Loading...
Bank One-LR030822CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94031289.0014 Service Date: August 14, 2003 'lrerracon 8901 Carpenter Frwy, Ste #100 Dallas, Texas 75247 (214) 630-1010 Client: Bank One Texas NA Attn: Danny Buckner 8111 Preston Suite 250 Dallas TX 75225 Report Date: August 22, 2003 Project: Bank One - Coppell TX 616 NoAh Denton Tap Rd Coppell, TX Project Number: 94031289 Material Information Specified Strength: 3000 psi @ 28 Days Batch Time: 10:12am Plant: 02 Supplier: LDJ Ready Mix Truck No: 723 Mix I.D. No.: 50A Field Test Data Test Slump, inches: Air Content, %: Concrete Temperature, o F: Ambient Temperature, o F: Plastic Unit Weight, pcf: Laboratory Test Data Result 5.50 4.4 88 86 Set Specimen Diameter Area No. ID (inches) (sq. inches) 1 2 3 4 5 6 Ticket No: 34742 Sample Information Sample Time: 12:15pm Date Cast:August 14, 2003 Technician: Eddie A. Eirod Weather Conditions: Padly cloudy Accumulative Yards: 10 Placement Method: Direct Discharge Sample Locations: Piers- C/8, C.5/8, C.9/8, E/9 Placement Location: Piers- See Report #94031289.0013 Note: The wrong mix was put in piers, Structural Engineers said to use if air was B/T 4-6% Specification Test Method Date Tested 6.00 28.27 08/21/2003 6.00 28.27 08/21/2003 ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-1064 08/28~2003 Age at Maximum Compressive Test Load Strength (days) (lbs) (psi) 7 66,170 2,340 7 62,160 2,200 Average 2,270 14 09/04/2003 21 09/11/2003 28 09/11/2003 28 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written appr°val °f Terrac°n Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical Page 1 of 2 'lrerr can CONCRETE COMPRESSIVE STRENGTH TEST Client: Bank One Texas NA Project Number:94031289 Report Number: 94031289.0014 Comments (cont'd): Comments: Not tested for plastic unit weight. Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Technician: Eddie A. Elrod Repod Distribution: (1) Bank One Texas NA (1) City of Coppell TX (1) Aguirre Building Systems (1) City ol Coppell TX Reviewed by: n Hussein H. Abusaad, PE. Senior Project Manager The tests were performed in general accordance with applicable ASTM, AASHTO, °r DOT test rneth°ds This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials CONCRETE COMPRESSIVE STRENGTH TEST Report Number: 94031289.0016 Service Date: August 14, 2003 ']l'erracan 8901 Carpenter Frwy, Ste #100 Dallas, Texas 75247 (214) 630-1010 Client: Bank One Texas NA Attn: Danny Buckner 8111 Preston Suite 250 Dallas TX 75225 Report Date: August 22, 2003 Project: Bank One - Coppell TX 616 North Denton Tap Rd Coppell, TX Project Number: 94031289 Material Information Specified Strength: 3000 psi @ 28 Days Batch Time: 1:38pm Plant: 02 Supplier: LDJ Truck No: 731 Ticket No: 34744 Mix I.D. No.: 50 Water Added Onsite Before Test: 10 Gallons Field Test Data Test Result Slump, inches: 6.00 Air Content, %: 0.9 Concrete Temperature, o F: 88 Ambient Temperature, o F: 88 Plastic Unit Weight, pcf: Laboratory Test Data Sample Information Sample Time: 1:45pm Date Cast: August 14, 2003 Technician: Eddie A. Elrod Weather Conditions: Cloudy Accumulative Yards: 10 Placement Method: Direct Discharge Sample Locations: Piers- B/3.6, B.1/7.1, B/5.6, B.1/1.9 Placement Location: Piers- See Report #94031289.0013 Specification Test Method Set Specimen Diameter Area Date No ID (inches) (sq inches) Tested 1 1 6.00 28.27 08/21/2003 1 2 6.00 28.27 08/21/2003 1 3 08/28/2003 1 4 ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-1064 Age at Maximum Compressive Test Load Strength (days) (lbs) (psi) 7 83,890 2,970 7 81,880 2,900 Average 2,940 14 09/04/2003 21 1 5 09/11/2003 28 1 6 09/11/2003 28 The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods This report is exclusively for the use of the client indicated above and shall not be reproduced except in full without the written approval of Terracon Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical Page 1 of 2 CONCRETE COMPRESSIVE STRENGTH TEST ~ 'll'erracan Client: Bank One Texas NA Project Number:94031289 Report Number: 94031289.0016 Comments (cont'd): Comments: Not tested for plastic unit weight. Services - Obtain samples of fresh concrete at the placement locations, perform required field tests and cast compressive strength samples. Technician: Eddie A. Elrod Report Distribution: (1) Bank One Texas NA (1) City of Coppell TX (1) Aguirle Building Systems (1) Cily of Coppell TX ~acon ev,ew d ,: Hus H Abusaad, P.E Manager The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods This report is exclusivety for the use of the client indicated above and shall not be reproduced except iR full without the written approval of Terracon Test results transmitted herein are only applicable to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical materials