Valley R Plaza 2B-LR030731CONCRETE COMPRESSIVE STRENGTH TEST IDC
Report Number: 5 1(erraeon
Service Date: Jul 3, 2003 8901 Carpenter Frwy, Ste #100
Y Dallas, Texas 75247
(214) 630 -1010
Client: Phase II BLMA Limited Report Date: July 31, 2003
Attn: Tad Weatherford Project: Valley Ranch Plaza Phase II
5950 Berkshire Ln Ste 410 817 South MacArthur Blvd
Dallas TX 75225 Coppell, TX
Number: 94031170
Specified Strength: 4000 psi @ 28 Days
Batch Time: 12:30pm Plant: 1
Supplier: Redi -Mix
Truck No: 111 Ticket No: 112045
Mix I.D. No.: 732
Water Added Onsite Before Test: 10 Gallons
Field Test Data
Test
Slump, inches:
Air Content, %:
Concrete Temperature,O F:
Ambient Temperature, 0 F
Plastic Unit Weight, pcf:
Laboratory Test Data
Sample Information
Sample Time: 2:00pm Date Cast: July 3, 2003
Technician: Wesley A. Lawson
Weather Conditions: Sunny
Accumulative Yards: 5
Placement Method: Direct Discharge
Sample Locations: See placement location
Placement Location: Paving
See attached sketch
Result Specification
5.00
4.5
102
91
Set
Specimen
Diameter
Area
No.
ID
(inches)
( sq. inches
1
1
6.00
28.27
1
2
6.00
28.27
1
3
6.00
28.27
1
4
6.00
28.27
Date
Tested
07/10/2003
07/10/2003
Test Method
ASTM C -143
ASTM C -231
ASTM C -1064
ASTM C -1064
Age at
Maximum
Compressive
Test
Load
Strength
(days)
(lbs)
(psi)
7
98,550
3,480
7
101.560
3,590
Average
07/31/2003 28 121,880
07/31/2003 28 123,570
Average
3,540
4,310
4,370
Comments: Not tested for plastic unit weight.
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
Technician: Wesley A. Lawson
Report Distribution: / A;rdr /gcon
(1) Phase II 31-MA Limited
(1) City of Coppell TX Reviewed by:
(1) City of Coppell TX
(1) Mycon General Contractors Senior r Cleveland, P.E.
or Project Engineer
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.
Page 1 of 1 o,.uwao''F . ".v