Bank One-LR031007CONCRETE COMPRESSIVE STRENGTH TEST
Report Number: 94031289.0056
Service Date: September 25, 2003
'lFerracan
8901 Carpenter Fr~/, Ste #100
Dallas, Texas 75247
(214) 630-1010
Client: Bank One Texas NA
Attn: Danny Buckner
8111 Preston Suite 250
Dallas TX 75225
Report Date: October 07, 2003
Project: Bank One - Coppell TX
616 North Denton Tap Rd
Coppell, TX
Project Number: 94031289
**REVISED
Material Information
Specified Strength: 3500 psi ~ 28 Days
Batch Time: Plant: 2
Supplier: LDJ Ready Mix
Truck No: 725
Mix I.D. No.: 60A
Water Added Onsite Before Test:
Field Test Data
Test
Ticket No: 35404
5 Gallons
Sample Information
Sample Time: 5:15am Date Cast: September 25, 2003
Technician: Roy T. Montgomery
Weather Conditions: Clear
Accumulative Yards: 30
Placement Method: Direct Discharge
Sample Locations: 28' N of SE entrance, 15' W of E curb
Placement Location: Paving, SE corner of project
Result Specification Test Method
Slump, inches: 6.00 ASTM C-143
Air Content, %: 4.8 ASTM C-231
Concrete Temperature, o F: 81 ASTM C-1064
Ambient Temperature, o F: 69 ASTM C-1064
Plastic Unit Weight, pcf:
laborator~ Test Data
Age at Maximum Compressive
Set Specimen Diameter Area Date Test Load Strength
No. ID (inches) (sq. inches) Tested (days) (lbs) (ps[)
1 I 6.00 28.27 10/02/2003 7 77,980 2,760
1 2 6.00 28.27 10/02/2003 7 80,870 2,860
Average 2,810
1 3 10/23/2003 28
1 4 f 0/23/2003 28
Comments: Not tested for plastic unit weight.
NOTE: **This report was REVISED by changing the Specified Strength from 4000 psi ~ 28 Days
to 3500 psi ~ 28 Days.
Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive
strength samples.
Technician: Roy T. Montgomery
Report Distribution:
(1) Bank One Texas NA
(1) City of Coppell TX
(1) Aguirre Building Systems
(1) City of Coppell TX
Reviewed by:
HBC/Terracon
Hussein H. Abusaad, P.E.
Senior Project Manager
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods This report is exclusively for the use of the client
indicated above and shall not be reproduced except in full without the written approval of Terracon Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.