Valley R Baptist 2-LR021219CONCRETE COMPRESSIVE STRENGTH TEST FDC
Report Number: 94021265.0034 lferraean
Service Date: November 20, 2002 Dallas, carpenter 247 Ste #100
Dallas, Texas 75247
(214) 630 -1010
Client: Valley Ranch Baptist Church Report Date: December 19, 2002
Attn: Robert Feille Project: Valley Ranch Baptist Church
1501 East Belt Line Road 1501 East Belt Line Rd
Coppell TX 75019 Coppell, TX
Proiect Number: 94021265
Material Information
Specified Strength: 3000 psi @ 28 Days
Batch Time: 2:45pm Plant: 6
Supplier: 1-MC
Truck No: 831 Ticket No: 6186205
Mix I.D. No.: 853
Sample Information
Sample Time: 3:20pm Date Cast: November 20, 2002
Technician: Terry L. Smith
Weather Conditions:
Accumulative Yards: 10
Placement Method:
Sample Locations: See placement location
Placement Location: Piers
Sample location: Piers- M.2/9.6, J9/9.1,
J.9/84, J.9/6.8
Field Test Data
Test
Result
Slump, inches:
6.00
Air Content, %:
ID
Concrete Temperature, 0 F:
68
Ambient Temperature, 0 F:
63
Plastic Unit Weight, pcf:
28.27
Laboratory Test Data
2
Set
Specimen
Diameter
Area
No.
ID
(inches)
( sq. inches
1
1
6.00
28.27
1
2
6.00
28.27
1
3
6.00
28.27
1
4
6.00
28.27
Specification Test Method
ASTM C -143
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
Technician: Terry L. Smith
Report Distribution: 1,16CITerracon
(1) Rogers -O'Brien Construction Co. (1) City of Coppell - Constr Insp
(1) Brockette Davis Drake Inc (1) City of Coppell Building Inspector Reviewed by -
(1) HKS Inc
(1) Valley Ranch Baptist Church Hu em H. Abusaad, P.E.
Senior Project Manager
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.
Page 1 of 1 °'- °°' "� °'- °w• "••
ASTM C1064
ASTM C -1064
Age at Maximum
Compressive
Date
Test Load
Strength
Tested
(days) (lbs)
(psi)
11/27/2002
7 72,700
2,570
11/27/2002
7 70,620
2,500
Average
2,540
12/18/2002
28 110,390
3,900
12/18/2002
28 109,140
3,860
Average
3,880
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
Technician: Terry L. Smith
Report Distribution: 1,16CITerracon
(1) Rogers -O'Brien Construction Co. (1) City of Coppell - Constr Insp
(1) Brockette Davis Drake Inc (1) City of Coppell Building Inspector Reviewed by -
(1) HKS Inc
(1) Valley Ranch Baptist Church Hu em H. Abusaad, P.E.
Senior Project Manager
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.
Page 1 of 1 °'- °°' "� °'- °w• "••
CONCRETE COMPRESSIVE STRENGTH TEST 1r[�fIDQ
Report Number: 94021265.0037
Service Date: November 21, 2002 Dallas, Carpenter 247 Ste #100
Dallas, Texas 75247
(214) 630 -1010
Client: Valley Ranch Baptist Church Report Date: December 19, 2002
Attn: Robert Feille Project: Valley Ranch Baptist Church
1501 East Belt Line Road 1501 East Belt Line Rd
Coppell TX 75019 Coppell, TX
Proiect Number: 94021265
Material Information
Specified Strength: 4000 psi @ 28 Days
Batch Time: 6:51 am Plant:7
Supplier: LMC
Truck No: 938 Ticket No: 7121821
Mix I.D. No.: 866
Sample Information
Sample Time: 7:26am Date Cast: November 21, 2002
Technician: Terry L. Smith
Weather Conditions: Clear
Accumulative Yards: 30
Placement Method: Truck
Sample Locations: 40' S from curve (Driveway)
Placement Location: Paving, S side of building
Field Test Data
Test
Result
Specification
Test Method
Slump, inches:
4.50
3 -5
ASTM C -143
Air Content, %:
5.3
4.5 -7.5
ASTM C -231
Concrete Temperature,O F:
69
ASTM C1064
Ambient Temperature, ° F:
60
ASTM C -1064
Plastic Unit Weight, pcf:
Laboratory Test Data
Age at Maximum
Compressive
Set Specimen Diameter
Area
Date
Test Load
Strength
No. ID (inches)
( sq. inches
Tested
(days) (lbs)
(psi)
1 1 6.00
28.27
11/28/2002
7 133,980
4,740
1 2 6.00
28.27
11/28/2002
7 136,400
4,820
Average
4,780
1 3 6.00
28.27
12/19/2002
28 154,360
5,460
1 4 6.00
28.27
12/19/2002
28 157,930
5,590
Average
5,530
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.
Page 1 of 2 °' "°'a°' - '" —,
CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 94021265.0037 1 rerracon
Service Date: November 21, 2002 Dallas, Carpenter 247 Ste #100
Dallas, Tezas 75247
(214) 630 -1010
Client: Valley Ranch Baptist Church Report Date: December 19, 2002
Attn: Robert Feille Project: Valley Ranch Baptist Church
1501 East Belt Line Road 1501 East Belt Line Rd
Coppell TX 75019 Coppell, TX
Project Number: 94021265
Material Information
Specified Strength: 4000 psi @ 28 Days
Batch Time: 8:31 am Plant:7
Supplier: LMC
Truck No: 956 Ticket No: 7121832
Mix I.D. No.: 866
Field Test Data
Sample Information
Sample Time: 9:20am Date Cast: November 21, 2002
Technician: Terry L. Smith
Weather Conditions: Sunny
Accumulative Yards: 130
Placement Method: Truck
Sample Locations: E side of curve
Placement Location: See page 1
Test
Result
Specification
Test Method
Slump, inches:
5.00
3 -5
ASTM C -143
Air Content, %:
5.8
4.5 -7.5
ASTM C -231
Concrete Temperature,O F:
71
ASTM C1064
Ambient Temperature, ° F:
69
ASTM C -1064
Plastic Unit Weight, pcf:
Laboratory Test Data
Age at Maximum
Compressive
Set Specimen Diameter
Area
Date
Test Load
Strength
No. ID (inches)
( sq. inches
Tested
(days) (jbs)
(psi)
2 1 6.00
28.27
11/28/2002
7 117,620
4,160
2 2 6.00
28.27
11/28/2002
7 116,640
4,120
Average
4,140
2 3 6.00
28.27
12/19/2002
28 142,570
5,040
2 4 6.00
28.27
12/19/2002
28 136,190
4,820
Average
4, 930
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast c
strength samples.
Technician: Terry L. Smith
Report Distribution: HBC/Terracon
(1) Rogers- O'Brien Construction Co. (1) City of Coppell - Constr Insp � /f
(1) Brocketle Davis Drake Inc (1) City of Coppell Building Inspector Reviewed by 4t�f� �.
(1) HKS Inc
(1) Valley Ranch Baptist Church Hussein n H. Abusaad, P.E.
Senior Project Manager
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.
Page 2 of 2 11 11 —. ".'
CONCRETE COMPRESSIVE STRENGTH TEST lrer con
Report Number: 94021265.0036
8901 Carpenter Texas 752 wy, Ste #loo
Service Date: November 21, 2002
Dallas, Texas 75247
(214) 630 -1010
Client: Valley Ranch Baptist Church Report Date: December 19, 2002
Attn: Robert Feille Project: Valley Ranch Baptist Church
1501 East Belt Line Road 1501 East Belt Line Rd
Coppell TX 75019 Coppell, TX
Project Number: 94021265
Material Information
Specified Strength: 3000 psi @ 28 Days
Batch Time: 2:20pm Plant: 7
Supplier: LMC
Truck No: 938 Ticket No: 7121859
Mix I.D. No.: 853
Sample Information
Sample Time: 2:35pm Date Cast: November 21, 2002
Technician: Terry L. Smith
Weather Conditions:
Accumulative Yards: 10
Placement Method: Truck
Sample Locations: Piers J.1/6.3, J.1/4.4, J.9/4
Placement Location: Piers
Field Test Data
Test
Result
Specification
Test Method
Slump, inches:
5.50
ASTM C -143
Air Content, %:
Concrete Temperature, ° F:
71
ASTM C1064
Ambient Temperature, ° F:
64
ASTM C -1064
Plastic Unit Weight, pcf:
Laboratory Test Data
Age at Maximum
Compressive
Set Specimen Diameter
Area
Date
Test Load
Strength
No. ID (inches)
( sq. inches
Tested
(days) (lbs)
(psi)
1 1 6.00
28.27
11/28/2002
7 99,950
3,530
1 2 6.00
28.27
11/28/2002
7 107,710
3,810
Average
3,670
1 3 6.00
28.27
12/19/2002
28 127,920
4,520
1 4 6.00
28.27
12/19/2002
28 127,790
4,520
Average
4,520
Services - Obtain samples
of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
Technician: Terry L. Smith
Report Distribution: HBC/Terrpcon
(1) Rogers- O'Brien Construction Co. (1) City of Coppell - Constr Insp
(1)Brockette Davis Drake Inc (1) City of Coppell Building Inspector Reviewed by
(1) HKS Inc
(1) Valley Ranch Baptist Church Hussein H. jest M a P.E.
Senior Project Manager
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.
Page 1 of 1
CONCRETE COMPRESSIVE STRENGTH TEST 1f�rFD
Report Number: 94021265.0065
Service Date: December 11, 2002 Dallas, Carpenter Fnvy, Ste #100
Dallas, Texas 75247
(214) 630 -1010
Client: Valley Ranch Baptist Church Report Date: December 19, 2002
Attn: Robert Feille Project: Valley Ranch Baptist Church
1501 East Belt Line Road 1501 East Belt Line Rd
Coppell TX 75019 Coppell, TX
Proiect Number: 94021265
Material Information
Specified Strength: 4000 psi @ 28 Days
Batch Time: 9:48am Plant: 7
Supplier: LMC
Truck No: 959 Ticket No: 7122156
Mix I.D. No.: 856
Field Test Data
Test
Result
Slump, inches:
5.00
Air Content, %:
2.0
Concrete Temperature, 0 F:
59
Ambient Temperature, 0 F:
50
Plastic Unit Weight, pcf:
28.27
Laboratory Test Data
2
Set
Specimen
Diameter
Area
No.
ID
(inches)
( sq. inches
1
1
6.00
28.27
1
2
6.00
28.27
1 3
1 4
01/08/2003 28
01/08/2003 28
Comments:
NOTE: Rogers- O'Brien's superintendent was informed that Mix #856 was the wrong mix.
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.
Sample Information
Sample Time: 9:53am Date Cast: December 11, 2002
Technician: Jose A. Martinez
Weather Conditions: Cloudy
Accumulative Yards: 20
Placement Method: Pump
Sample Locations: See placement location
Placement Location: Paving, N end of jobsite
(See attached sketch)
Specification Test Method
3 -5 ASTM C -143
ASTM C -231
ASTM C1064
ASTM C -1064
Pagel of 01 L` . " LI.. ".,
Age at
Maximum
Compressive
Date
Test
Load
Strength
Tested
(days)
(lbs)
(psi)
12/18/2002
7
124,220
4,390
12/18/2002
7
123,790
4,380
Average
4,390
01/08/2003 28
01/08/2003 28
Comments:
NOTE: Rogers- O'Brien's superintendent was informed that Mix #856 was the wrong mix.
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.
Sample Information
Sample Time: 9:53am Date Cast: December 11, 2002
Technician: Jose A. Martinez
Weather Conditions: Cloudy
Accumulative Yards: 20
Placement Method: Pump
Sample Locations: See placement location
Placement Location: Paving, N end of jobsite
(See attached sketch)
Specification Test Method
3 -5 ASTM C -143
ASTM C -231
ASTM C1064
ASTM C -1064
Pagel of 01 L` . " LI.. ".,
CONCRETE COMPRESSIVE STRENGTH TEST FDC
Report Number: 94021265.0065 lferracon
Service Date: December 11, 2002 8901 Carpenter Frwy, Ste #loo
Dallas, Texas 75247
(214) 630 -1010
Client: Valley Ranch Baptist Church Report Date: December 19, 2002
Attn: Robert Feille Project: Valley Ranch Baptist Church
1501 East Belt Line Road 1501 East Belt Line Rd
Coppell TX 75019 Coppell, TX
Proiect Number: 94021265
Material Information
Specified Strength: 4000 psi @ 28 Days
Batch Time: 10:30am Plant: 7
Supplier: LMC
Truck No: 1093 Ticket No: 7122161
Mix I.D. No.: 856
Field Test Data
Test
Result
Slump, inches:
5.25
Air Content, %:
4.0
Concrete Temperature,O F:
59
Ambient Temperature, 0 F:
50
Plastic Unit Weight, pcf:
28.27
Laboratory Test Data
2
Set
Specimen
Diameter
Area
No.
ID
(inches) ( sq.
inches
2
1
6.00
28.27
2
2
6.00
28.27
2 3
2 4
01/08/2003 28
01/08/2003 28
Mix #866 was used on this set of cylinders.
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
Technician: Jose A. Martinez
Report Distribution: HBCiTefracon
(1) Rogers- O'Brien Construction Co. (1) City of Coppell - Constr Insp
(1) Brockette Davis Drake Inc (1) City of Coppell Building Inspector Reviewed by
(1) HKS Inc
(1) Valley Ranch Baptist Church Hussein H. Abusaad, P.E.
Senior Project Manager
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.
Sample Information
Sample Time: 10:40am Date Cast: December 11, 2002
Technician: Jose A. Martinez
Weather Conditions: Cloudy
Accumulative Yards: 10
Placement Method: Pump
Sample Locations: See page 1
Placement Location: See page 1
Specification
Test Method
3 -5
ASTM C -143
ASTM C -231
ASTM C1064
ASTM C -1064
Age at Maximum
Compressive
Date
Test Load
Strength
Tested
(days) (lbs)
(psi)
12/18/2002
7 125,400
4,430
12/18/2002
7 118,630
4,200
Average
4,320
Page 2 of 2 oI -IL .l Imo,, ,
PROJECT: UA //cy R4,JCA laAp j s7 6�1,ra4 Page of
JOB NO. Date 1 a� / /a Comp. By CHECKED BY:
3tl'fz�Ne
_> � _> � a
,
g'G L
5'
—ter ; - -- - - -- - - -- -- - - --
1
o m�X $y6
r
w +E
S
CONCRETE COMPRESSIVE STRENGTH TEST �-
lferracon
Report Number: 94021265.0032
Diameter
Service Date: November 20, 2002
Dallas, Carpenter 247 Ste #100
Dallas, Texas 75247
ID
(214) 630 -1010
Client: Valley Ranch Baptist Church
Report Date: December 19, 2002
Attn: Robert Feille
Project: Valley Ranch Baptist Church
1501 East Belt Line Road
1501 East Belt Line Rd
Coppell TX 75019
Coppell, TX
28.27
Project Number: 94021265
Material Information
Sample Information
Specified Strength: 4000 psi @ 28 Days
Sample Time: 7:20am Date Cast: November 20, 2002
Technician: Terry L. Smith
Batch Time: 6:51 am Plant: 7
Weather Conditions: Clear
Supplier: LMC
Accumulative Yards: 30
Truck No: 1093 Ticket No:
7121773 Placement Method: Truck
Mix I.D. No.: 866
Sample Locations: 60'W from SE corner
Placement Location: Paving - S side of building
Field Test Data
Test
Result
Specification
3 -5
4.5 -7.5
Test Method
Slump, inches:
Air Content, %:
Concrete Temperature, 0 F:
Ambient Temperature, 0 F:
Plastic Unit Weight, pcf:
Laboratory Test Data
4.50
4.8
65
51
Set
Specimen
Diameter
Area
No.
ID
(inches)
( sq. inches
1
1
6.00
28.27
1
2
6.00
28.27
ASTM C -143
ASTM C -231
ASTM C1064
ASTM C -1064
Average 4,720
1 3 6.00 28.27 12/18/2002 28 168,920 5,970
1 4 6.00 28.27 12/18/2002 28 159,200 5,630
Average 5,800
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.
Page 1 of 3 1—^ .v
Age at
Maximum
Compressive
Date
Test
Load
Strength
Tested
(days)
(lbs)
(psi)
11/27/2002
7
137,000
4,840
11/27/2002
7
130,120
4,600
Average 4,720
1 3 6.00 28.27 12/18/2002 28 168,920 5,970
1 4 6.00 28.27 12/18/2002 28 159,200 5,630
Average 5,800
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.
Page 1 of 3 1—^ .v
CONCRETE COMPRESSIVE STRENGTH TEST Irerracon
Report Number: 94021265.0032
Service Date: November 20, 2002 Dallas, Carpenter F4✓y, Ste #100
Dallas, Texas 75247
(214) 630 -1010
Client: Valley Ranch Baptist Church Report Date: December 19, 2002
Attn: Robert Feille Project: Valley Ranch Baptist Church
1501 East Belt Line Road 1501 East Belt Line Rd
Coppell TX 75019 Coppell, TX
Project Number: 94021265
Material Information
Specified Strength: 4000 psi @ 28 Days
Batch Time: 8:35am Plant: 7
Supplier: 1-MC
Truck No: 938 Ticket No: 7121783
Mix I.D. No.: 866
Field Test Data
Test
Result
Slump, inches:
5.00
Air Content, %:
5.3
Concrete Temperature, 0 F:
67
Ambient Temperature, 0 F:
58
Plastic Unit Weight, pcf:
28.27
Laboratory Test Data
2
Set
Specimen
Diameter
Area
No.
ID
(inches)
( sq. inches
2
1
6.00
28.27
2
2
6.00
28.27
Sample Information
Sample Time: 9:30am Date Cast: November 20, 2002
Technician: Terry L. Smith
Weather Conditions: Cool, clear
Accumulative Yards: 140
Placement Method: Truck
Sample Locations: 50'W, 80' N from SE corner
Placement Location: See page 1
Specification
Test Method
3 -5
ASTM C -143
4.5 -7.5
ASTM C -231
ASTM C1064
ASTM C -1064
Age at Maximum
Compressive
Date
Test Load
Strength
Tested
(days) (lbs)
(psi)
11/27/2002
7 126,700
4,480
11/27/2002
7 134,650
4,760
Average 4,620
2 3 6.00 28.27 12/18/2002 28 161,640 5,720
2 4 6.00 28.27 12/18/2002 28 160,840 5,690
Average 5,710
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.
Page 2 of 3 °' """ " ° "" "' ""
CONCRETE COMPRESSIVE STRENGTH TEST 1ferCOn
Report Number: 94021265.0032
Dallas, Carpenter 247 Ste #100
Service Date: November 20, 2002
Dallas, Texas 75247
(214) 630 -1010
Client: Valley Ranch Baptist Church Report Date: December 19, 2002
Attn: Robert Feille Project: Valley Ranch Baptist Church
1501 East Belt Line Road 1501 East Belt Line Rd
Coppell TX 75019 Coppell, TX
Project Number: 94021265
Material Information
Specified Strength: 4000 psi @ 28 Days
Batch Time: 10:40am Plant: 7
Supplier: LMC
Truck No: 964 Ticket No: 3153239
Mix I.D. No.: 866
Field Test Data
Test
Slump, inches:
Air Content, %:
Concrete Temperature,° F:
Ambient Temperature, ° F:
Plastic Unit Weight, pcf:
Laboratory Test Data
Result
5.00
5.6
69
61
Set
Specimen
Diameter
Area
No.
ID
(inches)
( sq. inches
3
1
6.00
28.27
3
2
6.00
28.27
3
3
6.00
28.27
Sample Information
Sample Time: Date Cast: November 20, 2002
Technician: Terry L. Smith
Weather Conditions: Cool, clear
Accumulative Yards: 220
Placement Method: Truck
Sample Locations: 40'W, 120' N from SE corner
Placement Location: See page 1
Specification
3 -5
4.5 -7.5
Test Method
ASTM C -143
ASTM C -231
ASTM C1064
ASTM C -1064
Age at Maximum Compressive
Date
Tested
Test
(days)
Load
(jbs)
Strength
(psi)
11/27/2002
7
103,030
3,640
11/27/2002
7
103,520
3,660
Average
3,650
12/18/2002
28
130,120
4,600
3 4 6.00 28.27 12/18/2002 28 128,340 4,540
Average 4,570
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
Technician: Terry L. Smith
Report Distribution: HBCon
(1) Rogers- O'Brien Construction Co. (1) City of Coppell - Consir Insp
(1) Brockette Davis Drake Inc (1) City of Coppell Building Inspector Reviewed by
(1) HKS Inc
(1) Valley Ranch Baptist Church Hussein .
Senior Project a Project P. E.
Manager
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.
Page 3 of 3 01 - ""' 01- F°"'""