Valley R Plaza 2B-LR030620CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 94031-17Z-0013
Service Service Date: /May 23, 2003 )
lt'errrrrrrr con
8901 Carpenter Frwy, Ste #100
Dallas, Texas 75247
(214) 630 -1010
Client: Phase II BLMA Limited
Attn: Tad Weatherford
5950 Berkshire Ln Ste 410
Dallas TX 75225
Report Date: June 20, 2003
Project: Valley Ranch Plaza Phase II
817 South MacArthur Blvd
Coppell, TX
Project Number: 9403
Material Information
Sample Information
Specified Strength: 4500 psi @ 28 Days
Sample Time: 11:25am Date Cast: May 23, 2003
Technician: Joseph B. Gordon
Batch Time: 10:52am Plant:
10
Weather Conditions: Clear
Supplier: Redi -Mix
Accumulative Yards: 3
Truck No: 135
Ticket No:
1008221 Placement Method: Direct Discharge
Mix I.D. No.: 732
Sample Locations: See placement location
Placement Location: Inlet, NE corner of jobsite
Field Test Data
Test
Result
Specification Test Method
Slump, inches:
3.25
ASTM C -143
Air Content, %:
4.2
ASTM C -231
Concrete Temperature,O F:
73
ASTM C -1064
Ambient Temperature, 0 F:
77
ASTM C -1064
Plastic Unit Weight, pcf:
Laboratory Test Data
Age at Maximum Compressive
Set Specimen Diameter
Area
Date Test Load Strength
No. ID (inches) ( sq.
inches
Tested (days) (Ibs) (psi)
1 1 6.00
28.27
05/30/2003 7 131,580 4,650
1 2 6.00
28.27
05/30/2003 7 133,960 4,740
Average 4,700
1 3 6.00
28.27
06/20/2003 28 168,590 5,960
1 4 6.00
28.27
06/20/2003 28 167,510 5,920
Average 5,940
Comments: Not tested for plastic unit weight.
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
Technician: Joseph B. Gordon
Report Distribution:
(1) Phase II BLMA Limited
(1) City of Coppell TX Reviewed by:
(1) City of Coppell TX
Eric J. Cleveland, P.E.
Senior Project Engineer
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.
Page 1 of 1 u,- u.cm- .w,,..,