Loading...
Bank One-LR030912CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94031289,0014 Service Date: August 14, 2003 ']rerracon 8901 Carpenter Frwy, Ste #180 DalJas, Texas 75247 (214) 630-1010 Client: Bank One Texas NA Attn: Danny Buckner 8111 Preston Suite 250 Dallas TX 75225 Report Date: September 12, 2003 Project: Bank One - Coppell TX 616 North Denton Tap Rd Coppell, TX Project Number: 94031289 Material Information Specified Strength: 3000 psi @ 28 Days Batch Time: 10:12am Plant: 02 Supplier: LDJ Ready Mix Truck No: 723 Mix I.D. No.: 50A Ticket No: 34742 Sample Information Sample Time: 12:15pm Date Cast: August 14, 2003 Technician: Eddie A. Elrod Weather Conditions: Partly cloudy Accumulative Yards: 10 Placement Method: Direct Discharge Sample Locations: Piers- C/8, C.5/8, C.9/8, E/9 Placement Location: Piers- See Report #94031289.0013 Note: The wrong mix was put in piers, Structural Engineers said to use if air was B/T 4-6%. Field Test Data Test Result Specification Test Method Slump, inches: 5.50 Air Content, %: 4.4 Concrete Temperature, o F: 88 Ambient Temperature, o F: 86 Plastic Unit Weight, pcf: Laboratorl/ Test Data Age at Set Specimen Diameter Area Date Test No. ID (inches) (sq. inches) Tested (days) 1 1 6.00 28.27 08/21/2003 7 1 2 6.00 28.27 08/21/2003 1 3 6.00 28.27 08/28/2003 1 4 6.00 28.27 09/04/2003 1 5 6.00 28.27 09/11/2003 1 6 6.00 28.27 09/11/2003 ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-1064 Maximum Compressive Load Strength (lbs) (psi) 66,170 2,340 7 62,160 2,200 Average 2,270 14 71,490 2,530 21 74,190 2,620 28 87,330 3,090 28 86,890 3,070 Average 3,080 The tests were performed in general accordance with applicable ASTM. AASHTO. or DOT test methods This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon. Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indioative of the properties of other apparently similar or identical materials 'll'erracan CONCRETE COMPRESSIVE STRENGTH TEST Client: Bank One Texas NA Project Number:94031289 Report Number: 94031289.0014 Comments (cont'd): Comments: Not tested for plastic unit weight. Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Technician: Eddie A. EIrod Report Distribution: (1) Bank One Texas NA (1) City of Coppell TX (1) Aguirre Building Systems (1) City of Coppell TX Reviewed by: HBC/Terracon H~saad, P.E Senior Project Manager The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials CONCRETE COIV1PRESSIVE STRENGTH TEST Report Number: 94031289.0016 Service Date: August 14, 2003 'lrerracan 8901 Carpenter Frwy, Ste #100 Dallas, Texas 75247 (214) 630-1010 Client: Bank One Texas NA Attn: Danny Buckner 8111 Preston Suite 250 Dallas TX 75225 Report Date: September 12, 2003 Project: Bank One - Coppell TX 616 North Denton Tap Rd Coppell, TX Project Number: 94031 289 Material Information Specified Strength: 3000 psi @ 28 Days Sample Information Sample Time: 1:45pm Date Cast: August 14, 2003 Technician: Eddie A. Elrod Batch Time: 1:38pm Plant: 02 Weather Conditions: Cloudy Supplier: LDJ Accumulative Yards: 10 Truck No: 731 Ticket No: 34744 Placement Method: Direct Discharge Mix I.D No.: 50 Sample Locations: Piers- B/3.6, B.1/7.1, B/5.6, B.1/1.9 Water Added Onsite Before Test: 10 Gallons Placement Location: Piers- See Report #94031289.0013 Field Test Data Test Result Specification Test Method Slump, inches: 6.00 ASTM C-143 Air Content, %: 0.9 ASTM C-231 Concrete Temperature,o F: 88 ASTM C-1064 Ambient Temperature, o F: 88 ASTM C-1064 Plastic Unit Weight, pcf: Laboratory Test Data Age at Maximum Compressive Set Specimen Diameter Area Date Test Load Strength No. ID (inches) (sq. inches) Tested (days) (lbs) (psi) 1 1 6.00 28.27 08/21/2003 7 83,890 2,970 1 2 6.00 28.27 08/21/2003 7 81,880 2,900 Average 2,940 1 3 6.00 28.27 08/28/2003 14 91,750 3,240 1 4 6.00 28.27 09/04/2003 21 100,840 3,570 1 5 6.00 28.27 09/11/2003 28 96,100 3,400 1 6 6.00 28.27 09/11/2003 28 105,680 3,740 Average 3,570 The tests were performed Jn general accordance with applicable ASTM. AASHTO. or DOT test methods This report is exclusively for the use of the client indicated above and shall not be reproduced except Jn full without the written approval of Terracon Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently simiJar or identical materials 'irerracan CONCRETE COMPRESSIVE STRENGTH TEST Client: Bank One Texas NA Project Number:94031289 Report Number: 94031289.0016 Comments (cont'd): Comments: Not tested for plastic unit weight. Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Technician: Eddie A. Elrod Report Distribution: (1) Bank One Texas NA (1) City of Coppell TX (1) Aguirre Building Systems (1) City of Coppell TX Reviewed by: HBC/Terracon Hussein~H Abusaad, PE Senior Project Manager The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon Test results transmitted herein are only applicable to the actuar samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials