Bank One-LR031113CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 94031289.0068
Service Date: October 15, 2003
Client: Bank One Texas NA
Attn: Danny Buckner
8111 Preston Suite 250
Dallas TX 75225
'lrerracan
6901 Carpenter Frw¥, Ste #100
Dallas, Texas 75247
(214) 630-1010
Report Date: November 13, 2003
Project: Bank One - Coppell TX
616 North Denton Tap Rd
Coppell, TX
Project Number: 94031289
Material Information
Specified Strength: 4000 psi @ 28 Days
Batch Time:
Supplier: LDJ
Truck No: Ticket No: 51185
Mix I.D. No.: 60A
Water Added Onsite Before Test: 10 Gallons
Water Added Onsite After Test: 0 Gallons
Field Test Data
Test Result
Slump, inches: 5.25
Air Content, %: 3.4
Concrete Temperature, o F: 84
Ambient Temperature, o F: 78
Plastic Unit Weight, pcf:
Laboratorv Test Data
Sample Information
Sample Time: 4:07pm Date Cast: October 15, 2003
Technician: ThomasB. Combs
Weather Conditions: Sunny
Accumulative Yards: 20
Placement Method: Direct Discharge
Sample Locations: 45' N of SE approach
Placement Location: Parking Lot
Specification
Test Method
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-1064
Age at Maximum Compressive
Set Specimen Diameter Area Date Test Load Strength
No. ID (inches) (sq. inches) Tested (days) (lbs) (psi)
1 1 6.00 28.27 10/22/2003 7 86,200 3,050
1 2 6.00 28.27 10/22/2003 7 88,650 3,130
Average 3,090
1 3 6.00 28.27 11/12/2003 28 126,150 4,460
1 4 6.00 28.27 11/12/2003 28 123,340 4,360
Average 4,410
Comments: Not tested for plastic unit weight.
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
Technician: Thomas B. Combs
Repod Distribution:
(1) Bank One Texas NA
(1) City of Coppeil TX
(1) Aguirre Building Systems
(1) City of Coppell TX
Reviewed by:
Hussein H. Abusaad, P.E
Senior Project Manager
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written approval of Terracon Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical