Valley R Plaza 2B-LR030807CONCRETE COMPRESSIVE STRENGTH TEST lrerf con
Report Number: 94031170.0048 8901 Carpenter Fnvy, Ste #100
Service Date: July 9, 2003 Dallas, Texas 75247
(214) 630 -1010
Client: Phase II BLMA Limited Report Date: August 07, 2003
Attn: Tad Weatherford Project: Valley Ranch Plaza Phase II
5950 Berkshire Ln Ste 410 817 South MacArthur Blvd
Dallas TX 75225 Coppell, TX
Number: 94031170
Material Information
Specified Strength: 4000 psi @ 28 Days
Batch Time: 1:48pm Plant: 1
Supplier: Redi -Mix
Truck No: 223 Ticket No: 112222
Mix I.D. No.: 732
Field Test Data
Test
Result
Slump, inches:
5.25
Air Content, %:
4.9
Concrete Temperature, ° F:
89
Ambient Temperature, ° F:
92
Plastic Unit Weight, pcf:
28.27
Laboratory Test Data
2
Set
Specimen
Diameter
Area
No.
ID
(inches)
( sq. inches
1
1
6.00
28.27
1
2
6.00
28.27
1
3
6.00
28.27
1
4
6.00
28.27
Sample Information
Sample Time: 2:50pm Date Cast: July 9, 2003
Technician: Eddie A. Elrod
Weather Conditions: Partly cloudy
Accumulative Yards: 5
Placement Method: Direct Discharge
Sample Locations: 24'W & 5'S of SW building corner
Placement Location: Paving
fire lane replaced section
Specification Test Method
ASTM C -143
ASTM C -231
ASTM C -1064
ASTM C -1064
Date
Tested
Age at Maximum
Test Load
(days) (lbs)
Compressive
Strength
(psi)
07/16/2003
7 105,420
3,730
07/16/2003
7 110,470
3,910
Average
3,820
08/06/2003
28 133,140
4,710
08/06/2003
28 141,630
5,010
Average
4,860
Comments: Not tested for plastic unit weight.
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
Technician: Eddie A. Elrod
Report Distribution: err con
(1) Phase II BLMA Limited
(1) City of Coppell TX Reviewed by:
(1) City of Coppell TX is . Cleveland, P.E.
(1) Mycon General Contractors
for Project Engineer
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.
Page 1 of 1