT:
SPECIFICATION REQUIREMENTS
STRENGTH: 4000 psi 28 Days
SLUMP (in): 5" maximum
AIR 3% 6%
TEST METHOD: ASTM C -31
ASTM C -143
ASTM C -231
ASTM C -1064
ASTM C -138
ASTM C -39
CYLINDER MEASURED
MARKED SLUMP DATE
SET NO. (inches) TESTED
5 1 4.25 08/28/2003
2 4.25 09/18/2003
5
5 3 4.25
09/18/2003
5 4
Technician: Lanny Gist
Report Distribution:
(I) Duke Realty Services, LP
(1) Duke Realty Services, LP
(1) City of Coppell Engineering Dept.
(1) Potter Concrete
Duke Realty Services, LP
Potter
On site
CONCRETE COMPRESSIVE STRENGTH TEST
(1) Pacheco Koch Consulting Engineers
(I) Engineering Analyst
(1) City of Coppell Bldg. Inspections
Report No.:
Project No.:
Date of Service:
Report Date:
SAMPLE LOCATION: 25' north of north header
P e t 1
Concrete Compressive Cylinder 6" x 12" (area 28.27 sq. in.
AGE
(days)
7
28
28
MAXIMUM
LOAD
(Ibs. force)
129525
149865
151415
Average
Started: 6:30am Finished: 4:OOpm
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, HOUSI011, TX Corporate Phone: (214)630-9
192917
037333
08/21/2003
09/19/2003
COMPRESSIVE
STRENGTH
(Psi)
4580
00
FRACTURE
TYPE
Unbonded Cap
Unbonded Cap
Unbonded Cap
5350
5330
I
Wit
Scott Watson, AET
CMT Operations Manager
LIMITATIONS: The test results presented herein were prepared based upon the specific of n ett, Ltd.
fic samples provided for testing. We assume no responsibility for variation in quality
(c eports enforpthe ere us of the clients to whomethey feature
re of similar subject ttr provided addressed s and shall not be reproduced except in full without the frmance, etc.) or any r over
written app have no control. Our Our letters and
Page 5 of 5
RoneEngineers
A LEIGH COMPANY
Client: Duke Realty Services, LP
Attn: Mr. Jeff Langston
5495 Belt Line Road, Suite 360
Dallas TX 75254
Project:
Services:
CONTRACTOR:
CONCRETE SUPPLIER:
PLANT:
CYLINDER
MARKED
SET NO.
1 1
1 2
1 3
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77040
Corporate Phone: (214) 630 -9745
CONCRETE COMPRESSIVE STRENGTH TEST
Report No.:
Project No.:
Date of Service:
Report Date:
191316
037333
07/24/2003
09/19/2003
Freeport 10
500 Freeport Parkway
Coppell, TX
Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Duke Realty Services, LP
Potter
On site
SPECIFICATION REQUIREMENTS
STRENGTH: 4000 psi 28 Days
SLUMP (in): 5" maximum
AIR 3% 6%
TEST METHOD: ASTM C-172
ASTM C -31
ASTM C -143
ASTM C -231
ASTM C -1064
ASTM C -138
ASTM C -39
MEASURED
SLUMP DATE
(inches) TESTED
4.5 07/31/2003
4.5 08/21/2003
4.5 08/21/2003
1 4 Hold
PROJECT DATA
MIX DESIGN I.D.: 7752
PLACEMENT DATE: 07/24/2003
WEATHER CONDITIONS: Clear
TIME SAMPLED: 7:25aM BATCH TIME: 7:O9am
TEMPERATURE (F) AIR 80 F CONCRETE: 86 F
TRUCK NO: 1 TICKET NO: 117515
AIR CONTENT 3.7 UNIT WEIGHT (pct): NA
OVERALL PLACEMENT LOCATION:
South half of south parking lot, Building Column Line MM to NN
SAMPLE LOCATION: 15' west, 10' north, southeast
corner
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12" (area 28.27 sq. in.)
AGE
(days)
7
28
28
MAXIMUM
LOAD
(lbs. force)
103180
124455
123065
Average
COMPRESSIVE
STRENGTH
(psi)
3650
4400
4350
4380
FRACTURE
TYPE
Unbonded Cap
Unbonded Cap
Unbonded Cap
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and
reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd.
OIDD Pagelof6
RoneEngineers
A LEIGH COMPANY
Client: Duke Realty Services, LP
Attn: Mr. Jeff Langston
5495 Belt Line Road, Suite 360
Dallas TX 75254
Project: Freeport 10
500 Freeport Parkway
Coppell, TX
Services: Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
CONTRACTOR: Duke Realty Services, LP
CONCRETE SUPPLIER: Potter
PLANT: On site
SPECIFICATION REQUIREMENTS
STRENGTH: 4000 psi 28 Days
SLUMP (in): 5" maximum
AIR 3% 6%
TEST METHOD: ASTM C -172
ASTM C -31
ASTM C -143
ASTM C -231
ASTM C -1064
ASTM C -138
ASTM C -39
CYLINDER
MARKED
SET NO.
2 1
2 2
2 3
2 4
MEASURED
SLUMP
(inches)
5.0
5.0
5.0
5.0
DATE
TESTED
07/31/2003
08/21/2003
08/21/2003
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77040
Corporate Phone: (214) 630 -9745
CONCRETE COMPRESSIVE STRENGTH TEST
PROJECT DATA
09/18/2003 56
Report No.:
Project No.:
Date of Service:
Report Date:
191316
037333
07/24/2003
09/19/2003
MIX DESIGN I.D.: 7752
PLACEMENT DATE: 07/24/2003
WEATHER CONDITIONS: Clear
TIME SAMPLED: 8:5Oam BATCH TIME: 8:35am
TEMPERATURE (F) AIR 84 F CONCRETE: 86 F
TRUCK NO: 108 TICKET NO: 117531
AIR CONTENT 3.7 UNIT WEIGHT (pcf): NA
OVERALL PLACEMENT LOCATION:
South half of north parking lot, Building Column Line Z to LL
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12" (area 28.27 sq. in.)
SAMPLE LOCATION: 10' east, 10' north of southwest
COMM'
AGE
(days)
7
28
28
MAXIMUM
LOAD
(Ibs. force)
89570
109030
111260
Average
Does not comply with specified strength.
COMPRESSIVE
STRENGTH
(psi)
3170
3860
3930
3900
120470 4260
FRACTURE
TYPE
Unbonded Cap
Unbonded Cap
Unbonded Cap
Unbonded Cap
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and
reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd.
1111111 Page 2 of 6
RoneEngineers
A LEIGH COMPANY
Client: Duke Realty Services, LP
Attn: Mr. Jeff Langston
5495 Belt Line Road, Suite 360
Dallas TX 75254
Project: Freeport 10
500 Freeport Parkway
Coppell, TX
Services: Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
CONTRACTOR:
CONCRETE SUPPLIER:
PLANT:
CYLINDER
MARKED
SET NO.
3 1
3 2
3 3
3 4 5.0
Duke Realty Services, LP
Potter
On site
SPECIFICATION REQUIREMENTS
STRENGTH: 4000 psi 28 Days
SLUMP (in): 5" maximum
AIR 3% 6%
TEST METHOD: ASTM C-172
ASTM C-31
ASTM C -143
ASTM C -231
ASTM C -1064
ASTM C -138
ASTM C -39
MEASURED
SLUMP
(inches)
DATE
TESTED
5.0 07/31/2003
5.0 08/21/2003
5.0 08/21/2003
09/18/2003
CONCRETE COMPRESSIVE STRENGTH TEST
Report No.:
Project No.:
Date of Service:
Report Date:
PROJECT DATA
MIX DESIGN I.D.: 7752
PLACEMENT DATE: 07/24/2003
WEATHER CONDITIONS: Clear
TIME SAMPLED: 9:3Oam BATCH TIME:
TEMPERATURE (F) AIR 86
TRUCK NO: 102
AIR CONTENT 4.0
9:14am
F CONCRETE: 88 F
TICICET NO: 117537
UNIT WEIGHT (pcf): NA
OVERALL PLACEMENT LOCATION:
South half of north parking lot, Building Column Line Z to LL
SAMPLE LOCATION: 75' east, 15' north of southwest
comer
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12" (area 28.27 sq. in.)
AGE
(days)
7
28
28
56
MAXIMUM
LOAD
(lbs. force)
84970
104085
104195
Average
Does not comply with specified strength.
Water added at site: 5 gallons
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77040
Corporate Phone: (214) 630 -9745
COMPRESSIVE
STRENGTH
(psi)
119505 4230
191316
037333
07/24/2003
09/19/2003
3000
3680
3680
3680
FRACTURE
TYPE
Unbonded Cap
Unbonded Cap
Unbonded Cap
Unbonded Cap
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and
reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd.
OIDD Page 3 of 6
RoneEngineers
A LEIGH COMPANY
Client: Duke Realty Services, LP
Attn: Mr. Jeff Langston
5495 Belt Line Road, Suite 360
Dallas TX 75254
Project: Freeport 10
500 Freeport Parkway
Coppell, TX
Services: Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
CONTRACTOR:
CONCRETE SUPPLIER:
PLANT:
SPECIFICATION REQUIREMENTS
STRENGTH: 4000 psi 28 Days
SLUMP (in): 5" maximum
AIR( 3 -6%
TEST METHOD: ASTM C-172
ASTM C -31
CYLINDER
MARKED
SET NO.
4 1
4
4
Duke Realty Services, LP
Potter
On site
ASTM C -I43
ASTM C -231
ASTM C -1064
ASTM C -138
ASTM C -39
MEASURED
SLUMP DATE
(inches) TESTED
4.5 07/31/2003
4 2 4.5 08/21/2003
4 3 4.5 08/21/2003
4.5 09/18/2003
CONCRETE COMPRESSIVE STRENGTH TEST
Report No.:
Project No.:
Date of Service:
Report Date:
PROJECT DATA
MIX DESIGN I.D.: 7752
PLACEMENT DATE: 07/24/2003
WEATHER CONDITIONS: Clear
TIME SAMPLED: 10:15am BATCH TIME: 9:53arn
86 F CONCRETE: 89 F
TICKET NO: 117545
UNIT WEIGHT (pct): NA
TEMPERATURE (F) AIR
TRUCK NO: 102
AIR CONTENT 3.5
OVERALL PLACEMENT LOCATION:
South half of north parking lot, Building Column Line Z to LL
SAMPLE LOCATION:
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12" (area 28.27 sq. in.)
AGE
(days)
7
28
28
56
MAXIMUM
LOAD
pbs. force)
92530
108225
109375
Average
Does not comply with specified strength.
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77040
Corporate Phone: (214) 630 -9745
100' east, 10' south of northwest
comer
COMPRESSIVE
STRENGTH
(psi)
3270
3830
3870
3850
117145 4140
191316
037333
07/24/2003
09/19/2003
FRACTURE
TYPE
Unbonded Cap
Unbonded Cap
Unbonded Cap
Unbonded Cap
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and
reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd.
0111D Page 4 of 6
RoneEngineers
A LEIGH COMPANY
Client: Duke Realty Services, LP
Attn: Mr. Jeff Langston
5495 Belt Line Road, Suite 360
Dallas TX 75254
Project: Freeport 10
500 Freeport Parkway
Coppell, TX
Services: Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
CONTRACTOR: Duke Realty Services, LP
CONCRETE SUPPLIER: Potter
PLANT: On site
SPECIFICATION REQUIREMENTS
STRENGTH: 4000 psi 28 Days
SLUMP (in): 5" maximum
AIR 3% 6%
TEST METHOD: ASTM C-172
ASTM C -31
ASTM C -143
ASTM C -231
ASTM C -1064
ASTM C -138
ASTM C -39
CYLINDER
MARKED
SET NO.
5 1 5.0
5 2 5.0
5 3 5.0
5.0
5 4
MEASURED
SLUMP
(inches)
CONCRETE COMPRESSIVE STRENGTH TEST
PROJECT DATA
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12" (area 28.27 sq. in.)
DATE AGE
TESTED (days)
07/31/2003 7
08/21/2003 28
08/21/2003 28
09/18/2003 56
MIX DESIGN I.D.: 7752
PLACEMENT DATE: 07/24/2003
WEATHER CONDITIONS: Clear
TIME SAMPLED: 10:50an1 BATCH TIME: 10:32am
TEMPERATURE (F) AIR 86 F CONCRETE: 89 F
TRUCK NO: 108 TICKET NO: 1 17553
AIR CONTENT 3.8 UNIT WEIGHT (pct): NA
OVERALL PLACEMENT LOCATION:
South half of north parking lot, Building Column Line Z to LL
SAMPLE LOCATION: 150' east, 20' north of southwest
corner
MAXIMUM
LOAD
(Ibs. force)
84765
103500
103845
Average
Does not comply with specified strength.
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rotbway, Ste. 150, Houston, TX 77040
Corporate Phone: (214) 630-9745
Report No.:
Project No.:
Date of Service:
Report Date:
COMPRESSIVE
STRENGTH
(psi)
3000
3660
3670
3670
109605 3880
191316
037333
07/24/2003
09/19/2003
FRACTURE
TYPE
Unbonded Cap
Unbonded Cap
Unbonded Cap
Unbonded Cap
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and
reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd.
n1DD Page of
RoneEngineers
A LEIGH COMPANY
Client: Duke Realty Services, LP
Attn: Mr. Jeff Langston
5495 Belt Line Road, Suite 360
Dallas TX 75254
Project: Freeport 10
500 Freeport Parkway
Coppell, TX
Services: Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
CONTRACTOR: Duke Realty Services, LP
CONCRETE SUPPLIER: Potter
PLANT: On site
SPECIFICATION REQUIREMENTS
STRENGTH: 4000 psi 28 Days
SLUMP (in): 5" maximum
AIR 3% 6%
TEST METHOD: ASTM C-172
ASTM C -31
ASTM C -143
ASTM C -231
ASTM C -1064
ASTM C -138
ASTM C -39
CYLINDER
MARKED
SET NO.
6 1 5.0
6 2 5.0
6 3 5.0
6 4
MEASURED
SLUMP
(inches)
Technician: Lanny Gist
Report Distribution:
(1) Duke Realty Services, LP
(1) Duke Realty Services, LP
(1) City of Coppell Engineering Dept.
(1) Potter Concrete
DATE
TESTED
07/31/2003
08/21/2003
08/21/2003
Hold
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77040
Corporate Phone: (214) 630-9745
CONCRETE COMPRESSIVE STRENGTH TEST
Report No.:
Project No.:
Date of Service:
Report Date:
191316
037333
07/24/2003
09/19/2003
PROJECT DATA
MIX DESIGN I.D.: 7752
PLACEMENT DATE: 07/24/2003
WEATHER CONDITIONS: Clear
TIME SAMPLED: 11 BATCH TIME: 11:33am
TEMPERATURE (F) AIR 90 F CONCRETE: 90 F
TRUCK NO: 103 TICKET NO: 117564
AIR CONTENT 4.0 UNIT WEIGHT (pcf): NA
OVERALL PLACEMENT LOCATION:
South half of north parking lot, Building Column Line Z to LL
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12" (area 28.27 sq. in.)
Does not comply with specified strength.
started: 6:30am
AGE
(days)
7
28
28
(1) Pacheco Koch Consulting Engineers
(1) Engineering Analyst
(1) City of Coppell Bldg. Inspections
SAMPLE LOCATION: 200' east, 10' south of northwest
corner
Page 6 of 6
Finished: 2:30pm
MAXIMUM
LOAD
(lbs. force)
92595
112915
115150
Average
COMPRESSIVE
STRENGTH
(psi)
K. Scott Watson, AET
CMT Operations Manager
FRACTURE
TYPE
3270 Unbonded Cap
3990 Unbonded Cap
4070 Unbonded Cap
4030
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and
reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd.