Freeport NIP(7.0)-LR031010RoneEngineers Client: Duke Realty Services, LP Attn: Mr. Jeff Langston 5495 Belt Line Road, Suite 360 Dallas TX 75254 Project: Services: CONTRACTOR: CONCRETE SUPPLIER: PLANT: SPECIFICATION REQUIREMENTS STRENGTH: SLUMP (in): AIR TEST METHOD: CYLINDER MARKED SET NO. 1 1 1 2 1 3 Freeport 10 500 Freeport Parkway Coppell, TX Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. Duke Realty Services, LP Potter On site 4000 psi 28 Days 5" 3% 6% ASTM C -172 ASTM C -31 ASTM C -143 ASTM C -231 ASTM C -1064 ASTM C -138 ASTM C -39 MEASURED SLUMP (inches) 4.50 4.50 4.50 Concrete Compressive Cylinder 6" x 12" (area 28.27 sq. in.) DATE TESTED 08/21/2003 09/11/2003 09/11/2003 1 4 Hold Water added at site: 10 gallons CONCRETE COMPRESSIVE STRENGTH TEST REPORT OF TESTS AGE (days) 7 28 28 MAXIMUM LOAD (lbs. force) 117275 137685 140905 Average 8908 Ambassador Row, Dallas, TX 75247 2696 Gravel Drive, Fort Worth, TX 76118 6300 Rothway, Ste. 150, Houston, TX 77040 Corporate Phone: (214) 630 -9745 Report No.: Project No.: Date of Service: Report Date: PROJECT DATA MIX DESIGN I.D.: 7752 PLACEMENT DATE: 08/14/2003 WEATHER CONDITIONS: Clear TIME SAMPLED: 5:35am BATCH TIME: 5:1 Sam TEMPERATURE (F) AIR 74 F CONCRETE: 86 F TRUCK NO: 105 TICKET NO: 117970 AIR CONTENT 4.8 UNIT WEIGHT (pcf): NA OVERALL PLACEMENT LOCATION: Northwest fire lane SAMPLE LOCATION: North drive approach at Freeport Parkway COMPRESSIVE STRENGTH (psi) 4150 4870 4980 4930 192610 037333 08/14/2003 10/10/2003 FRACTURE TYPE Unbonded Cap Unbonded Cap Unbonded Cap LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd. DI Page 1 of 6 2 Ro= gineers sem Client: Duke Realty Services, LP Attn: Mr. Jeff Langston 5495 Belt Line Road, Suite 360 Dallas TX 75254 Project: Services: CONTRACTOR: CONCRETE SUPPLIER: PLANT: Freeport 10 500 Freeport Parkway Coppell, TX Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive stren gth samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. Duke Realty Services, LP Potter On site SPECIFICATION REQUIREMENTS STRENGTH: 4000 psi 28 Days 5" 3 -6% ASTM C -172 ASTM C -31 ASTM C -143 ASTM C -231 ASTM C -1064 ASTM C -138 ASTM C -39 SLUMP (in): AIR TEST METHOD: CYLINDER MARKED SET NO. 2 1 2 2 2 3 4 MEASURED SLUMP (inches) 4.00 09/11/2003 4.00 09/11/2003 Concrete Compressive Cylinder 6" x 12" (area 28.27 sq. in.) DATE TESTED 4.00 08/21/2003 Hold 8908 2696 Gravel Ambassador ive, Fo t Wo TX 76118 6300 Rothway, Ste. 150, Houston, TX 77040 Corporate Phone: (214) 630 -9745 CONCRETE COMPRESSIVE STRENGTH TEST PROJECT DATA MIX DESIGN LD.: 7752 PLACEMENT DATE: 08/14/2003 WEATHER CONDITIONS: Clear TIME SAMPLED: 7 :4Oam BATCH TIME: 6 :17 TEMPERATURE (F) AIR 76 F CONCRETE: 86 F TRUCK NO: 107 TICKET NO: 1 17979 AIR CONTENT nu 4. 3 OVERALL PLACEMENT LOCATION: IT WEIGHT (pct); NA Northwest fire lane SAMPLE LOCATION: 150' east of Freeport Parkway AGE (days) 28 28 MAXIMUM LOAD (Ibs, force) 7 123495 140635 157985 Avera Report No.: Project No.: Date of Service: Report Date: COMPRESSIVE STRENGTH (psi) 4370 192610 037333 08/14/2003 10/10/2003 FRACTURE TYPE Unbonded Cap Unbonded Cap Unbonded Cap ITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing We rosition appearance, performance, etc.) or an y other feature of similar subject matter provided by persons or conditions have over which we ha no controlits are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd. assume responsibility variation Our leers d Page 2 of 6 Ro =gin Client: Duke Realty Services, LP Attn: Mr. Jeff Langston 5495 Belt Line Road, Suite 360 Dallas TX 75254 CONCRETE COMPRESSIVE STRENGTH TEST Project: Freeport 10 500 Freeport Parkway Coppell, TX Services: Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. CONTRACTOR: Duke Realty Services, LP CONCRETE SUPPLIER: Potter PLANT: On site SPECIFICATION REQUIREMENTS STRENGTH: SLUMP (in): AIR TEST METHOD: CYLINDER MARKED SET NO. 3 1 3 2 3 3 4000 psi 28 Days 5" 3% 6% ASTM C -172 ASTM C -31 ASTM C -143 ASTM C -231 ASTM C -1064 ASTM C -138 ASTM C -39 MEASURED SLUMP (inches) 5.00 5.00 5.00 DATE TESTED 08/21/2003 09/11/2003 09/11/2003 3 4 Hold PROJECT DATA MIX DESIGN I.D.: 7752 PLACEMENT DATE: 08/14/2003 R FATHER CONDITIONS: TIME SAMPLED• 825am TEMPERATURE (F) AIR 77 TRUCK NO: 107 AIR CONTENT 4.3 OVERALL PLACEMENT LOCATION: Northwest fire lane SAMPLE LOCATION: REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" (area 28.27 sq. in.) AGE (days) 7 28 28 MAXIMUM LOAD (Ibs. force) 95090 117855 123330 Average 8908 Ambassador Row, Dallas, TX 75247 2696 Gravel Drive, Fort Worth, TX 76118 6300 Rothway, Ste. 150, Houston, TX 77040 Corporate Phone: (214) 630 -9745 Report No.: Project No.: Date of Service: Report Date: 192610 037333 08/14/2003 10/10/2003 Clear BATCH TIME: 7:59am F CONCRETE: 86 F TICKET NO: 1 17989 UNIT WEIGHT (pcf): NA 250' east of Freeport Parkway COMPRESSIVE STRENGTH (Psi) 3360 4170 4360 4270 FRACTURE TYPE Unbonded Cap Unbonded Cap Unbonded Cap LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd. 01 Page 3 of 6 RoneEngineers Client: Duke Realty Services, LP Attn: Mr. Jeff Langston 5495 Belt Line Road, Suite 360 Dallas TX 75254 Project: Freeport 10 500 Freeport Parkway Coppell, TX Services: Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. CONTRACTOR: CONCRETE SUPPLIER: PLANT: SPECIFICATION REQUIREMENTS STRENGTH: SLUMP (in): AIR TEST METHOD: CYLINDER MARKED SET NO. 4 1 5.00 4 2 5.00 4 3 5.00 4 4 5.00 Duke Realty Services, LP Potter On site 4000 psi 28 Days 5" ASTM C -172 ASTM C -31 ASTM C -143 ASTM C -231 ASTM C -1064 ASTM C -138 ASTM C -39 MEASURED SLUMP (inches) CONCRETE COMPRESSIVE STRENGTH TEST PROJECT DATA REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" (area 28.27 sq. in.) DATE AGE TESTED (days) 08/21/2003 7 09/11/2003 28 09/11/2003 28 10/09/2003 56 OVERALL PLACEMENT LOCATION: North fire lane, building column Line E to P SAMPLE LOCATION: 20' east, 5' north of southwest comer MAXIMUM LOAD (lbs. force) Does not comply with specified strength. Water added at site: 10 gallons 87175 3080 106510 108595 Average 119295 4220 8908 Ambassador Row, Dallas, TX 75247 2696 Gravel Drive, Fort Worth, TX 76118 6300 Rothway, Ste. 150, Houston, TX 77040 Corporate Phone: (214) 630 -9745 Report No.: Project No.: Date of Service: Report Date: COMPRESSIVE STRENGTH (psi) 3770 3840 3810 192610 037333 08/14/2003 10/10/2003 MIX DESIGN I.D.: 7752 PLACEMENT DATE: 08/14/2003 WEATHER CONDITIONS: Clear TIME SAMPLED: 9:50am BATCH TIME: 9:29am TEMPERATURE (F) AIR 78 F CONCRETE: 86 F TRUCK NO: 106 TICKET NO: 117999 3% 6% AIR CONTENT 4.9 UNIT WEIGHT (pcf): NA FRACTURE TYPE Unbonded Cap Unbonded Cap Unbonded Cap Unbonded Cap LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd. 01 Page 4 of 6 Ro =gin Client: Duke Realty Services, LP Attn: Mr. Jeff Langston 5495 Belt Line Road, Suite 360 Dallas TX 75254 Project: Services: CONTRACTOR: CONCRETE SLTPLIER: PLANT: SPECIFICATION REQUIREMENTS STRENGTH: SLUMP (in): AIR TEST METHOD: CYLINDER MARKED SET NO. 5 5 1 5 2 3 Freeport 10 500 Freeport Parkway Coppell, TX Obtain samples of fresh concrete at the placement locations, perform required field testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. Duke Realty Services, LP Potter On site 4000 psi 28 Days 5" 3% 6% AIR CONTENT 4.2 UNIT WEIGHT (pet): NA ASTM C -172 ASTM C -31 ASTM C -143 ASTM C -231 ASTM C -1064 ASTM C -138 ASTM C -39 MEASURED SLUMP (inches) 4.00 4.00 4.00 Concrete Compressive Cylinder 6" x 12" (area 28.27 sq. in.) DATE TESTED 08/21/2003 09/11/2003 09/11/2003 5 4 Hold CONCRETE COMPRESSIVE STRENGTH TEST PROJECT DATA REPORT OF TESTS OVERALL PLACEMENT LOCATION: North fire lane, building column Line E to P AGE (days) 7 28 28 MAXIMUM LOAD (Ibs. force) 103660 129310 128040 Average 8908 Ambassador Row, Dallas, TX 75247 2696 Gravel Drive, Fort Worth, TX 76118 6300 Rothway, Ste. 150, Houston, TX 77040 Corporate Phone: (214) 630 -9745 Report No.: Project No.: Date of Service: Report Date: 192610 037333 08/14/2003 10/10/2003 MIX DESIGN LD.: 7752 PLACEMENT DATE: 08/14/2003 WEATHER CONDITIONS: Clear TIME SAMPLED: 11:O5am BATCH TIME: 10:41 ant TEMPERATURE (F) AIR 80 F CONCRETE: 88 F TRUCK NO: 107 TICKET NO: 1 18010 SAMPLE LOCATION: 150' west, 10' south of northeast corner COMPRESSIVE STRENGTH (psi) 3670 4570 4530 4550 FRACTURE TYPE Unbonded Cap Unbonded Cap Unbonded Cap LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd. DI Page 5 of 6 Ro =gin Client: Duke Realty Services, LP Attn: Mr. Jeff Langston 5495 Belt Line Road, Suite 360 Dallas TX 75254 Project: Freeport 10 500 Freeport Parkway Coppell, TX Services: Obtain samples of fresh concrete at the placement locations, perform required field testing, cast mpressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. CONTRACTOR: CONCRETE SUPPLIER: PLANT: SPECIFICATION REQUIREMENTS STRENGTH: SLUMP (in): MR TEST METHOD: CYLINDER MARKED SET NO. 6 4 MEASURED SLUMP (inches) 6 1 4.50 6 2 4.50 6 3 4.50 Technician: Lanny Gist Report Distribution: (1) Duke Realty Services, LP (1) Duke Realty Services, LP (I) City of Coppell Engineering Dept. (1) Potter Concrete PROJECT DATA Duke Realty Services, LP MIX DESIGN 1.D.: 7752 Potter PLACEMENT DATE: 08/14/2003 On site WEATHER CONDITIONS: Partly cloudy TIME SAMPLED. 12:25pm BATCH TIME: 12:O9pm TEMPERATURE (F) AIR 82 F CONCRETE: 88 F TRUCK NO: 106 TICICET NO: 1 18019 AIR CONTENT cm: 5.0 UNIT WEIGHT (pct): NA OVERALL PLACEMENT LOCATION: North fire lane, building column Line E to P 4000 psi 28 Days 5" 3% 6% ASTM C -172 ASTM C -31 ASTM C -143 ASTM C -231 ASTM C -1064 ASTM C -138 ASTM C -39 Concrete Compressive Cylinder 6" x 12" (area 28.27 sq. in.) DATE TESTED 08/21/2003 09/11/2003 09/11/2003 Hold CONCRETE COMPRESSIVE STRENGTH TEST REPORT OF TESTS Started: 4:30am ocg AGE (days) 7 28 28 (I) Pacheco Koch Consulting Engineers (1) Engineering Analyst (I) City of Coppell Bldg. Inspections Finished: 2:OOpm MAXIMUM LOAD (Ibs. force) 103495 129200 131220 Average 8908 Ambassador Row, Dallas, TX 75247 2696 Gravel Drive, Fort Worth, TX 76118 6300 Rothway, Ste. 150, Houston, TX 77040 Corporate Phone: (214) 630 -9745 Report No.: 192610 Project No.: 037333 Date of Se. e: 08/14/2003 Repor 10/10/2003 SAMPLE LOCATION: 50' west, 10' south of northeast corner COMPRESSIVE STRENGTH (Psi) 3660 FRACTURE TYPE Unbonded Cap Unbonded Cap Unbonded Cap 4570 4 K. Scott Watson, AET CMT Operations Manager LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Roue Engineers, Ltd. Dl Page 6 of 6