Valley R Plaza 2B-LR030620CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94031-17Z-0013 Service Service Date: /May 23, 2003 ) lt'errrrrrrr con 8901 Carpenter Frwy, Ste #100 Dallas, Texas 75247 (214) 630 -1010 Client: Phase II BLMA Limited Attn: Tad Weatherford 5950 Berkshire Ln Ste 410 Dallas TX 75225 Report Date: June 20, 2003 Project: Valley Ranch Plaza Phase II 817 South MacArthur Blvd Coppell, TX Project Number: 9403 Material Information Sample Information Specified Strength: 4500 psi @ 28 Days Sample Time: 11:25am Date Cast: May 23, 2003 Technician: Joseph B. Gordon Batch Time: 10:52am Plant: 10 Weather Conditions: Clear Supplier: Redi -Mix Accumulative Yards: 3 Truck No: 135 Ticket No: 1008221 Placement Method: Direct Discharge Mix I.D. No.: 732 Sample Locations: See placement location Placement Location: Inlet, NE corner of jobsite Field Test Data Test Result Specification Test Method Slump, inches: 3.25 ASTM C -143 Air Content, %: 4.2 ASTM C -231 Concrete Temperature,O F: 73 ASTM C -1064 Ambient Temperature, 0 F: 77 ASTM C -1064 Plastic Unit Weight, pcf: Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Test Load Strength No. ID (inches) ( sq. inches Tested (days) (Ibs) (psi) 1 1 6.00 28.27 05/30/2003 7 131,580 4,650 1 2 6.00 28.27 05/30/2003 7 133,960 4,740 Average 4,700 1 3 6.00 28.27 06/20/2003 28 168,590 5,960 1 4 6.00 28.27 06/20/2003 28 167,510 5,920 Average 5,940 Comments: Not tested for plastic unit weight. Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Technician: Joseph B. Gordon Report Distribution: (1) Phase II BLMA Limited (1) City of Coppell TX Reviewed by: (1) City of Coppell TX Eric J. Cleveland, P.E. Senior Project Engineer The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials. Page 1 of 1 u,- u.cm- .w,,..,