Valley R Plaza 2B-LR030807CONCRETE COMPRESSIVE STRENGTH TEST lrerf con Report Number: 94031170.0048 8901 Carpenter Fnvy, Ste #100 Service Date: July 9, 2003 Dallas, Texas 75247 (214) 630 -1010 Client: Phase II BLMA Limited Report Date: August 07, 2003 Attn: Tad Weatherford Project: Valley Ranch Plaza Phase II 5950 Berkshire Ln Ste 410 817 South MacArthur Blvd Dallas TX 75225 Coppell, TX Number: 94031170 Material Information Specified Strength: 4000 psi @ 28 Days Batch Time: 1:48pm Plant: 1 Supplier: Redi -Mix Truck No: 223 Ticket No: 112222 Mix I.D. No.: 732 Field Test Data Test Result Slump, inches: 5.25 Air Content, %: 4.9 Concrete Temperature, ° F: 89 Ambient Temperature, ° F: 92 Plastic Unit Weight, pcf: 28.27 Laboratory Test Data 2 Set Specimen Diameter Area No. ID (inches) ( sq. inches 1 1 6.00 28.27 1 2 6.00 28.27 1 3 6.00 28.27 1 4 6.00 28.27 Sample Information Sample Time: 2:50pm Date Cast: July 9, 2003 Technician: Eddie A. Elrod Weather Conditions: Partly cloudy Accumulative Yards: 5 Placement Method: Direct Discharge Sample Locations: 24'W & 5'S of SW building corner Placement Location: Paving fire lane replaced section Specification Test Method ASTM C -143 ASTM C -231 ASTM C -1064 ASTM C -1064 Date Tested Age at Maximum Test Load (days) (lbs) Compressive Strength (psi) 07/16/2003 7 105,420 3,730 07/16/2003 7 110,470 3,910 Average 3,820 08/06/2003 28 133,140 4,710 08/06/2003 28 141,630 5,010 Average 4,860 Comments: Not tested for plastic unit weight. Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Technician: Eddie A. Elrod Report Distribution: err con (1) Phase II BLMA Limited (1) City of Coppell TX Reviewed by: (1) City of Coppell TX is . Cleveland, P.E. (1) Mycon General Contractors for Project Engineer The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 1 of 1