Coppell CC 1B1-LR010829ALLIANCE GEOTECHNICAL GROUP GEOTECHNICAL AND CONSTRUCTION MATERIALS ENGINEERING AND TESTING 10610 Newkirk Street, Suite 202, Dallas, Texas 75220 Phone: 972-444-8889 Fax: 972-444-8893 CONCRETE INSPECTION AND COMPRESSION TEST REPORT CLIENT: Koll Development Company REPORT DISTRIBUTION: PROJECT: Koll Center -Coppell Koll Development Company -James Williams REPORT DATE: 08!29/01 Hill & Wilkerson, Inc. -Kirk Woltman AGG REPORT #: C01-0206-209 Alliance Architects -Tom Maxwell AECC, Inc. -Andy Brundige BDD, Inc. -Russell Williams City of Coppell -Lee Stone City of Coppeil -Larry Davis SPECI FICATIONS PROJECT DATA Strength (psi): 4000 Placement Date: 07/30/01 Slump (in.): 5 max Sampled By: D. Vandergriff Air Content (%): 3.5 to 6.5 Weather: Sunny Concrete Temp (°F): 95 max Supplier/Mix: Hanson - 7752 FIELD DATA SET #1 Ticket #: 907611 Time Batched: 6:41 a.m. Time Sampled: 7:30 a.m. Slump (in.): 4.50 Air Content: 6,5 Unit Weight (pcf): na Conc. Temp. (°F): 92 Ambient Temp. (°F): 87 Yardage (c.y.): 40 of 650 Placement Location: Paving Area 200' North and 50' East of the Southeast Corner of Buildinq #3 Remarks: FIELD DATA SET #2 Ticket #: 907627 Time Batched: 8:20 a.m. Time Sampled: 9:05 a.m. Slump (in.): Conc. Temp. (°F): 6.0' 92 Air Content: 7.5' Unit Weight (pcf): Ambient Temp. (°F): 89 Yardage (c.y.): na 136 of 650 Placement Location: Paving Area 170' North and 75' East of the Southeast Corner of Buildin #3 Remarks: 'Slump and air content exceeds specifications CONCRETE COMPRESSION TEST RESULTS CYLINDERS MOLDED AND CURED PER ASTM C31, TESTED PER ASTM C39 nder # Test Date A e Da s Max. Load Ibs Areas . in. Stren th si FC A 08/06/01 7 92450 28.27 3270 D B 08/06/01 7 91870 28.27 3250 C C 08/27/01 28 116560 28.27 4120 B D 08/27/01 28 117020 28.27 4140 D E Hold A 08/06/01 7 88340 28.27 3120 D B 08/06/01 7 91410 28.27 3230 D C 08/27/01 28 112630 28.27 3980 D D 08/27/01 28 114690 28.27 4060 D E Hold (~) NVKMAL CYLINDER SIZE 6" X 12", AREA 28.27 sq. in., UNLESS NOTED ABOVE. (2) FAILURE TYPE A=CONE, B=CONE AND SPLIT, C=CONE AND SHEAR, D=SHEAR, E=COLUMNAR (3) TEST RESULTS COMPLY WITH PROJECT SPECIFICATIONS UNLESS INDICATED IN NOTES. (4) FIELD TESTS ARE PER APPLICABLE ASTM STANDARDS: C138, C143, C172, C231 ~~ Note: This report is for the exclusive use of the Client addressed. This report may not be reproduced except in its entirety, without A LIANCE GEOTECHNICAL GROUP the written consent of AGG. Results a pl onl to above tests. ALLIANCE GEOTECHNICAL GROUP GEOTECHNICAL AND CONSTRUCTION MATERIALS ENGINEERING AND TESTING 10610 Newkirk Street, Suite 202, Dallas, Texas 75220 Phone: 972-444-8889 Fax: 972-444-8893 CONCRETE INSPECTION AND COMPRESSION TEST REPORT CLIENT: Koll Development Company REPORT DISTRIBUTION: PROJECT: Koll Center -Coppell Koll Development Company -James Williams REPORT DATE: 08/29/01 Hill & Wilkerson, Inc. -Kirk Woltman AGG REPORT #: C01-0206-209 Alliance Architects -Tom Maxwell AECC, Inc. -Andy Brundige BDD, Inc. -Russell Williams City of Coppell -Lee Stone City of Coppell -Larry Davis SPECIFICATIONS PROJECT DATA Strength (psi): Slump (in.): Air Content (%): 4000 5 max 3.5 to 6.5 Placement Date: Sampled By: Weather: Supplier/Mix: 07/30/01 D. Vandergriff Sunny Hanson - 7752 Concrete Temp (°F): 95 max FIELD DATA SET #3 Ticket #: 907636 Time Batched: 9:30 a.m. Time Sampled: 10:15 a.m. Slump (in.): 6.25* Air Content: 3.5 Unit Weight (pcf): na Conc. Temp. (°F): 93 Ambient Temp. (°F): 94 Yardage (c.y.): 226 of 650 Placement Location: Paving Area 125' North and 10' East of the Southeast Corner of Building #3 Remarks: *Slump was out of project specifications. FIELD DATA SET #4 Ticket #: 807331 Time Batched: 10:24 a.m. Time Sampled: 11:40 a.m. Slump (in.): 5.00 Air Content: 3.7 Unit Weight (pcf): na Conc. Temp. (°F): 95 Ambient Temp. (°F): 97 Yardage (c.y.): 334 of 650 Placement Location: Paving Area 25' North and 40' East of the Northwest Corner of Building #2 Remarks: CONCRETE COMPRESSION TEST RESULTS CYLINDERS MOLDED AND CURED PER ASTM C31, TESTED PER ASTM C39 Set # C tinder # Test Date A e Da s Max. Load Ibs Areas . in. Stren th si FC Notes A 08/06/01 7 88030 28.27 3110 D 3 B 08/06/01 7 87810 28.27 3110 D C 08/27/01 28 112580 28.27 3980 D D 08/27/01 28 114700 28.27 4060 C E Discard A 08/06/01 7 91480 28.27 3240 D 4 B 08/06/01 7 83840 28.27 2970 D C 08/27/01 28 112610 28.27 3980 D D 08/27/01 28 115660 28.27 4090 D E Discard (1) NORMAL CYLINDER SIZE 6" X 12", AREA 28.27 sq. in., UNLESS NOTED ABOVE. (2) FAILURE TYPE A=CONE, B=CONE AND SPLIT, C=CONE AND SHEAR, D=SHEAR, E=COLUMNAR (3) TEST RESULTS COMPLY WITH PROJECT SPECIFICATIONS UNLESS INDICATED IN NOTES. (4) FIELD TESTS ARE PER APPLICABLE ASTM STANDARDS: C138, C143, C172, C231 Note: This report is for the exclusive use of the Client addressed. This report may not be reproduced except in its entirety, without LL ANCE GEOTECHNICAL GROUP the written consent of AGG. Results apply only to above tests. ALLIANCE GEOTECHNICAL GROUP GEOTECHNICAL AND CONSTRUCTION MATERIALS ENGINEERING AND TESTING 10610 Newkirk Street, Suite 202, Dallas, Texas 75220 Phone: 972-444-8889 Fax: 972-444-8893 CONCRETE INSPECTION AND COMPRESSION TEST REPORT CLIENT: Koll Development Company REPORT DISTRIBUTION: PROJECT: Koll Center -Coppell Koll Development Company -James Williams REPORT DATE: 08/29/01 Hill & Wilkerson, Inc. -Kirk Woltman AGG REPORT #: C01-0206-209 Alliance Architects -Tom Maxwell AECC, Inc. -Andy Brundige BDD, Inc. -Russell Williams City of Coppell -Lee Stone City of Coppell -Larry Davis SPECIFICATIONS PROJECT DATA Strength (psi): 4000 Placement Date: 07/30/01 Slump (in.): 5 max Sampled By: D. Vandergriff Air Content (%): 3.5 to 6.5 Weather: Sunny Concrete Temp (°F): 95 max Supplier/Mix: Hanson - 7752 FIELD DATA SET #5 Ticket #: 798074 Time Batched: 1:00 p.m. Time Sampled: 2:00 p.m. Slump (in.): 5.00 Air Content: 3.6 Unit Weight (pcf): na Conc. Temp. (°F): 96* Ambient Temp. (°F): 102 Yardage (c.y.): 432 of 650 Placement Location: Paving Area 50' North and 10' West of the Northeast Corner of Building #2 Remarks: *Temperature exceeds specifications -concrete pour stop ped at 472 c.y. Ticket #: Slump (in.): Conc. Temp. (°F): Placement Location: Remarks: FIELD DATA SET # Time Batched: _ Air Content: _ Ambient Temp. (°F): Time Sampled: Unit Weight (pcf): Yardage (c.y.): CONCRETE COMPRESSION TEST RESULTS CYLINDERS MOLDED AND CURED PER ASTM C31, TESTED PER ASTM C39 Set # C tinder # Test Date A e Da s Max. Load Ibs Areas . in. Stren th si FC Notes A 08/06/01 7 101060 28.27 3570 B 5 B 08/06/01 7 104260 28.27 3690 D C 08/27/01 28 132050 28.27 4670 C D 08/27/01 28 128450 28.27 4540 D E Hold (1) NORMAL CYLINDER SIZE 6" X 12", AREA 28.27 sq. in., UNLESS NOTED ABOVE. (2) FAILURE TYPE A=CONE, B=CONE AND SPLIT, C=CONE AND SHEAR, D=SHEAR, E=COLUMNAR (3) TEST RESULTS COMPLY WITH PROJECT SPECIFICATIONS UNLESS INDICATED IN NOTES. (4) FIELD TESTS ARE PER APPLICABLE ASTM STANDARDS: C138, C143, C172, C231 Note: This report is for the exclusive use of the Client addressed. This report may not be reproduced except in its entirety, without AL IANCE GEOTECHNICAL GROUP the written consent of AGG. Results apply only to above tests. ALLIANCE GEOTECHNICAL GROUP GEOTECHNICAL AND CONSTRUCTION MATERIALS ENGINEERING AND TESTING 10610 Newkirk Street, Suite 202, Dallas, Texas 75220 Phone: 972-444-8889 Fax: 972-444-8893 CONCRETE INSPECTION AND COMPRESSION TEST REPORT CLIENT: Koll Development Company PROJECT: Koll Center -Coppell REPORT DATE: 08/29/01 AGG REPORT#: C01-0206-211 REPORT DISTRIBUTION: Koll Development Company -James Williams Hill & Wilkerson, Inc. -Kirk Woltman Alliance Architects -Tom Maxwell AECC, Inc. -Andy Brundige BDD, Inc. -Russell Williams City of Coppell -Lee Stone City of Coppell -Larry Davis SPECIFICATIONS PROJECT DATA Strength (psi): 4000 Slump (in.): 5 max Air Content (%): na Concrete Temp (°F): ' 95 max FIELD DATA SET #1 Time Batched: 6:54 a.m. Ticket #: 613484 Slump (in.): 5.5* Air Content: na Placement Date: Sampled By: Weather: Supplier/Mix: Time Sampled: Unit Weight (pct): Yardage (c.y.): 07/31 /01 D. Vandergriff Sunny Potter - 9349 7:30 a.m. na Conc. Temp. (°F): 90 Ambient Temp. (°F): 89 Placement Location: Building #2 slab leaveout 100' east od NW corner Remarks: 10 FIELD DATA SET #2 Ticket #: Time Batched: Time Sampled: Slump (in.): Air Content: Unit Weight (pcfJ: Conc. Temp. (°F): Ambient Temp. (°F): Yardage (c.y.): Placement Location: Remarks: CONCRETE COMPRESSION TEST RESULTS CYLINDERS MOLDED AND CURED PER ASTM C31, TESTED PER ASTM C39 Set # C tinder # Test Date A e Da s Max. Load Ibs Areas . in. Stren th si FC Notes A 08/07/01 7 109220 28.27 3860 D 1 B 08/07/01 7 102170 28.27 3610 D C 08/28/01 28 143900 28.27 5090 D D 08/28/01 28 141090 28.27 4990 D E Discard 2 (1) NORMAL CYLINDER SIZE 6" X 12", AREA 28.27 sq. in., UNLESS NOTED ABOVE. (2) FAILURE TYPE A=CONE, B=CONE AND SPLIT, C=CONE AND SHEAR, D=SHEAR, E=COLUMNAR (3) TEST RESULTS COMPLY WITH PROJECT SPECIFICATIONS UNLESS INDICATED IN NOTES. (4) FIELD TESTS ARE PER APPLICABLE ASTM STANDARDS: C138, C143, C172, C231 Note: This report is for the exclusive use of the Client addressed. ~~ This report may not be reproduced except in its entirety, without L IANCE GEOTECHNICAL GROUP the written consent of AGG. Results apply onl to above tests. ALLIANCE GEOTECHNICAL GROUP GEOTECHNICAL AND CONSTRUCTION MATERIALS ENGINEERING AND TESTING 10610 Newkirk Street, Suite 202, Dallas, Texas 75220 Phone: 972-444-8889 Fax: 972-444-8893 CLIENT: Koll Development Company REPORT DISTRIBUTION: PROJECT: Koll Center -Coppell Koll Development Company -James Williams REPORT DATE: 8/29/01 Hill & Wilkerson, Inc. -Kirk Woltman AGG REPORT #: C01-0206-240 Alliance Architects -Tom Maxwell AECC, Inc. -Andy Brundige BDD, Inc. -Russell Williams CONCRETE INSPECTION AND COMPRESSION TEST REPORT City of Coppell -Lee Stone City of Coppell -Larry Davis SPECIFICATIONS PROJECT DATA Strength (psi): Slump (in.): Air Content (%): 4000 5 max 3.5 to 6.5 Placement Date: 8/20/01 Sampled By: D. Vandergriff Weather: Clear Concrete Temp (°F): 95 max Supplier/Mix: Hanson - 7752 FIELD DATA SET #1 Ticket #: 816799 Time Batched: 4:15 a.m. Time Sampled: 5:00 a.m. Slump (in.): 6.25* Air Content: 6.3 Unit Weight (pcf): na Conc. Temp. (°F): 89 Ambient Temp. (°F): 84 Yardage (c.y.): 68 of 650 Placement Location: Paving Area: 60' South and 20' West of the Northwest Corner of Building #1 Remarks: 'Contractor was notified of the slump being out of the project specifications. FIELD DATA SET #2 Ticket #: 816807 Time Batched: 5:02 a.m. Time Sampled: 5:45 a.m. Slump (in.): 5.50* Air Content: 5.8 Unit Weight (pct): na Conc. Temp. (°F): 89 Ambient Temp. (°F): 85 Yardage (c.y.): 146 of 650 Placement Location: Paving Area: 100' South and 40' West of the Northwest Corner of Building #1 Remarks: `Slump and air content exceeds specifications CONCRETE COMPRESSION TEST RESULTS CYLINDERS MOLDED AND CURED PER ASTM C31, TESTED PER ASTM C39 Set # C tinder # Test Date A e Da s Max. Load Ibs Areas . in. Stren th si FC Notes A 8/27/01 7 125000 28.27 4420 D 1 B 8/27/01 7 122330 28.27 4330 D C 9/17/01 28 28.27 D 9/17/01 28 28.27 E Hold A 8/27/01 7 128740 28.27 4550 C 2 B 8/27/01 7 125110 28.27 4430 D C 9/17/01 28 28.27 D 9/17/01 28 28.27 E Hold (1) NORMAL CYLINDER SIZE 6" X 12", AREA 28.27 sq. in., UNLESS NOTED ABOVE. (2) FAILURE TYPE A=CONE, B=CONE AND SPLIT, C=CONE AND SHEAR, D=SHEAR, E=COLUMNAR (3) TEST RESULTS COMPLY WITH PROJECT SPECIFICATIONS UNLESS INDICATED IN NOTES. (4) FIELD TESTS ARE PER APPLICABLE ASTM STANDARDS: C138, C143, C172, C231 Note: This report is for the exclusive use of the Client addressed. This report may not be reproduced except in its entirety, without the written consent of AGG. Results appl only to above tests. / N%" -~ LIANCE GEOTECHNICAL GROUP ALLIANCE GEOTECHNICAL GROUP GEOTECHNICAL AND CONSTRUCTION MATERIALS ENGINEERING AND TESTING 10610 Newkirk Street, Suite 202, Dallas, Texas 75220 Phone: 972-444-8889 Fax: 972-444-8893 CONCRETE INSPECTION AND COMPRESSION TEST REPORT CLIENT: Koll Development Company REPORT DISTRIBUTION: PROJECT: Koll Center -Coppell Koll Development Company -James Williams REPORT DATE: 8/29/01 Hill & Wilkerson, Inc. -Kirk Woltman AGG REPORT #: C01-0206-240 Alliance Architects -Tom Maxwell AECC, Inc. -Andy Brundige BDD, Inc. -Russell Williams City of Coppell -Lee Stone City of Coppell -Larry Davis SPECIFICATIONS PROJECT DATA Strength (psi): 4000 Placement Date: Slump (in.): 5 max Sampled By: Air Content (%): 3.5 to 6.5 Weather: Concrete Temp (°F): 95 max Supplier/Mix: 8/20/01 D. Vandergriff Clear Hanson - 7752 FIELD DATA SET #3 Ticket #: 816817 Time Batched: 6:15 a.m. Time Sampled: 7:15 a.m. Slump (in.): 5.50* Air Content: 2.7* Unit Weight (pcf): na Conc. Temp. (°F): 90 Ambient Temp. (°F): 86 Yardage (c.y.): 244 of 650 Placement Location: Paving Area: 190' South and 25' West of the Northwest Corner of Building #1. Remarks: *Contractor was notified of the slump and air being out of the project specifications. FIELD DATA SET #4 Ticket #: 816827 Time Batched: 7:21 a.m. Time Sampled: 8:15 a.m. Slump (in.): 5.00 Air Content: 3.7 Unit Weight (pct]: na Conc. Temp. (°F): 91 Ambient Temp. (°F): 90 Yardage (c.y.): 344 of 650 Placement Location: Paving Area: 200' North and 60' West of the Southwest Corner of Building #1 Remarks: CONCRETE COMPRESSION TEST RESULTS CYLINDERS MOLDED AND CURED PER ASTM C31, TESTED PER ASTM C39 Set # C tinder # Test Date A e Da s Max. Load Ibs Areas . in. Stren th si FC Notes A 8/27/01 7 120470 28.27 4260 D 3 B 8/27/01 7 122650 28.27 4340 D C 9/17/01 28 28.27 D 9/17/01 28 28.27 E Hold A 8/27/01 7 120230 28.27 4250 D 4 B 8/27/01 7 120950 28.27 4280 C C 9/17/01 28 28.27 D 9/17/01 28 28.27 E Hold (1) NORMAL CYLINDER SIZE 6" X 12", AREA 28.27 sq. in., UNLESS NOTED ABOVE. (2) FAILURE TYPE A=CONE, B=CONE AND SPLIT, C=CONE AND SHEAR, D=SHEAR, E=COLUMNAR (3) TEST RESULTS COMPLY WITH PROJECT SPECIFICATIONS UNLESS INDICATED IN NOTES. (4) FIELD TESTS ARE PER APPLICABLE ASTM STANDARDS: C138, C143, C172, C231 Note: This report is for the exclusive use of the Client addressed. This report may not be reproduced except in its entirety, without the written consent of AGG. Results apply only to above tests. /~Li~ A IANCE GEOTECHNICAL GROUP ALLIANCE GEOTECHNICAL GROUP GEOTECHNICAL AND CONSTRUCTION MATERIALS ENGINEERING AND TESTING 10610 Newkirk Street, Suite 202, Dallas, Texas 75220 Phone: 972-444-8889 Fax: 972-444-8893 CONCRETE INSPECTION AND COMPRESSION TEST REPORT CLIENT: Koll Development Company REPORT DISTRIBUTION: PROJECT: Koll Center -Cop pell Koll Development Company -James Williams REPORT DATE: 8/29/01 Hill & Wilkerson, Inc. -Kirk Woltman AGG REPORT #: C01-0206-240 Alliance Architects -Tom Maxwell AECC, Inc. -Andy Brundige BDD, Inc. -Russell Williams City of Coppell -Lee Stone City of Coppell -Larry Davis SPECIFICATIONS PROJECT DATA Strength (psi): 4000 Placement Date: 8/20/01 Slump (in.): 5 max Sampled By: D. Vandergriff Air Content (%): 3.5 to 6.5 Weather: Clear Concrete Temp (°F): 95 max Supplier/Mix: Hanson - 7752 FIELD DATA SET #5 Ticket #: 936081 Time Batched: 8:30 a.m. Time Sampled: 9:20 a.m. Slump (in.): 5.00 Air Content: 3.7 Unit Weight (pct: na Conc. Temp. (°F): 91 Ambient Temp. (°F): 92 Yardage (c.y.): 444 of 650 Placement Location: Paving Area: 140' North and 30' West of the Southwest Corner of Building #1 Remarks: FIELD DATA SET #6 Ticket #: 816849 Time Batched: 9:15 a.m. Time Sampled: 10:15 a.m. Slump (in.): 4.75 Air Content: 4.2 Unit Weight (pcf): na Conc. Temp. (°F): 92 Ambient Temp. (°F): 93 Yardage (c.y.): 542 of 650 Placement Location: Paving Area: 70' North and 50' West of the Southwest Corner of Building #1 Remarks: CONCRETE COMPRESSION TEST RESULTS CYLINDERS MOLDED AND CURED PER ASTM C37, TESTED PER ASTM C39 Set # C tinder # Test Date A e Da s Max. Load Ibs Areas . in. Stren th si FC Notes A 8/27/01 7 113810 28.27 4030 D 5 B 8/27/01 7 112090 28.27 3960 D C 9/17/01 28 28.27 D 9/17/01 28 28.27 E Hold A 8/27/01 7 99400 28.27 3520 C 6 B 8/27/01 7 104910 28.27 3710 D C 9/17/01 28 28.27 D 9/17/01 28 28.27 E Hold (1) NORMAL CYLINDER SIZE 6" X 12", AREA 28.27 sq. in., UNLESS NOTED ABOVE. (2) FAILURE TYPE A=CONE, 6=CONE AND SPLIT, C=CONE AND SHEAR, D=SHEAR, E=COLUMNAR (3) TEST RESULTS COMPLY WITH PROJECT SPECIFICATIONS UNLESS INDICATED IN NOTES. (4) FIELD TESTS ARE PER APPLICABLE ASTM STANDARDS: C138, C143, C172, C231 Note: This report is for the exclusive use of the Client addressed. /~ ~~ This report may not be reproduced except in its entirety, without LLIANCE GEOTECHNICAL GROUP the written consent of AGG. Results apply onl to above tests. ALLIANCE GEOTECHNICAL GROUP GEOTECHNICAL AND CONSTRUCTION MATERIALS ENGINEERING AND TESTING 10610 Newkirk Street, Suite 202, Dallas, Texas 75220 Phone: 972-444-8889 Fax: 972-444-8893 CLIENT: PROJECT: REPORT DATE: AGG REPORT #: CONCRETE INSPECTION AND COMPRESSION TEST REPORT Koll Development Company Koll Center -Coppell 08/28/01 C01-0206-207 Strength (psi): Slump (in.): Air Content (%): Concrete Temp (°F): 3000 5 max na 95 max Placement Date: Sampled By: Weather: Supplier/Mix: DATA 07/27/01 D. Vandergriff Sunny Hanson - 9337 Ticket #: Slump (in.): Conc. Temp. (°F): Placement Location Remarks: FIELD DATA SET #1 937203 Time Batched: 11:20 a.m. Time Sampled: 12:00 p.m. 4.50 Air Content: na Unit Weight (pcf): na 94 Ambient Temp. (°F): 96 Yardage (c.y.): 20 Light poles on east side of building #1 _ REPORT DISTRIBUTION: Koll Development Company -James Williams Hill & Wilkerson, Inc. -Kirk Woltman Alliance Architects -Tom Maxwell AECC, Inc. -Andy Brundige BDD, Inc. -Russell Williams City of Coppell -Lee Stone City of Coppell -Larry Davis (Steel inspection handled by contractor) Ticket #: Slump (in.): Conc. Temp. (°F): Placement Location: Remarks: FIELD DATA SET #2 Time Batched: Time Sampled: Air Content: Unit Weight (pct): Ambient Temp. (°F): Yardage (c.y.): CONCRETE COMPRESSION TEST RESULTS CYLINDERS MOLDED AND CURED PER ASTM C37, TESTED PER ASTM C39 Set # C tinder # Test Date A e Da s Max. Load Ibs Areas . in. Stren th si FC Notes A 08/03/01 7 93510 28.27 3310 D 1 B 08/03/01 7 90210 28.27 3190 D C 08/24/01 28 125970 28.27 4460 D D 08/24/01 28 128970 28.27 4560 C E Discard 2 (1) NORMAL CYLINDER SIZE 6" X 12", AREA 28.27 sq. in., UNLESS NOTED ABOVE. (2) FAILURE TYPE A=CONE, 6=CONE AND SPLIT, C=CONE AND SHEAR, D=SHEAR, E=COLUMNAR (3) TEST RESULTS COMPLY WITH PROJECT SPECIFICATIONS UNLESS INDICATED IN NOTES. (4) FIELD TESTS ARE PER APPLICABLE ASTM STANDARDS: C138, C143, C172, C231 Note: This report is for the exclusive use of the Client addressed. // This report may not be reproduced except in its entirety, without L IANCE GEOTECHNICAL GROUP the written consent of AGG. Results apply only to above tests. ALLIANCE GEOTECHNICAL GROUP GEOTECHNICAL AND CONSTRUCTION MATERIALS TESTING AND ENGINEERING 10610 Newkirk, Suite #202, Dallas, Texas 75220 Phone #972-444-8889 Fax #972-444-8893 REINFORCING STEEL OBSERVATION REPORT CLIENT: Koll Development Company PROJECT: Koll Center -Coppell REPORT DATE: 08/28/01 AGG REPORT #: C01-0206-246 DISTRIBUTION: Koll Development Company -James Williams Hill & Wilkerson, Inc. -Kirk Woltman Alliance Architects -Tom Maxwell AECC, Inc. -Andy Brundige City of Coppell -Lee Stone City of Coppell -Larry Davis TECHNICIAN: Duane Vandergriff WEATHER: Cloudy DATE: 08/25/01 AREAS OBSERVED: Paving area -fire lane between bldg #1 and #2 from NW corner of bldg #1 to SW corner of bldg #1 OBSERVATION CHECK LIST: SIZE: X COVER: X SPLICE LENGTH: X CLEANLINESS: X PROPERLY TIED: X CLEANLINESS OF FORM WORK: X PROPER SUPPORT: X REFERENCE DRAWING: REMARKS: All reinforcing steel appears to comply with project specifications Note: This report is for the exclusive use of the Client addressed. /~~_ This report may not be reproduced except in its entirety, without the written consent of AGG. Results apply only to above tests. Z-ALLIANCE GEOTECHNICAL GROUP