Valley R Baptist 2-LR030127FIELD DENSITY TESTING
Report Number: 94021265.0098
Service Date: January 10, 2003
lrerr�acon
8901 Carpenter Frwy, Ste #100
Dallas, Texas 75247
(214) 630 -1010
Client: Valley Ranch Baptist Church
Attn: Robert Feille
1501 East Belt Line Road
Coppell TX 75019
Material Information
Material Laboratory
No. Test Method
1.212650002 ASTM D 698
Report Date: January 27, 2003
Project: Valley Ranch Baptist Church
1501 East Belt Line Rd
Coppell, TX
Project Number: 94021265
Lab Test Data
Project Requirements
Optimum
Max. Lab
Water
Dry Unit
Water
Dry Unit
Content
Minimum Dry
Content
Weight
Range
Unit Weight
Description and Classification (%)
(pcf)
( %)
(°,v compaction)
Dk brown clay w /limestone 19.8
104.8
-1/ +3
95
Field Test Data
Probe
Water
Dry Unit
Dry Unit
Test Lift/
Mat.
Depth
Content
Weight
Weight
No. Test Location Elevation
No.
(inches)
( %)
(pcf)
°h compaction)
Grade Beam Backfill, SE corner of New
Addition
69 20'W & VS from SE corner of New 1st
1
6
21.2
102.3
98
Addition
70 20' N & 1' E from SE corner of New 1 st
1
6
22.7
101.6
97
Addition
71 20'W & V S from SE corner of New 2nd
1
6
19.6
104.5
100
Addition
72 20' N & 1' E from SE corner of New 2nd
1
6
20.4
103.2
98
Addition
Comments:
Test results on this report meet project specification.
NOTE: One Lift = 1' of backfill - Total of 4' to top of beam
Services - Perform in -place density and moisture content tests to determine degree of compaction and material
moisture
condition.
Field Test MethodASTM D2922, ASTM D3017
Gauge ID: 1614
Field Results Reported To: Contractor /Charlie Campbell
Technician: Bryan C. Hughes
Report Distribution: HBC/Terracon
(1) HKS Inc (1) City of Coppell - Bldg Insp
(1) Rogers- O'Brien Construction Co. (1) Valley Ranch Baptist Church Reviewed by �(t/
(1) Brockette Davis Drake -
H ussein H. aa P.E.
(1) City of Coppell - Constr Insp Se Project est l Ma
nager
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.