Valley R Baptist 2-LR020819FIELD DENSITY TESTING 1r
Y,N(T(NEEROVG
Report Number: 94021265.0011 8901 Carpenter Frwy., Suite #100
Service Date: August 9, 2002 Dallas, Texas 75247
(214) 630 -1010
Client: Valley Ranch Baptist Church Report Date: August 19, 2002
Attn: Robert Feille Project: Valley Ranch Baptist Church
1501 East Belt Line Road 1501 East Belt Line Rd
Coppell TX 75019 Coppell, TX
Project Number: 94021265
Material Information
Lab Test Data
Project Requirements
Optimum
Max. Lab
Water
Water
Dry Unit
Content
Minimum Dry
Content
Weight
Range
Unit Weight
Material Laboratory
Test Method
Description and Classification
P
( %)
(pcf)
( %)
(% compaction)
No.
1.212650002 ASTM D 698
Dk brown clay w /limestone
19.8
104.8
-1/ +3
95
Field Test Data
Probe
Water
Dry Unit
Dry Unit
Lift/ Mat. Depth
Content
Weight
Weight
Test
No. Test Locati Elevation No. (inches)
N
(pcf)
(% compactio
Water Line Backfill, Water Line Running
EtoW
27 At N end of S parking lot, 60' S & 40' E 2' BEG 1 6 21.6 100.9 96
from SE corner of existing building
28 At N end of S parking lot, 90'S & 90' E 2' BEG 1 6 22.0 100.0 95
from SE corner of existing building
29 At N end of S parking lot, 90' S & 150' E 2' BEG 1 6 21.4 101.6 97
from SE corner of existing building
Datum: BEG = below existing grade
Comments:
Test results on this report meet project specification.
Services - Perform in -place density and moisture content tests to determine degree of compaction and material moisture
condition.
Field Test Method D2922, ASTM D3017
Gauge ID: 2077
Field Results Reported To: Contractor's Superintendent
Technician: Bryan C. Hughes
Report Distribution: HBC Engineering
(1) Rogers- O'Brien Construction Co. () y Coppell tr p ector Reviewed b
(1) Brockette Davis Drake Inc (1) City of Coppell Building I ns
g P y
(1) HKS Inc Hussein Ff. Abusaad, P.E.
(1) Valley Ranch Baptist Church Senior Project Manager
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.
Page 1 of i