Valley R Plaza 2B-LR030925CONCRETE COMPRESSIVE STRENGTH TEST lferrr con
Report Number: 94031170.0065 8901 Carpenter Frwy, Ste #100
Service Date: August 26, 2003 Dallas, Texas 75247
(214) 630 -1010
Client: Phase II BLMA Limited
Report Date: September 25, 2003
Attn: Tad Weatherford Project: Valley Ranch Plaza Phase II
5950 Berkshire Ln Ste 410 817 South MacArthur Blvd
Dallas TX 75225 Coppell, TX
Material Information
Specified Strength: 3000 psi @ 28 Days
Batch Time: 6:26am Plant: 89
Supplier: Beall
Truck No: 213
Mix I.D. No.: 23011524
Water Added Onsite Before Test:
Water Added Onsite After Test:
Field Test Data
Test
Slump, inches:
Air Content, %:
Concrete Temperature, F:
Ambient Temperature, 0 F:
Plastic Unit Weight, pcf:
Laboratory Test Data
Project Number: 940
Sample Information
Sample Time: 6:40am Date Cast: August 26, 2003
Technician: Joseph B. Gordon
Weather Conditions: Clear
Accumulative Yards: 30
Ticket No: 89029986 Placement Method: Direct Discharge
Sample Locations: 15' W of NE corner & N of S
5 Gallons Placement Location: Sidewalk from NE corner of bldg. to NW
0 Gallons corner & NE corner to SE corner
Sampled from truck.
Result Specification Test Method
5.25 3 -5 ASTM C -143
4.8 3 -6 ASTM C -231
86 ASTM C -1064
80 ASTM C -1064
Age at Maximum Compressive
Set
Specimen
Diameter
Area
No.
ID
(inches) ( sq.
inches
1
1
6.00
28.27
1
2
6.00
28.27
1
3
6.00
28.27
1
4
6.00
28.27
Date
Test Load
Strength
Tested
(days) (lbs)
(psi)
09/02/2003
7 79,910
2,830
09/02/2003
7 75,120
2,660
Average
2,750
09/23/2003
28 99,130
3,510
09/23/2003
28 98,100
3,470
Average
3,490
Comments: Not tested for plastic unit weight.
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
Technician: Joseph B. Gordon r n
ric J. Cleveland, P.E.
Report Distribution
(1) Phase II BLMA Limited Reviewed by
(1) City of Coppell TX
(1) City of Coppell TX
(1) Mycon General Contractors Senior Project Engineer
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.
Page 1 of 1