Valley R Baptist 2-LR021213CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94021265.0031 Service Date: November 14, 2002 ��C'FDCOf1 Dall carpenter 2 4 7 Ste #100 Dallas, Texas 75247 (214) 630 -1010 Client: Valley Ranch Baptist Church Report Date: December 13, 2002 Attn: Robert Feille Project: Valley Ranch Baptist Church 1501 East Belt Line Road 1501 East Belt Line Rd Coppell TX 75019 Coppell, TX 6.00 Project Number: 94021265 Material Information Sample Information Specified Strength: 4000 psi @ 28 Days Sample Time: 7:58am Date Cast: November 14, 2002 1 Technician: Marvin R. Arandia Batch Time: 6:35am Plant: 6 Weather Conditions: Clear Supplier: LMC Accumulative Yards: 20 Truck No: 980 Ticket No: 6185694 Placement Method: Direct Discharge Mix I.D. No.: 866 Sample Locations: See placement location 4,420 Placement Location: Pavement 28 (See attached sketch) Field Test Data Test Result Specification 3 -5 4.5 -7.5 Test Method Slump, inches: Air Content, %: Concrete Temperature, F: Ambient Temperature, ° F: Plastic Unit Weight, pcf: Laboratory Test Data 5.75 3.6 63 49 Set Specimen Diameter Area No. ID (inches) ( sq. inches 1 1 6.00 28.27 1 2 6.00 28.27 1 3 6.00 28.27 1 4 6.00 28.27 ASTM C -143 ASTM C -231 ASTM C1064 ASTM C -1064 Average 4,380 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 1 of 3 01uL m01 FA. x.y Age at Maximum Compressive Date Test Load Strength Tested (days) (lbs) (psi) 11/21/2002 7 99,660 3,520 11/21/2002 7 93,120 3,290 Average 3,410 12/12/2002 28 124,900 4,420 12/12/2002 28 122,520 4,330 Average 4,380 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 1 of 3 01uL m01 FA. x.y CONCRETE COMPRESSIVE STRENGTH TEST IDC Report Number: 94021265.0031 lferracon Service Date: November 14, 2002 Dail carpenter F wy, Ste atoo Dallas, Texas 75247 (214) 630 -1010 Client: Valley Ranch Baptist Church Report Date: December 13, 2002 Attn: Robert Feille Project: Valley Ranch Baptist Church 1501 East Belt Line Road 1501 East Belt Line Rd Coppell TX 75019 Coppell, TX Project Number: 94021265 Material Information Specified Strength: 4000 psi @ 28 Days Batch Time: 8:36am Plant: 6 Supplier: LMC Truck No: 804 Ticket No: 6185717 Mix I.D. No.: 866 Field Test Data Sample Information Sample Time: 10:10am Date Cast: November 14, 2002 Technician: Marvin R. Arandia Weather Conditions: Clear Accumulative Yards: 130 Placement Method: Direct Discharge Sample Locations: See page 1 Placement Location: See page 1 Test Result Specification Test Method Slump, inches: 5.25 3 -5 ASTM C -143 Air Content, %: 4.1 4.5 -7.5 ASTM C -231 Concrete Temperature, F: 65 ASTM C1064 Ambient Temperature, ° F: ASTM C -1064 Plastic Unit Weight, pcf: Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Test Load Strength No. ID (inches) ( sq. inches Tested (days) (lbs) (psi) 2 1 6.00 28.27 11/21/2002 7 97,930 3,460 2 2 6.00 28.27 11/21/2002 7 95,870 3,390 Average 3,430 2 3 6.00 28.27 12/12/2002 28 115,600 4,090 2 4 6.00 28.27 12/12/2002 28 118,830 4,200 Average 4,150 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 2 of 3 01 LLLW 01 P' W K.� CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94021265.0031 Service Date: November 14, 2002 FDQ lferraeon 8901 carpenter Fnwy, Ste #100 Dallas, Texas 75247 (2 63 0 -1010 Client: Valley Ranch Baptist Church Report Date: December 13, 2002 Attn: Robert Feille Project: Valley Ranch Baptist Church 1501 East Belt Line Road 1501 East Belt Line Rd Coppell TX 75019 Coppell, TX 6.00 Project Number: 9 4021265 Material Information Sample Information Specified Strength: 4000 psi @ 28 Days Sample Time: 12:35pm Date Cast: November 14, 2002 3 Technician: Marvin R. Arandia Batch Time: 11:03am Plant: 6 Weather Conditions: Clear Supplier: LMC Accumulative Yards: 210 Truck No: 982 Ticket No: 6185746 Placement Method: Direct Discharge Mix I.D. No.: 866 Sample Locations: See page 1 Placement Location: See page 1 Field Test Data Test Result Specification 3 -5 4.5 -7.5 Test Method Slump, inches: Air Content, %: Concrete Temperature,O F: Ambient Temperature, 0 F: Plastic Unit Weight, pcf: Laboratory Test Data 5.50 4.1 65 70 Set Specimen Diameter Area No. ID (inches) ( sq. inches 3 1 6.00 28.27 3 2 6.00 28.27 3 3 6.00 28.27 3 4 6.00 28.27 ASTM C -143 ASTM C -231 ASTM C1064 ASTM C -1064 Date Tested Age at Test (days) Maximum Compressive Load Strength (lbs) (psi) 11/21/2002 7 87,840 3,110 11/21/2002 7 90,180 3,190 Average 3,150 12/12/2002 28 121,010 4,280 12/12/2002 28 117,570 4,160 Average 4,220 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Technician: Marvin R. Arandia Report Distribution: HBC/Terracon (1) Rogers- O'Brien Construction Co. (1) City of Coppell - Constr Insp (1) Brockefte Davis Drake Inc (1) City of Coppell Building Inspector Reviewed by (1) HKS Inc Husse n H. Abusaad, P.E. (1) Valley Ranch Baptist Church Senior Project Manager The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 3 of 3 0 1-LL�°°IFw k ^v rerracon PROJECT: JOB NO. G1%A 17-6S. 1 Date -Comp. By %.or, Page of CHECKED BY: T Form 112 -5 -93 FIELD DENSITY TESTING F- Report Number: 94021265.0064 lrerracon Service Date: December 10, 2002 Dallas, Carpenter 247 Ste #100 Dallas, Texas 75247 (214) 630 -1010 Client: Valley Ranch Baptist Church Report Date: December 13, 2002 Attn: Robert Feille Project: Valley Ranch Baptist Church 1501 East Belt Line Road 1501 East Belt Line Rd Coppell TX 75019 Coppell, TX Project Number: 94021265 Material Information Material Laboratory No. Test Method 1. 212650005 ASTM D 698 Description and Classification Med brown clay w /sand Field Test Data Test No. Test Location Paving /Parking @ NE Corner of Project 67 20' S & 15'W from NE corner of paving 68 40' S & 40'W from NE corner of paving Lab Test Data Optimum Max. Lab Water Dry Unit Content Weight ( %) (pcf) fE:tYiGk�1 Project Reouirements Water Content Minimum Dry Range Unit Weight ( %) (% compaction) 6ICE«:1.7 Probe Water Dry Unit Dry Unit Lift/ Mat. Depth Content Weight Weight Elevation No. (inches) ( %) (pcf) (% compaction) Final 1 8 20.2 99.9 96 Final 1 8 20.5 99.2 95 Comments: Test results on this report meet project specification. Services - Perform in -place density and moisture content tests to determine degree of compaction and material moisture condition. Field Test MethodASTM D2922, ASTM D3017 Gauge ID: 1614 Field Results Reported To: Contractor's Supt Technician: Bryan C. Hughes Report Distribution (1) Rogers- O'Brien Construction Co. (1) City of Coppell - Constr Insp (1) Brockefte Davis Drake Inc (1) City of Coppell Building Inspector (1) HKS Inc (1) Valley Ranch Baptist Church HBC Terracon Reviewed by: Husseirf H. Abusaad, P.E. Senior Project Manager The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page i of i .1. Lwv,a,.rw,. s.. rONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94021265.0054 Service Date: December 2, 2002 1 �� Dallas, Carpenter Fnvy, Ste #100 Dallas, Texas 75247 (214) 630 -1010 Client: Valley Ranch Baptist Church Report Date: December 13, 2002 Attn: Robert Feille Project: Valley Ranch Baptist Church 1501 East Belt Line Road 1501 East Belt Line Rd Coppell TX 75019 Coppell, TX ASTM C -1064 Project Number: 94021265 Material Information Sample Information Specified Strength: 3000 psi @ 28 Days Sample Time: 11:20am Date Cast: December 2, 2002 Test Load Technician: Terry L. Smith Batch Time: 11:02am Plant: 3 Weather Conditions: Clear, mild Supplier: LMC Accumulative Yards: 10 Truck No: 1049 Ticket No: 3153619 Placement Method: Truck Discharge Mix I.D. No.: 853 Sample Locations: Piers F /11, F /10 2,960 Placement Location: Piers Field Test Data Test Slump, inches: Air Content, %: Concrete Temperature,° F: Ambient Temperature, 0 F: Plastic Unit Weight, pcf: Laboratory Test Data Result 5.50 62 54 Specification Test Method Diameter 3 -5 ASTM C -143 ID (inches) ( sq. ASTM C -1064 1 1 ASTM C -1064 28.27 1 Age at Maximum Compressive Date Test Load Strength Tested (days) (lbs) (psi) 12/09/2002 7 85,330 3,020 12/09/2002 7 83,800 2,960 Average 2,990 Set Specimen Diameter Area No. ID (inches) ( sq. inches 1 1 6.00 28.27 1 2 6.00 28.27 1 3 1 4 12/30/2002 28 12/30/2002 28 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 1 of 2 01 LL " 01 F " l V" CONCRETE COMPRESSIVE STRENGTH TEST lrerracon Report Number: 94021265.0054 Specification Service Date: December 2, 2002 6901 carpenter Frwy, Ste #100 Slump, inches: Dallas, Texas 75247 3 -5 (214) 630 -1010 Client: Valley Ranch Baptist Church Report Date: December 13, 2002 Attn: Robert Feille Project: Valley Ranch Baptist Church 1501 East Belt Line Road 1501 East Belt Line Rd Coppell TX 75019 Coppell, TX Project Number: 94021265 Material Information Sample Information Specified Strength: 3000 psi @ 28 Days Sample Time: 5:23pm Date Cast: December 2, 2002 ASTM C -1064 Technician: Terry L. Smith Batch Time: 5:00pm Plant: 3 Weather Conditions: Clear, mild Supplier: 1-MC Accumulative Yards: 10 Truck No: 947 Ticket No: 7122064 Placement Method: Truck Discharge Mix I.D. No.: 853 Sample Locations: Piers F/6.5, F.7/7, C/8 Placement Location: See page 1 Field Test Data Test Result Specification Test Method Slump, inches: 5.00 3 -5 ASTM C -143 Air Content, %: Concrete Temperature,o F: 64 ASTM C -1064 Ambient Temperature, 0 F: 62 ASTM C -1064 Plastic Unit Weight, pcf: Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Test Load Strength No. ID (inches) ( sq. inches Tested (days) (lbs) (psi) 2 1 6.00 28.27 12/09/2002 7 102,190 3,610 2 2 6.00 28.27 12/09/2002 7 99,400 3,520 Average 3,570 2 3 12/30/2002 28 2 4 12/30/2002 28 Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Technician: Terry L. Smith Report Distribution: HBC/Terracon (1) Rogers- O'Brien Construction Co. (1) City of Coppell - Constr Insp (1) Brockefle Davis Drake Inc (1) City of Coppell Building Inspector Reviewed by (1) HKS Inc (1) Valley Ranch Baptist Church Hussein H. Abusaad, P.E. Senior Project Manager The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 2 of 2 rrw�o�- FAN•••.