Loading...
CF-Pump Station-CS 810410L. A. Fuess & Co. Incorporated structura[ engineers 10 April 1981 Frank Rasor Hogan & Rasor, Inc. 2730 Republic Bank Tower Dallas, Texas 75201 RE: Coppell Water Storage Tank Dear Frank: In order to provide zero buoyancy of the proposed 500,000 gallon water storage tank under flood conditions with an outside water level of 446.0 (mean sea level elevation), one of the following conditions must be met: A. The tank as presently designed would not be bouyant if an inside water level of at least 14'-3" is maintained; The footing at the base of the tank can be increased from 9" to 7'-6" wider than the tank walls and the thickness increased from 1'-0" to 1'-6", which will provide zero buoyancy with the tank empty. Please advise us of any necessary changes in the tank design; and call us if you have any questions. Yours truly, Larry ~es-~, P.E. President ~ LF/am LF8032 3603 Lemmon Avenue at Lee Pa~kv, ay DaJJas, lexas 7.5219 telephone 214/522-1991