Loading...
Bank One-LR031006CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94031289.0033 Service Date: September 5, 2003 'lFerracan 8901 Carpenter Frwy, Ste #100 Dallas, Texas 75247 (214) 630-1010 Client: Bank One Texas NA Attn: Danny Buckner 8111 Preston Suite 250 Dallas TX 75225 Report Date: October 06, 2003 Project: Bank One - Coppell TX 616 North Denton Tap Rd Coppell, TX Project Number: 94031289 Material Information Specified Strength: 3000 psi @ 28 Days Batch Time: 2:18pm Supplier: LDJ Truck No: 500 Mix I.D. No.: 50 Plant: 724 Field Test Data Test Slump, inches: Air Content, %: Concrete Temperature, o F: Ambient Temperature, o F: Plastic Unit Weight, pcf: Laboratoq/ Test Data Result 5.50 1.3 93 95 Ticket No: 116005 Sample Information Sample Time: 3:40pm Date Cast: September 5, 2003 Technician: Melvin L. Searles Weather Conditions: Partly cloudy, hot & humid Accumulative Yards: 5 Placement Method: Direct Discharge Sample Locations: Pier D/4.2 Placement Location: Pier D/4.2 Specification 3-5 Set Specimen Diameter Area Date No. ID (inches) (sq. inches) Tested 1 1 6.00 28.27 09/12/2003 1 2 6.00 28.27 09/12/2003 1 3 600 28.27 10/03/2003 1 4 6.00 28.27 10/03/2003 Test Method ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-1064 Age at Maximum Compressive Test Load Strength (days) (lbs) (psi) 7 71,360 2,520 7 70,670 2,500 Average 2,510 28 93,690 3,310 28 96,520 3,410 Average 3,360 Comments: Not tested for plastic unit weight. Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Technician: Melvin L. Seades Repod Distribution: (1) Sank One Texas NA (1) City of Coppell TX (1) Aguirre BuildJn§ Systems (1) City of Coppell TX Reviewed by: HBC/Terracon Hussein H. Abusaad, P.E. Senior Project Manager The tests were pertormed in general accordance with applicabte ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical Page 1 of 1 MORTAR COMPRESSIVE STRENGTH TEST Report Number: 94031289.0057 Service Date: September 25, 2003 lrerracan 8901 Carpenter FP,W, Ste #100 DaLlas, Texas 75247 (214) 630-1010 Client: Bank One Texas NA Attn: Danny Buckner 8111 Preston Suite 250 Dallas TX 75225 Report Date: October 06, 2003 Project: Bank One - Coppell TX 616 North Denton Tap Rd Coppell, TX Project Number: 94031289 Contractor: Mortar Supplier: Onsite Plant: Specification Requirements: Strength: 750 psi @ 28 Days Test Methods: ASTM C109 ASTM C270 PROJECT DATA Mortar Mix I.D.: Type N Placement Date: 09/25/2003 Batch Time: 1:30pm Time Sampled: 1:35pm By: Michael W. Whyman Weather Conditions: Partly cloudy Temperature (F) - Air 75 °F Mortar: 78 °F Truck No: Ticket No: Sample Size: 2 x 2 x 2 Sample Location: 2'-4' elevation Placement Location: Limestone wainscot on S side of bldg. REPORT OF TESTS Cube Measured Measured Maximum Compressive Marked Slump Flow Date Age Load Strength Set No. (inches) (seconds) Tested (days) (lbs. force) (psi) 1 1 10/02/2003 7 2370 590 1 2 10/23/2003 28 1 3 10/23/2003 28 Services- Obtain a sample of masonry mortar used during construction and cast 2 inch cube specimens for compressive strength determination. Technician: Michael W. Whyman Report Distribution: (1) Bank One Texas NA (1) City of Coppell TX (1) Aguirre Building Systems (1) City of Coppel~ TX Reviewed by: HBC/Terracon Hussein H Abusaad, PE. Senior Project Manager The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shalt not be reproduced except in full without the written approval of Terracon Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94031289.0061 Service Date: September 27, 2003 'lrerracan 8901 Carpenter Frwy, Ste #100 Dallas, Texas 75247 (214) 630-1010 Client: Bank One Texas NA Attn: Danny Buckner 8111 Preston Suite 250 Dallas TX 75225 Report Date: October 06, 2003 Project: Bank One - Coppell TX 616 North Denton Tap Rd Coppell, TX Project Number: 94031289 Material Information Specified Strength: 3600 psi @ 28 Days Batch Time: 6:12am Plant: 2 Supplier: LDJ Truck No: 724 Mix I.D. No.: 50A Water Added Onsite Before Test: Field Test Data Test Ticket No: 35486 5 Gallons Slump, inches: Air Content, %: Concrete Temperature, o F: Ambient Temperature, o F: Plastic Unit Weight, pcf: Sample Information Sample Time: 7:30am Technician: Tom Cleaver Weather Conditions: Cloudy Accumulative Yards: 10 Placement Method: Direct Discharge Sample Locations: See attached sketch Placement Location: Approach S of bank Result Specification Test Method 5.75 ASTM C-143 5.1 ASTM C-231 85 ASTM C-1064 73 ASTM C-1064 Date Cast: September 27, 2003 Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Test Load Strength No. ID (inches) (sq. inches) Tested (days) (lbs) (psi) 1 1 6.00 28.27 10/04/2003 7 76,280 2,700 1 2 6.00 28.27 10/04/2003 7 74,210 2,620 Average 2,660 1 3 10/25/2003 28 1 4 10/25/2003 28 Comments: Not tested for plastic unit weight. Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Technician: Tom Cleaver Report Distribution: (1) Bank One Texas NA (4) City of CoppelJ TX (1) Aguirle Building Systems (1) Oily ol Coppell TX Reviewed by: HBC/Terracon Hussein H Abusaad, P.E Senior Project Manager The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusfvely for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical Page 1 of ~ I'erracan Consulting Engineers & Scientists