Freeport NIP(7.0)-LR030912RoneEngineers
A LEIGH COMPANY
Client: Duke Realty Services, LP
Attn: Mr. Jeff Langston
5495 Belt Line Road, Suite 360
Dallas TX 75254
Project:
Services:
STRENGTH:
SLUMP (in):
AIR
TEST METHOD:
CYLINDER
MARKED
SET NO.
Freeport 10
500 Freeport Parkway
Coppell, TX
Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
CONTRACTOR: Duke Realty Services, LP
CONCRETE SUPPLIER: Potter
PLANT: On site
SPECIFICATION REQUIREMENTS
1 1 4.50
1 2 4.50
1 3 4.50
4000 psi 28 Days
3 -6%
ASTM C -172
ASTM C -31
ASTM C -143
ASTM C -231
ASTM C -1064
ASTM C -138
ASTM C -39
MEASURED
SLUMP
(inches)
DATE
TESTED
08/21/2003
09/11/2003
09/11/2003
1 4 Hold
Water added at site: 10 gallons
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12" (area 28.27 sq. in.)
AGE
(days)
7
28
28
MAXIMUM
LOAD
(Ibs. force)
117275
137685
140905
Average
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77040
Corporate Phone: (214) 630-9745
CONCRETE COMPRESSIVE STRENGTH TEST
Report No.:
Project No.:
Date of Service:
Report Date:
COMPRESSIVE
STRENGTH
(psi)
4150
4870
4980
4930
192610
037333
08/14/2003
09/12/2003
PROJECT DATA
MIX DESIGN I.D.: 7752
PLACEMENT DATE: 08/14/2003
WEATHER CONDITIONS: Clear
TIME SAMPLED: 5:35am BATCH TIME: 5:1Sam
TEMPERATURE (F) AIR 74 F CONCRETE: 86 F
TRUCK NO: 105 TICKET NO: 1 17970
AIR CONTENT 4.8 UNIT WEIGHT (pcf): NA
OVERALL PLACEMENT LOCATION:
Northwest fire lane
SAMPLE LOCATION: North drive approach at Freeport
Parkway
FRACTURE
TYPE
Unbonded Cap
Unbonded Cap
Unbonded Cap
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and
reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd.
01 Page 1 of 6
RoneEngineers
to
A LEIGH COMPANY
Client: Duke Realty Services, LP
Attn: Mr. Jeff Langston
5495 Belt Line Road, Suite 360
Dallas TX 75254
Project:
Services:
CONTRACTOR:
CONCRETE SUPPLIER:
PLANT:
SPECIFICATION REQUI
STRENGTH:
SLUMP (in):
AIR
TEST METHOD:
CYLINDER
MARKED
SET NO.
2 1
2 2
2 3
CONCRETE COMPRESSIVE STRENGTH TEST
Freeport 10
500 Freeport Parkway
Coppell, TX
Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Duke Realty Services, LP
Potter
On site
REMENTS
4000 psi 28 Days
5"
3% 6%
ASTM C -172
ASTM C -31
ASTM C -143
ASTM C -231
ASTM C -1064
ASTM C -138
ASTM C -39
MEASURED
SLUMP DATE
(inches) TESTED
4.00 08/21/2003
4.00 09/11/2003
4.00 09/11/2003
2 4 Hold
PROJECT DATA
SAMPLE LOCATION: 150' east of Freeport Parkway
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12" (area 28.27 sq. in.)
MIX DESIGN I.D.: 7752
PLACEMENT DATE: 08/14/2003
WEATHER CONDITIONS: Clear
TIME SAMPLED 7 BATCH TIME: 6:17am
TEMPERATURE (F) AIR 76 F CONCRETE 86 F
TRUCK NO: 107 TICKET NO: 117979
AIR CONTENT 4.3 UNIT WEIGHT (pcf): NA
OVERALL PLACEMENT LOCATION:
Northwest fire lane
AGE
(days)
7
28
28
MAXIMUM
LOAD
(lbs. force)
123495
140635
157985
Average
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77040
Corporate Phone: (214) 630 -9745
Report No.:
Project No.:
Date of Service:
Report Date:
COMPRESSIVE
STRENGTH
(Psi)
4370
4970
5590
5280
192610
037333
08/14/2003
09/12/2003
FRACTURE
TYPE
Unbonded Cap
Unbonded Cap
Unbonded Cap
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and
reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd.
01 Page 2 of 6
RoneEngineers
A LEIGH COMPANY
Client: Duke Realty Services, LP
Attn: Mr. Jeff Langston
5495 Belt Line Road, Suite 360
Dallas TX 75254
Project:
Services:
CONTRACTOR: Duke Realty Services, LP
CONCRETE SUPPLIER: Potter
PLANT: On site
SPECIFICATION REQUIREMENTS
STRENGTH: 4000 psi 28 Days
SLUMP (in): 5
AIR %n): 3% 6%
TEST METHOD: ASTM C -172
ASTM C -31
ASTM C -143
ASTM C -231
ASTM C -1064
ASTM C -138
ASTM C -39
CYLINDER
MARKED
SET NO.
Freeport 10
500 Freeport Parkway
Coppell, TX
Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
MEASURED
SLUMP
(inches)
DATE
TESTED
3 1 5.00 08/21/2003
3 2 5.00 09/11/2003
3 3 5.00 09/11/2003
3 4 Hold
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77040
Corporate Phone: (214) 630 -9745
CONCRETE COMPRESSIVE STRENGTH TEST
Report No.:
Project No.:
Date of Service:
Report Date:
192610
037333
08/14/2003
09/12/2003
PROJECT DATA
MIX DESIGN I.D.: 7752
PLACEMENT DATE: 08/14/2003
WEATHER CONDITIONS: Clear
TIME SAMPLED: 8:25am BATCH TIME: 7: S9am
TEMPERATURE (F) AIR 77 F CONCRETE: 86 F
TRUCK NO: 107 TICKET NO: 117989
AIR CONTENT 4.3 UNIT WEIGHT (pcf): NA
OVERALL PLACEMENT LOCATION:
Northwest fire lane
SAMPLE LOCATION: 250' east of Freeport Parkway
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12" (area 28.27 sq. in.)
AGE
(days)
7
28
28
MAXIMUM
LOAD
(lbs. force)
95090
117855
123330
Average
COMPRESSIVE
STRENGTH
(psi)
3360
4170
4360
4270
FRACTURE
TYPE
Unbonded Cap
Unbonded Cap
Unbonded Cap
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and
reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Roue Engineers, Ltd.
01 Page 3 of 6
RoneEngineers
A LEIGH COMPANY
Client: Duke Realty Services, LP
Attn: Mr. Jeff Langston
5495 Belt Line Road, Suite 360
Dallas TX 75254
Project:
Services:
CONTRACTOR:
CONCRETE SUPPLIER:
PLANT:
SPECIFICATION REQUIREMENTS
STRENGTH:
SLUMP (in):
AIR
TEST METHOD:
CYLINDER
MARKED
SET NO.
4 1
4 2
4 3
Freeport 10
500 Freeport Parkway
Coppell, TX
Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Duke Realty Services, LP
Potter
On site
4000 psi 28 Days
5
3 -6%
ASTM C -172
ASTM C -31
ASTM C -143
ASTM C -231
ASTM C -1064
ASTM C -138
ASTM C -39
MEASURED
SLUMP DATE
(inches) TESTED
4 4 5.00 10/09/2003
CONCRETE COMPRESSIVE STRENGTH TEST
PROJECT DATA
REPORT OF TESTS
SAMPLE LOCATION: 20' east, 5' north of southwest
comer
Concrete Compressive Cylinder 6" x 12" (area 28.27 sq. in.)
5.00 08/21/2003
5.00 09/11/2003
5.00 09/11/2003
Does not comply with specified strength.
Water added at site: 10 gallons
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77040
Corporate Phone: (214) 630 -9745
Report No.:
Project No.:
Date of Service:
Report Date:
MIX DESIGN I.D.: 7752
PLACEMENT DATE: 08/14/2003
WEATHER CONDITIONS: Clear
TIME SAMPLED: 9:50am BATCH TIME: 9:29am
TEMPERATURE (F) AIR 78 F CONCRETE: 86 F
TRUCK NO: 106 TICKET NO: 117999
AIR CONTENT 4.9 UNIT WEIGHT (pcf): NA
OVERALL PLACEMENT LOCATION:
North fire lane, building column Line E to P
AGE
(days)
7
28
28
56
MAXIMUM
LOAD
(Ibs. force)
87175
106510
108595
Average
COMPRESSIVE
STRENGTH
(Psi)
3080
192610
037333
08/14/2003
09/12/2003
3770
3840
3810
FRACTURE
TYPE
Unbonded Cap
Unbonded Cap
Unbonded Cap
Unbonded Cap
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and
reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd.
01 Page 4 of 6
RoneEngineers
A LEIGH COMPANY
Client: Duke Realty Services, LP
Attn: Mr. Jeff Langston
5495 Belt Line Road, Suite 360
Dallas TX 75254
Project:
Services:
STRENGTH:
SLUMP (in):
AIR
TEST METHOD:
CYLINDER
MARKED
SET NO.
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77040
Corporate Phone: (214) 630-9745
CONCRETE COMPRESSIVE STRENGTH TEST
Report No.:
Project No.:
Date of Service:
Report Date:
192610
037333
08/14/2003
09/12/2003
Freeport 10
500 Freeport Parkway
Coppell, TX
Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
CONTRACTOR: Duke Realty Services, LP
CONCRETE SUPPLIER: Potter
PLANT: On site
SPECIFICATION REQUIREMENTS
MEASURED
SLUMP
(inches)
5 1 4.00
4000 psi 28 Days
5"
3 -6%
ASTM C -172
ASTM C -31
ASTM C -143
ASTM C -231
ASTM C -1064
ASTM C -138
ASTM C -39
DATE
TESTED
08/21/2003
5 2 4.00 09/11/2003
5 3 4.00 09/11/2003
5 4 Hold
PROJECT DATA
MIX DESIGN I.D.: 7752
PLACEMENT DATE: 08/14/2003
WEATHER CONDITIONS: Clear
TIME SAMPLED: 11:OSam BATCH TIME: 10:41am
TEMPERATURE (F) AIR 80 F CONCRETE: 88 F
TRUCK NO: 107 TICKET NO: 118010
AIR CONTENT 4.2 UNIT WEIGHT (per): NA
OVERALL PLACEMENT LOCATION:
North fire lane, building column Line E to P
REPORT OF TFSTS
Concrete Compressive Cylinder 6" x 12" (area 28.27 sq. in.)
SAMPLE LOCATION: 150' west, 10' south of northeast
corner
AGE
(days)
7
28
28
MAXIMUM
LOAD
(Ibs. force)
103660
129310
128040
Average
COMPRESSIVE
STRENGTH
(Psi)
3670
4570
4530
4550
FRACTURE
TYPE
Unbonded Cap
Unbonded Cap
Unbonded Cap
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and
reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd.
01 Page 5 of 6
RoneEngineers
A LEIGH COMPANY
Client: Duke Realty Services, LP
Attn: Mr. Jeff Langston
5495 Belt Line Road, Suite 360
Dallas TX 75254
Project:
Services:
CONTRACTOR:
CONCRETE SUPP
PLANT:
SPECIFICATION
STRENGTH:
SLUMP (in):
AIR
TEST METHOD:
CYLINDER
MARKED
SET NO.
6 1
6 2
6 3
6 4
Freeport 10
500 Freeport Parkway
Coppell, TX
Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Duke Realty Services, LP
LIER• Potter
On site
REQUIREMENTS
4000 psi 28 Days
5
3 -6%
ASTM C -172
ASTM C -31
ASTM C -143
ASTM C -231
ASTM C -1064
ASTM C -138
ASTM C -39
MEASURED
SLUMP
(inches)
4.50
4.50
4.50
Technician: Lanny Gist
Report Distribution:
(I) Duke Realty Services, LP
(1) Duke Realty Services, LP
(1) City of Coppell Engineering Dept.
(1) Potter Concrete
DATE
TESTED
08/21/2003
09/11/2003
09/11/2003
Hold
CONCRETE COMPRESSIVE STRENGTH TEST
PROJECT DATA
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12" (area 28.27 sq
Started: 4:30am
(1) Pacheco Koch Consulting Engineers
(1) Engineering Analyst
(1) City of Coppell Bldg. Inspections
Report No.:
Project No.:
Date of Service:
Report Date:
MIX DESIGN I.D.: 7752
PLACEMENT DATE: 08/14/2003
WEATHER CONDITIONS: Partly cloudy
TIME SAMPLED: 12:25pm BATCH TIME: 12:09pm
TEMPERATURE (F) AIR 82 F CONCRETE: 88 F
TRUCK NO: 106 TICKET NO: 118019
AIR CONTENT 5.0 UNIT WEIGHT (pcf): NA
OVERALL PLACEMENT LOCATION:
North fire lane, building column Line E to P
SAMPLE LOCATION: 50' west, 10' south of northeast
corner
AGE
(days)
7
28
28
Finished: 2:OOpm
in.)
MAXIMUM
LOAD
(lbs. force)
103495
129200
131220
Average
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77040
Corporate Phone: (214) 630 -9745
COMPRESSIVE
STRENGTH
(Psi)
3660
4570
4640
4610
192610
037333
08/14/2003
09/12/2003
FRACTURE
TYPE
Unbonded Cap
Unbonded Cap
Unbonded Cap
K. Scott Watson, AET
CMT Operations Manager
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and
reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd.
01 Page 6 of 6