Coppell CC 1B1-LR010824ALLIANCE GEOTECHNICAL GROUP GEOTECHNICAL AND CONSTRUCTION MATERIALS ENGINEERING AND TESTING 10610 Newkirk Street, Suite 202, Dallas, Texas 75220 Phone: 972-444-8889 Fax: 972-444-8893 CONCRETE INSPECTION AND COMPRESSION TEST REPORT CLIENT: Koll Development Company REPORT DISTRIBUTION: PROJECT: Koll Center -Coppell Koll Development Company -James Williams REPORT DATE: 08/24/01 Hill & Wilkerson, Inc. -Kirk Woltman AGG REPORT #: C01-0206-203 Alliance Architects -Tom Maxwell AECC, Inc. -Andy Brundige BDD, Inc. -Russell Williams City of Coppell -Lee Stone City of Coppell -Larry Davis SPECI FICATIONS PROJECT DATA Strength (psi): 4000 Placement Date: 07/26/01 Slump (in.): 5 max Sampled By: D. Vandergriff Air Content (%): na Weather: Sunny Concrete Temp (°F): 95 max Supplier/Mix: Potter - 9349 FIELD DATA SET #1 Ticket #: 613366 Time Batched: 7:46 a.m. Time Sampled: 8:30 a.m. Slump (in.): 5.00 Air Content: na Unit Weight (pct): na Conc. Temp. (°F): 94 Ambient Temp. (°F): 91 Yardage (c.y.): 10 of 60 Placement Location: Building #2 leaveout 10' W. of NE corner Remarks: FIELD DATA SET #2 Ticket #: Time Batched: Time Sampled: Slump (in.): Air Content: Unit Weight (pcf): Conc. Temp. (°F): Ambient Temp. (°F): Yardage (c.y.): Placement Location: Remarks: CONCRETE COMPRESSION TEST RESULTS CYLINDERS MOLDED AND CURED PER ASTM C31, TESTED PER ASTM C39 Set # C tinder # Test Date A e Da s Max. Load Ibs Areas . in. Stren th si FC Notes A 08/02/01 7 111840 28.27 3960 D 1 B 08/02/01 7 106870 28.27 3780 D C 08/23/01 28 136460 28.27 4830 D D 08/23/01 28 142480 28.27 5040 C E Discard 2 (1) NORMAL CYLINDER SIZE 6" X 12", AREA 28.27 sq. in., UNLESS NOTED ABOVE. (2) FAILURE TYPE A=CONE, B=CONE AND SPLIT, C=CONE AND SHEAR, D=SHEAR, E=COLUMNAR (3) TEST RESULTS COMPLY WITH PROJECT SPECIFICATIONS UNLESS INDICATED IN NOTES. (4) FIELD TESTS ARE PER APPLICABLE ASTM STANDARDS: Ct38, C143, C172, C231 Note: This report is for the exclusive use of the Client addressed. ~/t'Y This report may not be reproduced except in its entirety, without LIANCE GEOTECHNICAL GROUP the written consent of AGG. Results apply onl to above tests. ALLIANCE GEOTECHNICAL GROUP, INC. GEOTECHNICAL AND CONSTRUCTION MATERIALS TESTING & ENGINEERING 10610 Newkirk Street Suite #202 Dallas, Texas 75220 Phone 972-444-8889 Fax 972-444-8893 SOIL MOISTURE -DENSITY TEST REPORT IN-PLACE TESTS BY NUCLEAR METHODS (ASTM D 2922) CLIENT: Koll Development Company DISTRIBUTION: PROJECT: Koll Center -Coppell Koll Development Company- James Williams REPORT DATE: 08/28/01 Hill & Wilkerson, Inc. -Kirk Woltman AGG REPORT #: C01-0206-245 Alliance Architects -Tom Maxwell AECC, Inc. -Andy Brundige City of Coppell -Lee Stone City of Coppell -Larry Davis SPECIFICATIONS TEST DATA Compaction: 97 Date Tested: Moisture: -2 to +2 Techniolan: MATERIAL REFERENCE CURVE DATA CURVE NO. TEST METHOD MATERIAL DESCRIPTION OPTIMUM MOISTURE MAX. DRY DENSITY (pcf) 343 ASTM D 698 Gra ish Brown Cla 23.2 99.0 344 AS7M D 698 Dark Brown Cla 23.9 97.5 IN-PLACE TEST RESULTS TEST NO. ELEVATION OR LIFT LOCATION REF. CURVE % MOISTURE DRY DENSITY MOISTURE DEVIATION DENSITY 1 Final Paving area 90' W. & 25' S. of NW corner of Buildin #1 343 22.1 99.6 -1.1 100.6 2 Final Paving area 90' W. & 150' S. of NW corner of Buildin #1 344 21.9 98.4 -2.0 100.9 3 Final Paving area 90' W. & 150' N. of SW corner of Buildin #1 344 22.7 98.0 -1.2 100.5 4 Final Paving area 90' W. & 25' N. of SW corner of Buildin #1 343 21.6 99.2 -1.6 100.2 'GOES NOT COMPLY WITH PROJECT SPECIFICATIONS Notes: ALLIANCE GEOTECHNICAL GROUP, INC. ALLIANCE GEOTECHNICAL GROUP GEOTECHNICAL AND CONSTRUCTION MATERIALS ENGINEERING AND TESTING 10610 Newkirk Street, Suite 202, Dallas, Texas 75220 Phone: 972-444-8889 Fax: 972-444-8893 CONCRETE INSPECTION AND COMPRESSION TEST REPORT CLIENT: Koll Development Company REPORT DISTRIBUTION: PROJECT: Koll Center -Coppell Koll Development Company -James Williams REPORT DATE: 08/24/01 Hill & Wilkerson, Inc. -Kirk Woltman AGG REPORT #: C01-0206-200 Alliance Architects -Tom Maxwell AECC, Inc. -Andy Brundige BDD, Inc. -Russell Williams City of Coppell -Lee Stone City of Coppell -Larry Davis Strength (psi): Slump (in.): Air Content (%): Concrete Temp (°F): 4000 5 max 3.5 to 6.5 95 max Placement Date: Sampled By: Weather: Supplier/Mix: 07/25/01 D. Vandergriff Sunny Potter - 9349 FIELD DATA SET #1 Ticket #: Slump (in.): Conc. Temp. (°F): Placement Location Remarks: 613292 5.00 na Unit Weight (pcf): na 90 Ambient Temp. (°F): 87 Yardage (c.y.): 40 of 400 Paving area 30' north and 10' east of NE corner of building #3 Time Batched: Air Content: 7:01 a.m. Time Sampled: 7:45 a.m. FIELD DATA SET #2 Ticket #: 613302 Time Batched: 8:15 a.m. Time Sampled: 8:45 a.m. Slump (in.): 5.75* Air Content: na Unit Weight (pcf): na Conc. Temp. (°F): 90 Ambient Temp. (°F): 88 Yardage (c.y.): 140 of 400 Placement Location: Paving area 30' east and 75' south of NE corner of buildin g #3 Remarks: *Slump exceeds specifications CONCRETE COMPRESSION TEST RESULTS CYLINDERS MOLDED AND CURED PER ASTM C31, TESTED PER ASTM C39 Set # C tinder # Test Date A e Da s Max. Load Ibs Areas . in. Stren th si FC Notes A 08/01/01 7 99960 28.27 3540 D 1 B 08101/01 7 94280 28.27 3330 D C 08/22/01 28 119620 28.27 4230 D D 08/22/01 28 117840 28.27 4170 D E Discard 2 A 08/01/01 7 84320 28.27 2980 D B 08/01 /01 7 85830 28.27 3040 D C 08/22/01 28 109420 28.27 3870 D D 08/22/01 28 104800 28.27 3710 C * Does not meet specs. E 09/19/01 56 (1) NORMAL CYLINDER SIZE 6" X 12", AREA 28.27 sq. in., UNLESS NOTED ABOVE. (2) FAILURE TYPE A=CONE, B=CONE AND SPLIT, C=CONE AND SHEAR, D=SHEAR, E=COLUMNAR (3) TEST RESULTS COMPLY WITH PROJECT SPECIFICATIONS UNLESS INDICATED IN NOTES. (4) FIELD TESTS ARE PER APPLICABLE ASTM STANDARDS: C138, C143, Ct72, C231 Note: This report is for the exclusive use of the Client addressed. ~ it/~ This report may not be reproduced except in its entirety, without LL NCE GEOTECHNICAL GROUP the written consent of AGG. Results apply only to above tests. ALLIANCE GEOTECHNICAL GROUP GEOTECHNICAL AND CONSTRUCTION MATERIALS ENGINEERING AND TESTING 10610 Newkirk Street, Suite 202, Dallas, Texas 75220 Phone: 972-444-8889 Fax: 972-444-8893 CONCRETE INSPECTION AND COMPRESSION TEST REPORT CLIENT: Koll Development Company REPORT DISTRIBUTION: PROJECT: Koll Center -Coppell Koll Development Company -James Williams REPORT DATE: 08/24/01 Hill & Wilkerson, Inc. -Kirk Woltman AGG REPORT #: C01-0206-200 Alliance Architects -Tom Maxwell AECC, Inc. -Andy Brundige BDD, Inc. -Russell Williams City of Coppell -Lee Stone City of Coppell -Larry Davis SPECIFICATIONS PROJECT DATA Strength (psi): 4000 Placement Date: 07/25/01 Slump (in.): 5 max Sampled By: D. Vandergriff Air Content (%): 3.5 to 6.5 Weather: Sunny Concrete Temp (°F): 95 max Supplier/Mix: Potter - 9349 FIELD DATA SET #3 Ticket #: 613313 Time Batched: 9:49 a.m. Time Sampled: 10:15 a.m. Slump (in.): 6.25* Air Content: 9.5* Unit Weight (pcf): na Conc. Temp. (°F): 94 Ambient Temp. (°F): 96 Yardage (c.y.): 240 of 400 Placement Location: Paving area 110' south and 90' east of NE corner of building #3 Remarks: *Slump and air content exceeds specifications FIELD DATA SET #4 Ticket #: No ticket No. Time Batched: 10:50 a.m. Time Sampled: 11:15 a.m. Slump (in.): 5.25* Air Content: 9.0* Unit Weight (pct): na Conc. Temp. (°F): 95 Ambient Temp. (°F): 99 Yardage (c.y.): 340 of 400 Placement Location: Paving area 100' south and 25' east of NE corner of building #3 Remarks: *Slump and air content exceeds specifications CONCRETE COMPRESSION TEST RESULTS CYLINDERS MOLDED AND CURED PER ASTM C31, TESTED PER ASTM C39 Set # C tinder # Test Date A e Da s Max. Load Ibs Areas . in. Stren th si FC Notes A 08/01/01 7 72520 28.27 2570 D 3 B 08/01/01 7 72340 28.27 2560 D C 08/22/01 28 83960 28.27 2970 D * D 08/22/01 28 80830 28.27 2860 C * Does not meet specs. E 09/19/01 56 4 A 08/01 /01 7 76000 28.27 2690 D B 08/01 /01 7 72730 28.27 2570 D C 08/22/01 28 99450 28.27 3520 D D 08/22/01 28 91760 28.27 3250 D * Does not meet specs. E 09/19/01 56 (1) NORMAL CYLINDER SIZE 6" X 12", AREA 28.27 sq. in., UNLESS NOTED ABOVE. (2) FAILURE TYPE A=CONE, B=CONE AND SPLIT, C=CONE AND SHEAR, D=SHEAR, E=COLUMNAR (3) TEST RESULTS COMPLY WITH PROJECT SPECIFICATIONS UNLESS INDICATED IN NOTES. (4) FIELD TESTS ARE PER APPLICABLE ASTM STANDARDS: C138, C143, C172, C231 Note: This report is for the exclusive use of the Client addressed. This report may not be reproduced except in its entirety, without the written consent of AGG. Results apply onl to above tests. AL-~EOTECHNICAL GROUP ALLIANCE GEOTECHNICAL GROUP GEOTECHNICAL AND CONSTRUCTION MATERIALS ENGINEERING AND TESTING 10610 Newkirk Street, Suite 202, Dallas, Texas 75220 Phone: 972-444-8889 Fax: 972-444-8893 CONCRETE INSPECTION AND COMPRESSION TEST REPORT CLIENT: Koll Development Company REPORT DISTRIBUTION: PROJECT: Koll Center -Coppell Koll Development Company -James Williams REPORT DATE: 08/24/01 Hill & Wilkerson, Inc. -Kirk Woltman AGG REPORT #: C01-0206-200 Alliance Architects -Tom Maxwell AECC, Inc. -Andy Brundige _ BDD, Inc. -Russell Williams City of Coppell -Lee Stone City of Coppell -Larry Davis SPECIFICATIONS PROJECT DATA Strength (psi): 4000 Placement Date: 07/25/01 Slump (in.): 5 max Sampled By: D. Vandergriff Air Content (%): 3.5 to 6.5 Weather: Sunny Concrete Temp (°F): 95 max Supplier/Mix: Potter - 9349 FIELD DATA SET #5 Ticket#: 613333 Time Batched: 11:49 a.m. Time Sampled: 12:30 p.m. Slump (in.): 4.75 Air Content: 6.5 Unit Weight (pcf): na Conc. Temp. (°F): 97' Ambient Temp. (°F): 101 Yardage (c.y.): 440 of 500 Placement Location: Paving area 210' south and 40' east of NE corner of building #3 Remarks: `Temperature exceeds specifications FIELD DATA SET #6 Ticket #: Time Batched: Time Sampled: Slump (in.): Air Content: Unit Weight (pcf): Conc. Temp. (°F): Ambient Temp. (°F): Yardage (c.y.): Placement Location: Remarks: CONCRETE COMPRESSION TEST RESULTS CYLINDERS MOLDED AND CURED PER ASTM C3'I, TESTED PER ASTM C39 Set # C tinder # Test Date A e Da s Max. Load Ibs Areas . in. Stren th si FC Notes A 08/01/01 7 104310 28.27 3690 B 5 B 08/01 /01 7 103030 28.27 3640 D C 08/22/01 28 134770 28.27 4770 D D 08/22/01 28 139440 28.27 4930 D E Discard 6 (t) NORMAL CYLINDER SIZE 6' X 12", AREA 28.27 sq. in., UNLESS NOTED ABOVE. (2) FAILURE TYPE A=CONE, B=CONE AND SPLIT, C=CONE AND SHEAR, D=SHEAR, E=COLUMNAR (3) TEST RESULTS COMPLY WITH PROJECT SPECIFICATIONS UNLESS INDICATED IN NOTES. (4) FIELD TESTS ARE PER APPLICABLE ASTM STANDARDS: C138, C143, C172, C231 Note: This report is for the exclusive use of the Client addressed. This report may not be reproduced except in its entirety, without AL IA CE GEOTECHNICAL GROUP the written consent of AGG. Results apply only to above tests.