Loading...
Coppell CC 1B1-LR010529ALLIANCE GEOTECHNICAL GROUP GEOTECHNICAL AND CONSTRUCTION MATERIALS ENGINEERING AND TESTING 10610 Newkirk Street, Suite 202, Dallas, Texas 75220 Phone: 972-444-8889 Fax: 972-444-8893 CONCRETE INSPECTION AND COMPRESSION TEST REPORT CLIENT: Koll Development Company REPORT DISTRIBUTION: PROJECT: KoH Center -Coppell Koll Development Company -James Williams REPORT DATE: 05/29/01 Hill 8, Wilkerson, Inc. -Kirk Woltman AGG REPORT #: C01-0206-076 Alliance Architects -Tom Maxwell AECC, Inc. -Andy Brundige City of Coppell -Lee Stone City of Coppell -Larry Davis SPECI FICATIONS PROJECT DATA Strength (psi): 4000 Placement Date: 05/14/01 Slump (in.): 4 - 6 Sampled By: D. Vandergriff Air Content (%): na Weather: Partly Cloudy Concrete Temp (°F): 55 - 90 Supplier/Mix: Pioneer #7752 FIELD DATA SET #1 Ticket #: 698897 Time Batched: 1:55 p.m. Time Sampled: 2:45 p.m. Slump (in.): 5.00 Air Content: n/a Unit Weight (pct): n/a Conc. Temp. (°F): 85 Ambient Temp. (°F): 90 Yardage (c.y.): 5 of 5 Placement Location: SS #3 Infet Remarks: FIELD DATA SET #2 Ticket #: Time Batched: Time Sampled: Slump (in.): Air Content: Unit Weight (pcf): Conc. Temp. (°F): Ambient Temp. (°F): Yardage (c.y.): Placement Location: Remarks: CONCRETE COMPRESSION TEST RESULTS CYLINDERS MOLDED AND CURED PER ASTM C31, TESTED PER ASTM C39, CAPPED PER ASTM C617 Set # C tinder # Test Date A e Da s Max. Load Ibs Areas . in. Stren th si FC Notes 1 A 05/21/01 7 110390 28.27 3900 B 06/11/01 28 28.27 C 06/11/01 28 28.27 D hold 2 (1) NORMAL CYLINDER SIZE 6" X 12', AREA 28.27 sq. in., UNLESS NOTED ABOVE. (2) TYPE "A" CONE FRACTURE UNLESS INDICATED OTHERWISE IN NOTES. (3) TEST RESULTS COMPLY WITH PROJECT SPECIFICATIONS UNLESS INDICATED IN NOTES. (4) FIELD TESTS ARE PER APPLICABLE ASTM STANDARDS: C138, C143, Ci72, C231 Note: This report is for the exclusive use of the Client addressed. ~j This report may not be reproduced except in i[s entirety, without the written consent of AGG. Results apply only to above tests. ~ ALLIANCE GEOTECHNICAL GROUP