Freeport NIP(2.2)-LR010810FIELD DENSITY TESTING
Report Number: 94011204.0003
Service Date: July 24, 2001
8901 Carpenter F~vy., Suite #100
Dallas, Texas 75247
(214) 630-1010
Client: TNA North American, Inc.
Attn: Terry Raley
1321 Valwood Parkway, Suite 440
Carrollton TX 75006
Report Date: August 10, 2001
Project: Sales Office & Warehouse Fac.
Coppell, Texas
Project Number: 94011204
Material Information
Material Laboratory
No. Test Method
Description and Classification
Lab Test Data Proiect Requirements
Optimum Max. Lab Water
Water Dry Unit Content Minimum Dry
Content Weight Range Unit Weight
(%) (pcf) (%) (% compaction)
1. 112040002 ASTM D-698 Dk & med brown clay
Field Test Data Probe
Test Lift/ Mat. Depth
No. Test Location Elevation No. (inches)
Bldg Pad Subgrade
1 25' N and 25' W of SE corner of building 1st 1 6
2 45' N and 55' W of SE corner of building 1st 1 6
3 75' N and 75' W of SE corner of building 1st 1 6
4 35' S and 45' E of NW corner of building 1st 1 6
5 65' S and 20' W of NE corner of building 1st 1 6
23.0 97.0 -1/+3 95
Water Dry Unit Dry Unit
Content Weight Weight
(%) (pcO (% compaction)
18.9 * 98.9 102
19.8 * 99.2 102
20.2 * 100.6 104
19.7 * 98.7 102
20.6 * 95.9 99
Comments:
An asterisk (*) appears next to test results which do NOT meet the project specifications.
Services - Perform in-place density and moisture content tests to determine degree of compaction and material moisture
condition.
Field Test Method:ASTM D2922, ASTM D3017
Gauge ID:
Field Results Reported To: ContractorNVier Bros.
Technician: Brad Rengstorff
Repod Distribution:
(1) TNA North American, Inc. (1) FACSe~vices Inc
(1) Carrell poole & Yost Architecture (1) David Kent
(1) R L Goodson Consulting Engineers (1) City of Coppell - Bldg Insp
Reviewed by:
Eric J. Cleveland, P.E~
(1) Pacific Builders Inc (1) City of Coppell - Constr Insp Senior Project Engineer
The tests were pen~ormed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client
indicated above and shall not bo reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable
to the actual samples tested at the Iocafion(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials,