Magnolia Rest-LR030705RoneEngineers
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77040
Corporate Phone: (214) 630-9745
IN-PLACE DENSITY TESTING
Client:
Purple Mountain Construction Services
Attn: Mr. Jeff Burkham
4712 Memphis St.
Dallas TX 75207
Project: Deliman Grill
605 N. Denton Tap Road
Coppell, TX
Services: Perform In-Place Density Test in accordance with ASTM Standards.
Report No.: 179305
Project No.: 037748
Date of Service: 06/26/2003
Report Date: 07/05/2003
PROJECT DATA
CONTRACTOR: Purple Mountain Construction
Gauge: Troxler 3430
Test Methods: ASTM D-2922
ASTM D-3017 Gauge Serial No: 33305
Test Mode: DT
Standard Counts
Moisture Density
Current: 558 Current: 2727
Previous: 551 Previous: 2742
MOISTURE DENSITY RELATIONS
Maximum Project Requirements
M/D No. Description Moisture % Density pcf Moisture Density
1 Reddish Brown Clayey Sand 11.0 119.5 Optimum + 95 min
FIELD DENSITY TESTS
TEST PROBE
NO TEST LOCATION DEPTH
IVIED MOISTURE WET DENSITY DRY DENSITY DENSITY
No. (%) ~c0 ~c~ (% max)
Building Pad
1 15' south, 15' east from northwest building 6" 1 13.4 119.6 105.5 88 *
comer, 1st lift
Building Pad
2 20' south, 20' west from northeast building 6" 1 12.3 119.7 106.6 89 *
Technician: Scott Fagan
Report Distribution:
(1) Purple Mountain Construction Services
comer, 1st lift
Started: 7:30am Finished: 8:45am
x--.Cla~ Stark
Projg~t Manager
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, performance, etc.) or any other feature of similar subject maOer provided by persons or conditions over which we have no control. Our letters and
reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full w/thout the wd~aen approval of Rone Engineers, Ltd.
07DD Page 1 of 1
RoneEngineers
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77040
Corporate Phone: (214) 630-9745
IN-PLACE DENSITY TESTING
Client:
Project:
Purple Mountain Comtmction Services
Attn: Mr. Jeff Burkham
4712 Memphis St.
Dallas TX 75207
Deliman Grill
605 N. Denton Tap Road
CoppeR, TX
Perform In-Place Density Test in accordance with ASTM Standards.
Report No.: 179274
Project No.: 037748
Date of Service: 06/26/2003
Report Date: 07/05/2003
PROJECT DATA
CONTRACTOR: Purple Mountain Construction Gauge: Troxler 3430
Test Methods: ASTM D-2922
Gauge Serial No: 33305
ASTM D-3017
Test Mode: DT
Moisture
Current: 558
Previous: 551
M/D No.
Description
MOISTURE DENSITY RELATIONS
Maximum
Moisture % Density pcf
Reddish Brown Clayey Sand
Standard Counts
Density
Current: 2727
Previous: 2742
Project Requirements
Moisture Density
11.0 119.5 Optimum + 95 min
FIELD DENSITY TESTS
TEST PROBE
NO TEST LOCATION DEPTH
M/D MOISTURE WET DENSITY DRY DENSITY DENSITY
No. (%) (pcf) (PC0 (% max)
Building Pad
1 Retest from item #1 on report #179309 6" 1 12.2
Building Pad
2 Retest from item #2 on report gl 79305 6" 1
Test results on this report meet project specification.
Technician: SCOtt Fagan
Report Distribution:
(1) Purple Mountain Constmcfion Services
Started: 12:30p
128.2 114.3 96
11.3 126.3 ~,~ 95
Finished: 2:00pm R~Ltd.
~-~ C~y Stark
Pr~ect Manager
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and
reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd.
07DD Page 1 of 1
Ro gineers
Client:
Purple Mountain Construction Services
Atto: Mr. JeffBurkham
4712 Memphis St.
Dallas TX 75207
Project: Deliman Grill
605 N. Denton Tap Road
Coppell, TX
Services: Drilled Pier Inspection
8908 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77640
Corporate Phone: (214) 630-9745
REPORT OF DRILLED PIER INSPECTION
Report No.: 179445
Project No.: 037748
Date of Service: 06/30/2003
Report Date: 07/05/2003
Report of Inspection
On this date, a Rone Engineers, Ltd. representative(s) was on site to perform
Drilled Pier Inspection. The results are attached.
Technician Time: 7:30am - 6:15pm
Page 1 of 3
Technician: Shawn Deal
Report Distribution:
(1) Purple Mountain Construction Services
'-Clq~ Stark
Proj orct Manager
LiMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation ia quality
(composition, appearance, performance, em.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our le~ers and
reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approvaI of Rone Engineers, Llxt.
99DD Page 1 of 1
RONE ENGINEERS, Ltd.
REPORT OF
STRAIGHT SHAFT PIER INSPECTION
Client: Purple Mountain Construction Services Report No.: 179445
Project No.: 037748
Project: Deliman Grill Date of Service: 6/30/2003
Page 2 of 3
Driller: Auger Drilling
Pier Identification C/8 B/8 A/7 E/6 A/5
Pier Diameter (in) 18 18 18 18 18
Depth of Pier From Surface (f~) 22.50 23.80 24.90 20.80 23.70
Depth of Bearinl~ Stratum From Surface (R) 19.80 19.70 20.60 18.70 20.90
Required Penetration (ft) 2.00 3.00 4.00 2.00 2.00
Actual Penetration (ft)* 2.70 4.10 4.30 2.10 2.80
Condition of Bottom (wet / dry) Dry Dry Dry Dry Dry
Plumb Within Tolerance (yes / no) Yes Yes Yes Yes Yes
Casing Diameter (in) / Casing Length (fi) 22/19.7 22/19.7 22/22.4 22/19.7 22/22.4
Number of Bars / Reinforcing Bar Size 4/#7 4/#7 4/#7 4/#7 4/#7
Length of Reinforcing Steel (t~) 22.80 22..80 23.50 23.30 22.80
rime Drilling was Completed (am / pm) 9:08 AM 10:45 AM 12:30 PM 3:17 PM 2:48 PM
rime Concrete was Placed (am / pm) 2:52 PM 2:30 PM 2:00 PM 4:45 PM 3:55 PM
Depth of Pier From Top of Concrete (f0 23.33 24.55 25.48 21.55 24.45
Elevation: Surface (ft)** 97.17 97.25 97.42 97.25 97.25
iElevation: Top of Pier (R)** 98.00 98.00 98.00 98.00 98.00
Elevation: Bottom of Pier (ft)** 74.67 73.45 72.52 76.45 73.55
Elevation: Top of Bearinl~ Stratum (f~.)** 77.37 77.55 76.82 78.55 76.35
Bearial~ Stratum (description) Dark Gray Shale
Note: See report # 179446 for Compressive Stxength Test Specimens.
* Additional Penetration not requested unless noted.
Remarks: Pier location A/7: Significant gravel strata encountered at 13-14' below existing surface resulting
in enlarged sidewall diameter prior to installation of temporary casing.
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in
quality (composition. appearance, pedormance, etc,) or any other feature of similar subject matter provided by persons or conditions over which we have no
control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except In full without the written
approval of Rone Engineers, Ltd.
RONE ENGINEERS, Ltd.
REPORT OF
STRAIGHT SHAFT PIER INSPECTION
Client: Purple Mountain Construction Services Report No.: 179445
Project No.: 037748
Project: Deliman Grill Date of Service: 6/30/2003
Page 3 of 3
Driller: Auger Drilling
Pier Identification Ag4
Pier Diameter (in) 18
Depth of Pier From Surface (ft) 24.70
Depth of Bearing Stratum From Surface (ft) 18.80
Required Penetration (ft) 5.00
Actual Penetration (fi)* 5.90
Condition of Bottom (wet / dry) Dry
Plumb Within Tolerance (yes / no) Yes
Casing Diameter (in) / Casing Length (fi) 22/19.7
Number of Bars / Reinforcing Bar Size 4/#7
Length &Reinforcing Steel (ft) 23.30
rime Drillin~ was Completed (am / pm) 3:41 PM
rime Concrete was Placed (am / pm) 4:25 PM
Depth of Pier From Top of Concrete (fi) 25.70
Elevation: Surface (fi)** 97.00
Elevation: Top of Pier (fi)** 98.00
Elevation: Bottom of Pier (fi)** 72.30
Elevation: Top of Bearing Stratum (f~.)** 78.20
Bearing Stratum (description) Dark Gm~ Shale
Note: See report # 179446 for Compressive Strength Test Spemmens.
* Additional penetration not requested unless noted.
Remarks:
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for tesgng. We assume no responsibility for variation in
quality (composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no
:ontrol. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except In full without the written
~pproval of Rone Engineers, Ltd.
Ro gineers
8900 Ambassador Row, Dallas, TX 75247
2696 Gravel Drive, Fort Worth, TX 76118
6300 Rothway, Ste. 150, Houston, TX 77040
Corporate Phone: (214) 630-9745
IN-PLACE DENSITY TESTING
Client:
Project:
Purple Mountain Construction Services
Attn: Mr. JeffBurkham
4712 Memphis St.
Dallas TX 75207
Deliman Grill
605 N. Denton Tap Road
Coppell, TX
Perform In-Place Density Test in accordance with ASTM Standards.
Report No.: 179306
Project No.: 037748
Date of Service: 06/26/2003
Report Date: 07/05/2003
PROJECT DATA
CONTRACTOR: Purple Mountain Construction
Gauge: Troxler 3430
Test Methods: ASTM D-2922
ASTM D-3017 Gauge Serial No: 33305
Test Mode: DT
Standard Counts
Moisture Density
Current: 558 Current: 2727
Previous: 551 Previous: 2742
MOISTURE DENSITY RELATIONS
Maximum Project Requirements
M/D No. Description Moisture % Density pcf Moisture Density
1 Light Brown Sandy Clay 20.0 100.0 Optimum +5 95 min
FIELD DENSITY TESTS
TEST LOCATION
TEST PROBE M/D MOISTURE WET DENSITY DRY DENSITY DENSITY
NO DEPTH No. (%) (per) (pci) (% max)
Utility Backfill
1 15' south of tie-in at the northwest comer of 6" 1 23.7 119.0 96.2 96
project on 8" sanitary sewer, 1st lift
Utility Backfill
2 15' south of tie-in at the northwest comer of 6" 1 22.4 117.3 95.8 96
project on 8" sanitary sewer, 2nd lift
Utility Backfill
3 15' south of tie-in at the northwest comer of 6" 1 23.8 119.2 96.3 96
project on 8" sanita~ sewer, 3rd & final
Utility Bacicfill
4 24' north of manhole at the southwest 6" 1 24.1 120.5 97.1 97
comer of project, 8" sanitary sewer, 1st lift
Utility Backfill
5 24' north of manhole at the southwest 6" 1 23.0 117.8 95.8 96
comer of project, 8" sanitary sewer, 2nd lift
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variafion in quality
(composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and
reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineers, Ltd.
07DD Page 1 of 2
RoneEngineers
Report No.: 179306 m~~
Project No.: 037748 CHent: Purple Mountaifi Constraction Services
TEST PROBE
NO TEST LOCATION DEPTH
M/D MOISTURE WET DENSITY DRY DENSITY DENSITY
No. (%) (pcf) (pc0 (% max)
Utility Backfill
6 24' north of manhole at the southwest 6"
comer of project, 8" sanita~ sewer, 3rd &
final
Technician: Scott Fagan
Report Distribution:
(1) ptuple Mountain Construction Services
1 21.8 117.2 96.2 96
Test results on this report meet project specification.
Started: 8:45am
Finished: 10:15a
x,.OYa~Stark
Projec~Manager
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, performance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and
reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without thc wri~en approval of Rone Engineers, Ltd.
07DD Page 2 of 2